Pepperl+Fuchs KCD2-RR2-Ex1 Manuel utilisateur

ISO9001
2
Functional Safety
Resistance Repeater
KCD2-RR2-Ex1(.SP)
PROCESS AUTOMATION
MANUAL

With regard to the supply of products, the current issue of the following document is applicable: The General Terms of
Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical
Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the
supplementary clause: "Expanded reservation of proprietorship"
Functional Safety KCD2-RR2-Ex1(.SP)

Functional Safety KCD2-RR2-Ex1(.SP)
Content
2019-11
3
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Content of this Document. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4 Standards and Directives for Functional Safety . . . . . . . . . . . . . . . . . . 7
3 Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 System Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Assumptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.3 Safety Function and Safe State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4 Characteristic Safety Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.5 Useful Lifetime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4 Mounting and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.1 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.1 Proof Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6 Maintenance and Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7 List of Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

2019-11
4
Functional Safety KCD2-RR2-Ex1(.SP)
Introduction
1 Introduction
1.1 Content of this Document
This document contains information for usage of the device in functional safety-related
applications. You need this information to use your product throughout the applicable stages
of the product life cycle. These can include the following:
• Product identification
• Delivery, transport, and storage
• Mounting and installation
• Commissioning and operation
• Maintenance and repair
• Troubleshooting
• Dismounting
• Disposal
The documentation consists of the following parts:
• Present document
• Instruction manual
• Manual
• Datasheet
Additionally, the following parts may belong to the documentation, if applicable:
• EU-type examination certificate
• EU declaration of conformity
• Attestation of conformity
• Certificates
• Control drawings
• FMEDA report
• Assessment report
• Additional documents
For more information about Pepperl+Fuchs products with functional safety,
see www.pepperl-fuchs.com/sil.
Note!
This document does not substitute the instruction manual.
Note!
For full information on the product, refer to the instruction manual and further documentation
on the Internet at www.pepperl-fuchs.com.

Functional Safety KCD2-RR2-Ex1(.SP)
Introduction
2019-11
5
1.2 Safety Information
Target Group, Personnel
Responsibility for planning, assembly, commissioning, operation, maintenance,
and dismounting lies with the plant operator.
Only appropriately trained and qualified personnel may carry out mounting, installation,
commissioning, operation, maintenance, and dismounting of the product.
The personnel must have read and understood the instruction manual
and further documentation.
Intended Use
The device is only approved for appropriate and intended use. Ignoring these instructions
will void any warranty and absolve the manufacturer from any liability.
The device is developed, manufactured and tested according to the relevant safety standards.
Use the device only
• for the application described
• with specified environmental conditions
• with devices that are suitable for this safety application
Improper Use
Protection of the personnel and the plant is not ensured if the device is not used according
to its intended use.

2019-11
6
Functional Safety KCD2-RR2-Ex1(.SP)
Introduction
1.3 Symbols Used
This document contains symbols for the identification of warning messages
and of informative messages.
Warning Messages
You will find warning messages, whenever dangers may arise from your actions.
It is mandatory that you observe these warning messages for your personal safety and in order
to avoid property damage.
Depending on the risk level, the warning messages are displayed in descending order
as follows:
Informative Symbols
Action
This symbol indicates a paragraph with instructions. You are prompted to perform an action
or a sequence of actions.
Danger!
This symbol indicates an imminent danger.
Non-observance will result in personal injury or death.
Warning!
This symbol indicates a possible fault or danger.
Non-observance may cause personal injury or serious property damage.
Caution!
This symbol indicates a possible fault.
Non-observance could interrupt the device and any connected systems and plants,
or result in their complete failure.
Note!
This symbol brings important information to your attention.

Functional Safety KCD2-RR2-Ex1(.SP)
Product Description
2019-11
7
2 Product Description
2.1 Function
This isolated barrier is used for intrinsic safety applications.
It transfers resistance values of RTDs or potentiometers from hazardous areas to safe areas.
The device supports 2-, 3-, or 4-wire technique depending on the required accuracy.
The input card of the control system measures the same load as if it were connected directly
to the resistance in a hazardous area.
The device is mounted on a 35 mm DIN mounting rail according to EN 60715.
2.2 Interfaces
The device has the following interfaces.
• Safety relevant interfaces: input and output
2.3 Marking
2.4 Standards and Directives for Functional Safety
Device specific standards and directives
System-specific standards and directives
Note!
For corresponding connections see datasheet.
Pepperl+Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
KCD2-RR2-Ex1(.SP) Up to SIL 2
Functional safety IEC/EN 61508, part 1 –7, edition 2010:
Functional safety of electrical/electronic/programmable electronic
safety-related systems (manufacturer)
Functional safety IEC 61511-1:2016+COR1:2016+A1:2017
EN 61511-1:2017+A1:2017
Functional safety –Safety instrumented systems for the process
industry sector (user)

2019-11
8
Functional Safety KCD2-RR2-Ex1(.SP)
Planning
3 Planning
3.1 System Structure
3.1.1 Low Demand Mode of Operation
If there are two control loops, one for the standard operation and another one for
the functional safety, then usually the demand rate for the safety loop is assumed to be less
than once per year.
The relevant safety parameters to be verified are:
• the PFDavg value (average Probability of dangerous Failure on Demand)
and the T1value (proof test interval that has a direct impact on the PFDavg value)
• the SFF value (Safe Failure Fraction)
• the HFT architecture (Hardware Fault Tolerance)
3.1.2 High Demand or Continuous Mode of Operation
If there is only one safety loop, which combines the standard operation and safety-related
operation, then usually the demand rate for this safety loop is assumed to be higher
than once per year.
The relevant safety parameters to be verified are:
• the PFH value (Probability of dangerous Failure per Hour)
• Fault reaction time of the safety system
• the SFF value (Safe Failure Fraction)
• the HFT architecture (Hardware Fault Tolerance)
3.1.3 Safe Failure Fraction
The safe failure fraction describes the ratio of all safe failures and dangerous detected failures
to the total failure rate.
SFF = (s + dd) / (s + dd + du)
A safe failure fraction as defined in IEC/EN 61508 is only relevant for elements or (sub)systems
in a complete safety loop. The device under consideration is always part of a safety loop but
is not regarded as a complete element or subsystem.
For calculating the SIL of a safety loop it is necessary to evaluate the safe failure fraction
of elements, subsystems and the complete system, but not of a single device.
Nevertheless the SFF of the device is given in this document for reference.

Functional Safety KCD2-RR2-Ex1(.SP)
Planning
2019-11
9
3.2 Assumptions
The following assumptions have been made during the FMEDA:
• Failure rate based on the Siemens standard SN 29500.
• Failure rates are constant, wear is not considered.
• External power supply failure rates are not included.
• The safety-related device is considered to be of type A device with a hardware fault
tolerance of 0.
• The device will be used under average industrial ambient conditions comparable
to the classification "stationary mounted" according to MIL-HDBK-217F.
Alternatively, operating stress conditions typical of an industrial field environment similar
to IEC/EN 60654-1 Class C with an average temperature over a long period of time
of 40 ºC may be assumed. For a higher average temperature of 60 ºC, the failure rates
must be multiplied by a factor of 2.5 based on experience. A similar factor must be used
if frequent temperature fluctuations are expected.
• The application program in the programmable logic controller (PLC) is configured
to detect underrange and overrange failures.
• The device do not has a fault bus.
SIL 2 Application
• The device shall claim less than 10 % of the total failure budget for a SIL 2 safety loop.
• For a SIL 2 application operating in low demand mode the total PFDavg value
of the SIF (Safety Instrumented Function) should be smaller than 10-2,
hence the maximum allowable PFDavg value would then be 10-3.
• For a SIL 2 application operating in high demand mode the total PFH value
of the SIF should be smaller than 10-6 per hour, hence the maximum allowable PFH value
would then be 10-7 per hour.
• Since the safety loop has a hardware fault tolerance of 0 and it is a type A device,
the SFF must be > 60 % according to table 2 of IEC/EN 61508-2 for a SIL 2 (sub) system.

2019-11
10
Functional Safety KCD2-RR2-Ex1(.SP)
Planning
3.3 Safety Function and Safe State
Safety Function
The device transfers analog signals from the input to the output with a tolerance of 2 % related
to the full signal range.
The attached PLC must recognize a fault when the resistance drops below 15 or rises
above 400 (for Pt100) or above 4 k (for Pt1000).
The switch position of the DIP switch on the device has no influence on the safety function.
Safe State
The safe state of the output is the high impedance state (> 100 k) or the fault state (< 15 ).
Reaction Time
The reaction time for all safety functions is < 20 ms.
Note!
See corresponding datasheets for further information.
Ce manuel convient aux modèles suivants
1
Table des matières
Autres manuels Pepperl+Fuchs Répétiteur

Pepperl+Fuchs
Pepperl+Fuchs KFD0-CS 54 Series Manuel utilisateur

Pepperl+Fuchs
Pepperl+Fuchs KFD0-CS .50 Series Manuel utilisateur

Pepperl+Fuchs
Pepperl+Fuchs KFD2-VR4-Ex1.26 Manuel utilisateur

Pepperl+Fuchs
Pepperl+Fuchs KFD0-CS-Ex1.50P Manuel utilisateur

Pepperl+Fuchs
Pepperl+Fuchs KFD0-CS 50 Series Manuel utilisateur

Pepperl+Fuchs
Pepperl+Fuchs HiD2035 Manuel utilisateur