To Order Model ICN77000 SERIES CONTROLLER (Specify Model Number)
PROCESS CONTROLLER, DUAL DISPLAY FOR THERMOCOUPLE, RTD, VOLTAGE OR CURRENT INPUTS IN A 1/16 DIN CASE
Ordering Ex mples:
1.) ICN77R322-C2 is a NEMA 1 bezel case with 1.75 inch round hole ounting adaptor, dual SSR control outputs and RS232 co unications output.
2.) ICN77330 is a NEMA 12 bezel case with 1/16 DIN ounting and single Relay control output.
3.) ICN77544-A2 is a NEMA 4 bezel case with 1/16 DIN ounting, dual pulse control outputs, and a SPST 3A Alar relay.
Model No. Description
ICN77 Dual displays for si ultaneous display of easured value and setpoint.
Selectable preset tune, adaptive tune, autotune, PID, PI, PD control odes. The
dual control outputs can be configured for a variety of control and alar
applications such as heat, heat/cool, heat/alar , cool or cool/alar . The ra p to
setpoint feature allows the user to define the rate of rise to setpoint, ini izing
ther al shock to the load during start-up. Maxi u ra p ti e 99.59 (HH.MM),
Soak: 00.00 to 99.59 (HH.MM),Da ping: 1 to 8 in unit steps. Input types
J,K,T,E,R,S,B,N,J-DIN°C, RTD 100Ω 0.00385, 100Ω & 1kΩ 0.00392, 0 to 20 A,
4 to 20 A, 0 to 100 V, 0 to 1V, 0 to 10Vdc. Alar 1 output includes SPST relay,
3A @ 120Vac, 3A @ 240Vac.
NOTE: The Controller ust be ordered co pletely configured. Options are not field installable.
[ ] CASE TYPE
R3 NEMA 1, 1.89 x1.89" (48 x 48 ) bezel and 1.75" ROUND cutout
R5 NEMA 1, 2.1 x 2.1" bezel and 1.75” ROUND cutout
3 NEMA 12 bezel for
1
/
16
DIN panel cutout 45 x 45 (1.772 x 1.772")
5 NEMA 4 bezel for
1
/
16
DIN panel cutout 45 x 45 (1.772 x 1.772")
[ ] CONTROL OUTPUT #1 (Direct or Reverse Acting)
2 Solid State Relay SSR : 1A @ 120/240Vac continuous
3 Relay: For “C” 5A @ 120Vac, 3A @ 240Vac
4 Pulsed 10Vdc @20 A (for use with external SSR)
5 Non-Isolated 1 to 10Vdc or 0-20 A @500Ω ax
[ ] CONTROL OUTPUT #2 (Direct or Reverse Acting)
0 Insert “0” if second output is not desired
2 Solid State Relay SSR: 1A @ 120/240Vac continuous
3 Relay: For “C” 5A @ 120Vac, 3A @ 240Vac
4 Pulsed 10Vdc @20 A (use for external SSR)
Model No. Description cont.
[ ] OPTIONAL OUTPUTS
*none (no entry required)
-A2 SPST relay, 3A@ 120Vac, 3A @ 240Vac (Alar 2)
-C2 Isolated RS232, 300 to 19.2k baud
-C4 Isolated RS485, 300 to 19.2k baud
-PV Isolated Analog Output
-RSP Re ote Setpoint Selection
[ ] POWER SUPPLY
*90 to 240 Vac/dc, 50 to 400Hz (no entry required)
NEMA 1/UL Type 1: Intended for indoor use, to provide a degree of
protection against contact with the enclosed equip ent and against li ited
a ount of falling dirt.
NEMA 4/UL Type 4: Intended for indoor use, to provide a degree of
protection against splashing water, windblown dust and rain, and hose
directed water and unda aged by the for ulation of ice on the enclosure.
Testing-Hosedown:Enclosure is subjected to a strea of water fro a
hose which has a 1" dia eter nozzle and which delivers at least 65 gallons
per inute fro a distance of 10 to 12 feet for a ini u of 5 inutes.
NEMA 12/UL Type 12: Intended for indoor use, to provide a degree of
protection against circulating dust, falling dirt, and dripping non-corrosive
liquids. Testing-Drip:Enclosure is subjected to a drip pan which produces
both splashing and dripping. Testing-Atomized ater:Enclosure is
subjected to a spray of ato ized water by using a nozzle that produces a
3" round dia eter spray, 12" fro enclosure. The air pressure is at 30psi.
For harsh environ ents, we reco end installation of the controller for
square panel cutouts.