NewMar SilverLeaf RV-C Control System Guide d'installation

2012
Newmar Corporation
October 2011
SilverLeaf RV-C Control System
Training Manual


Page 1
Newmar SilverLeaf RV-C Control System Operation/Set-UP Manual
SCREEN ACCESS
Please be aware that not all of the following screens are available to
the end user!
Some configuration screens require a password for access. Password
protected screens contain control settings that should only be
changed by qualified individuals! Changing these control settings to
an improper setting can adversely affect the operation of the control
system and may cause damage to the coach!
The following is a list of the control and system status screens available on the Newmar
SilverLeaf Control System Touch Screen Display.
SYSTEM SPLASH SCREEN
The Splash Screen is displayed momentarily on
system power up. This screen can also be
selected for display as one of the screen saver
selections found in the monitor configuration.

Page 2
HOME SCREEN
Every control function can be accessed by
pressing one of the Buttons on the Home
Screen. The Home Screen also displays system
status and warnings in order of priority. The
following items are displayed and/or controlled
from this screen:
HOME SCREEN WITH FLOOR HEAT OPTION
BUTTON FUNCTIONS
Home Button –Pressing this Button returns
you to the Home screen from the other
control screens. The Home Button is not
highlighted and is only operational from the
other screens.
AC Power Button –Pressing this Button
selects the AC Power Screen. (see AC Power
Screen)
DC Power Button –Pressing this Button
selects the DC Power Screen. (see DC Power
Screen)
Genset Button –Pressing this button selects
the Genset Screen. (see Genset Screen)
Water Button –Pressing this button selects
the Water Control Screen. (see Water
Control Screen)
Climate Button –Pressing this button
selects the Climate Control Screens. (see
Climate Control Screen)
Temp Button (Standard Control) Pressing
the Temp Button selects a screen that
displays the outside ambient temperature.
(see Temp Screen)
Floor Button (Floor Heat Option) When the
Floor Heat option is installed, the Floor
Button will be displayed in place of the
Temp Button. Pressing the Floor Button
selects the Floor Heat Control Screen. This
button is only displayed if the control
system is configured for floor heat. (see
Floor Heat Control Screen)
Features Button –Pressing this button will
select the Features Screens. (see Features
Screens)

Page 3
Genset Button (Top Center) –Pressing this
button will manually start and stop the
generator. The button indicator is
highlighted when the generator is running.
This button works the same as the Dash and
other remote switches.
AUTOFILL Button –Pressing this button will
turn on the Auto Fill feature. The button
indicator is highlighted when the Auto Fill is
on.
PUMP Button –pressing this button will
turn the Water Pump on and off. The
button indicator is highlighted when the
pump is powered.
AUTOGEN Button –Pressing this button will
select the AGS screens. The button indicator
is highlighted when the Auto Charger is
enabled. (see AGS Screens below)
Block Heater Button –Pressing this button
toggles the Block Heater relay on/off. The
button indicator is highlighted yellow when
the load is being shed and blue when on.
STATUS DISPLAYS
Overall System Status - “OK” if no errors or
warnings are present.
Warnings and Errors will be displayed in this
area in order of priority.
Date/Outside Temperature/Time –The
system date, outside temperature and time
are displayed in this area.
Tank Status –The Fresh, and Holding tanks
status is displayed as a percentage of “Full”.
Both a bar graph representation and a
numerical percentage are displayed.
DC Voltage –Both the House Battery
voltage and the Chassis Battery Voltage are
displayed. There is also a Lightning Bolt icon
that will illuminate when the isolator relay
(Charge Bridge) is energized and connecting
both battery systems together.
AC Power Source, Voltage and Current –The
AC Power Source
(Shore/Generator/Inverter), as well as, the
Voltage and Current (Amperage) for both
AC power legs are displayed.

Page 4
AC POWER SCREENS MAIN AC POWER SCREEN
The AC Power Screen displays the AC Power
Source, Line Voltage and Current (Amperage)
usage, as well as, the AC Line Frequency (Hz).
The Ac Power Source is displayed for Shore
Power; Generator or Inverter Power. The AC
Amperage values are displayed both numeri-
cally and with horizontal bar graphs. The AC
Voltage values are displayed numerically. The
AC Line Frequency is displayed in Hertz (Hz).
This screen also displays the maximum charge
draw amps setting value, as well as, the inverter
status. The Load Shed Management screen is
selected from the Load Shed Button located on
this screen. The Inverter can also be turned on
and off from this screen, via the blank button to
the right of the Inverter Status display.
AC POWER SCREENS LOAD (SHED) MANAGEMENT SCREEN
The Load Management Screen displays the
Shore Power Phase setting (Single Phase 30
Amps and less Service, Dual Phase 50 Amp
Service) and allows you to change between the
phase selections using the Change Button. The
current Amp draw is displayed for both legs on
this screen. The Load Status screen is selected
from the Loads Button. The Load Settings
Screen is selected from the Settings Button.
AC POWER SCREENS LOAD STATUS SCREEN
The Load Status Screen displays the electrical
Shed status of all the AC powered devices that
are controlled by the control system. This
screen also displays the AC voltage and
amperage usage for both power legs

Page 5
AC POWER SCREENS LOAD SETTING SCREEN 1
The first Load Setting screen configures the
following settings:
Phase Detection Manual / Automatic
Set to Manual for standard Transfer Switch.
Set to Automatic for RV-C Transfer Switch.
A RV-C Transfer Switch has the capability of
automatically detecting Dual Phase (240 VAC)
50 Amp AC power based on the available AC
power source.
Default Phase Single
Phase / Dual Phase
Selects the default Phase setting for the Load
Shedding function.
Capacity - Single Phase
(Amperage)
This setting sets the Load Shedding Amperage
value for the Single Phase selection.
Capacity Dual Phase (Amperage)
This setting sets the Load Shedding Amperage
value for the Dual Phase selection. This
should normally be set 50 Amps.
AC POWER SCREENS LOAD SETTING SCREEN 2
The second Load Setting screen configures the
following settings:
Capacity - Dual Phase
(Amperage)
This setting sets the Load Shedding Amperage
value for the Dual Phase selection. This
should normally be set 50 Amps.
Load Shedding Enabled / Disabled
Load Shedding Enabled allows the control
system to shed (turn off) system configured
AC powered devices in order to maintain a
maximum phase capacity AC amperage usage.
Generator Settling Enabled / Disabled
This setting should be set to Enabled for
proper Auto Gen operation.
Charger 1 Shedding Enabled / Disabled
This setting determines if the Battery Charger
should be shed (turned off) with the other
Load Shedding devices.

Page 6
DC POWER SCREENS MAIN DC POWER SCREEN
The Main DC Power Screen displays the Inverter
/ Charger status and allows access to the
Magnum Setting Screens
The Battery Icon has a vertical bar graph that
indicates the battery charge level. The battery
voltage value is displayed directly below the
icon. The arrows between the Battery and
Inverter Icons indicate the direction of the DC
current flow. The DC current (amperage) value
is displayed below the arrows. The Inverter/
Charger status is displayed inside the Inverter
Icon.
DC POWER SCREENS MAGNUM SETTINGS SCREEN 1
The first Magnum Setting screen configures the
following settings:
Inverter Status On / Off / Standby
Charger Status On / Off /
Standby
Max Charging Current
( Amperage)
This is the maximum amount of current the
charger can output.
Load Sense Power
( Wattage)
This is the Power Level (Search Watts Setting)
required to activate (wake up) the inverter.
DC POWER SCREENS MAGNUM SETTINGS SCREEN 2
The second Magnum Setting screen configures
the following settings:
Charger Status On / Off /
Standby
Max Charging Current
( Amperage)
This is the maximum amount of current the
charger can output.
Load Sense Power
( Wattage)
This is the Power Level (Search Watts Setting)
required to active (wake up) the inverter.
Max Charger Rate (Percentage)
This is the maximum % of AC current
(amperage) used to recharge the batteries.

Page 7
DC POWER SCREENS MAGNUM STATUS SCREEN
The DC Power (Settings) Magnum Status Screen
displays the following Status Values:
Magnum Model/Version
This value is read from the inverter via the
Inverter Module.
Battery Temperature
This value is read from the inverter battery
temperature sensor via the Inverter Module.
Internal Temperature
This value is read from the inverter via the
inverter Module.
FET Temperature
This value is read from the inverter via the
Inverter Module.
DC POWER SCREENS MAGNUM ADVANCED SETTINGS SCREEN ACCESS
The Password Access Screen is displayed to
provide access to advanced system
configuration screens. The advanced
configuration screens contain control settings
that should only be changed by qualified
individuals. Changing these control settings to
an improper setting can adversely affect the
operation of the control system and may cause
damage to the coach.
DC POWER SCREENS MAGNUM ADVANCED SETTINGS SCREEN 1
The Magnum Advanced Settings Screen has the
following Configuration Values:
Low Voltage Shutdown ( DC Voltage)
This setting is the low DC Voltage trigger point
that will turn off the Inverter.
Battery TypeFlooded / Gel /
AGM / AGM2
This should be set to match the physical
battery type.
Battery Rating (AH)
This should be set to match total house
battery power capacity
Equalization Volts ( DC Voltage)
This setting should match the manufacturer
setting for the battery type.

Page 8
DC POWER SCREENS MAGNUM ADVANCED SETTINGS SCREEN 2
The Magnum Advanced Settings Screen has the
following Configuration Values:
Low AC Volts ( AC Voltage)
This setting is the low AC Voltage (Brown Out)
trigger point that will turn off the charger and
turn the inverter on.
Absorption Volts (DC Voltage)
This is the DC Voltage that will be output
when the charger is in Absorption Mode.
Absorption Time (Hr)
This is the amount of time that the charger
will stay in Absorption Mode.
Float Volts (DC Voltage)
This is the DC Voltage that will be output
when the charger is in Float Mode.
GENSET SCREEN
The Genset Screen displays the current
Generator Status and control system run time.
Note: The system generator run time can be set
to match the physical generator hour meter
using the OnmiScope Service Tool.
The Start and Stop Buttons allow you to
manually start and stop the generator. The
Clear AGS Button allows you to clear the AGS
Safety Lockout flag to reset the Auto Gen
function.