MULTI MEASURING INSTRUMENTS MPR-601W Manuel utilisateur

Thank you for purchasing our model MRP-601W Digital Power Recorder.
Before use the instrument, read this instruction manual thoroughly and operate it correctly.
Keep this instruction manual carefully to take out whenever you need.
MULTI MEASURING INSTRUMENT CO.,LTD.
Akihabara Murai Bldg. 7F, 1-26 Kanda Sakuma-cho,
Chiyoda-ku, Tokyo, 101-0025 Japan
TEL: 81-3-3251-7013 FAX: 81-3-3253-4278
URL: http://www.multimic.com/
E-mail: multi@multimic.com
Digital Power Recorder
MPR-601W
Instruction
Manual

APPENDIX
Thank you for purchasing MPR-601W Digital Power Recorder.
Please read the appendix carefully along with the instruction manual.
●Regarding USB flash drive used on MRP-601W:
One 4GB USB Memory Stick is included as a standard accessory.
Use this memory stick, as there might be possibility that the logging (measurement record)
cannot be done by other USB memory.
USB flash drive made with flash memory, called semiconductor memory.
The semiconductor memory is deteriorated every time wring data; therefore, USB flash drive
has a limit to the number of writing. The longevity of USB flash drive depends on
manufactures, products, individual differences, and usage. Generally, its limit is
approximately 2,000 to 10,000 times.
To extend the life of the USB, in MPR-601W, write to the USB memory together as a single
batch of 50 pieces data logging. If using USB flash drive of a limit of 2,000 times memory,
total 100,000 pieces (2,000×50) logging data can be stored.
If USB flash drive, which has been used for a long time is used on the logging mode, the
logging might be suspended. To avoid unexpected suspension, use never-used USB flash
drive for a long-time measurement on the logging mode.

~ 1 ~
・・・CAUTION FOR INSTRUCTION MANUAL・・・
●Carefully read this instruction manual and comprehend the contents completely before
using the instrument.
●Keep this instruction manual carefully, as it would not be reissued.
●Cannot guarantee the safety for the use other than the original applications of this
instrument and provided in this instruction manual.
●Follow the instructions about the safety in this manual by all means.
●The contents of this manual are subject to change without notice due to the development
of specifications & functions of the instrument in the future.
●There may be the differences between the display of the instrument mentioned in this
instruction manual and the actual instrument.
●The drawings in this manual may have been omitted partially and or been abstracted.
●Although trying to make assurance doubly sure, please inform us through the dealers if
you find any suspicious point, error and or omission in this instruction manual.
●It is prohibited to reprint and or to copy this instruction manual in all or partially without
permission.
●Read carefully the guarantee regulations at the final page.
●"MicrosoftR" & "WindowsR" are the trade marks registered by Microsoft Corporation in
U.S.A. and other countries.
The names of corporations & merchandise are their trade marks or the registered trade
marks.

~ 2 ~
Contents
Cautions for Instruction Manual 1
Table of Contents 2
Safety Summary 3
Cautions for the operation of POWER RECORDER 5
1. Introduction 6
2. Suggestions before use 6
3. Name of each part & function 7
4. Cautions for the measurement 9
5. Wire Connection 10
5.1 Measuring Circuit 10
6. Operation
6.1 Preparation for use 13
1. Install MPR-601W Data Viewer 13
2. Place the Battery 13
3. Prepare USB memory 14
6.2 Operation Procedure
1. Power Switch on 15
2. Setting for measuring conditions 16
3. Measurement 18
4. Management for memory(logging data) 21
5. Import Logging data to PC 23
7. Specifications
7.1 Basic Specification 25
7.2 Function Specification 26
7.3 General Specification 28
7.4 Clamp CT Specification(CT-40PB) 28
7.5 Clamp CT Specification(CT-80PB), option 29
7.6 Composition of Measuring Range 30
7.7 Calculation Formulas 31
8. Repair Service 32
9. Warranty 32

~ 3 ~
SAFETY SUMMARY observe by all means
●To use this instrument safely, read this " SAFETY SUMMARY " carefully and apply
the instrument correctly.
●The CAUTIONs and WARNlNGs which appear on the following pages are stated to
prevent the operator & other people from the dangers and their properties from the
damages beforehand.
△
!WARNlNG : This symbol indicates the contents " Possibilities of the death
or the serious wound can be supposed " caused from
mis-operations.
△
!CAUTION : This symbol indicates the contents " Possibilities of the injury or
only the material damage can be supposed" caused from
mis-operations.
○OPERATION ENVIRONMENT
△
!CAUTION
●Do not use or storage this instrument under the condition of direct rays of the
sun, high temperature & humidity and or condensation, as it may cause the
deformation and or the isolation defect of the instrument.
●Do not use this instrument in the environment influenced by acids, alkalis,
organic solutions, corrosive gas, etc.
●Do not use or storage this instrument where the mechanical vibration can be
directly transmitted, as it may cause defect of the instrument.
●Do not use this instrument nearby the appliances which generate strong
magnetic field and or electrified, as it may cause mis-movement of the
instrument.
●This instrument does not have the water / dust-proof structure. Do not use this
instrument in the environment with a lot of dust and drops of water, as it may
cause defect of the instrument.
○OPERATION CONDITION & CONNECTlON
△
!WARNlNG
●Take notice that the measurement wetted instrument and or wetted hands may
cause the electrical shock accident. If the water gets into the inside of instrument,
stop the operation immediately.
●In case of measurement for active lines, use protection tools such as rubber
gloves, etc. for the safety and to avoid electrical shock.
●Before input the power, confirm that the voltage indicated on AC Adapter of this
instrument conforms with the power supply voltage to be used.
●Do not apply the voltage except the indicated power supply voltage, as it may
cause the damage to the instrument and or the electrical accident.
●To avoid electrical shock and short-circuit accident, connect the voltage sensor
cords with the lines to be measured after cut off the power supply of the lines.

~ 4 ~
○CONNECTIONS FOR SECONDARY CIRCUIT & SENSOR CORDS AND
OPERATION OF ACCESSORIES
△
!DANGER
●Connect the input line of POWER RECORDER to the secondary circuit of
breaker. Firstly, connect the clamp CTs and the voltage sensors to the instrument
body and then, connect them to the active power lines.
●Be careful sufficiently, if the clip of voltage sensor removes and touches the
line between two wires, it will cause short-circuit and or electrical shock
accident.
●Apply Clamp CTs only to the coated cables and do not clamp bare cables, as
it may cause electrical shock.
●If excessive current is applied to CT, it will be heated. Use the CT according to
the rating current, as it may cause electrical shock or fire hazard accident.
●Examine the connection cable sensors(including power supply cable) every
time before use(disconnection,contact defect, break of coating, etc.). If there
is anything unusual after examination, do not use it definitely.
△
!CAUTION
●Do not drop the instrument & CTs and or do not give the strong shock.
●Do not put heavy goods on the cables of instrument, CTs & accessories and
do not modify those cables.
●If dropping CTs and or giving strong shock, the joint surface of CTs are
damaged and it may cause wrong influences to the measurement.
●To avoid defect of CTs due to the break of cables, do not bend and or pull the
cables at the base of CTs. Handle them very carefully.
○HOW TO USE
●When direct voltage input, must have clip to the active power terminals. Be
carefully for short-circuit accident, in case of touch between 2 wires at the time of
clipping.
●Do not apply the voltage to the current input terminals.
The instrument will be damaged.
●The max. input rated voltage is AC500V. The excess input than the rated
voltage will cause the damage of instrument and the human accident.
●To avoid defect of CTs due to the break of cables, do not bend and or pull the
cables at the base of CTs. Handle them very carefully.
△
!CAUTION
●Be careful sufficiently. It may cause the damage of instrument in case of the
over input of voltage & current than each measuring range.
●Do not apply the current to clamp CT more than 600A. It may cause the
damage of CT.
●Use the exclusive AC adapter from the accessories. It may cause the damage
of instrument, in case of the use of other adapters than designated.

~ 5 ~
○CAUTION FOR OPERATING POWER RECORDER
The apparent power & power factor measured by this instrument are calculated by the
operation expressions indicated in this manual and based on the measured voltage(V),
current(I) and active power(P). It may cause the different display value from the instruments
with different operation principle and or different operation expression.
The integral values of this instrument are calculated by the operation on the software from
the measured values of power. It may cause the different integral values from the instrument
with different response speed and or sampling rate, etc.
This instrument is designed exclusively for AC current and cannot measure the line of AC
current mixed with DC.
This instrument has the function for the measurement of frequency but may be unable to do
the correct measurement, in case that the input wave form is extremely distorted.
When using external transformers (PT,CT), it may cause big error in the measurement of
power due to their phase differences. For the accurate measurement, use the PT&CT with
phase difference, as small as possible.
When using PT&CT, use the magnification function and read the measurement value
directly.

~ 6 ~
1. INTRODUCTION
This digital power recorder (Model: MPR-601W) can measure voltage, current, active power
and power factor up to three phase/4 wires(3P4W), which are necessary for the electric
power control and can storage the measured data into USB flash memory. The measured
data on USB flash memory can be stored, processed and managed on your computer.
2. SUGGESTIONS BEFORE USE
After opening the package, check the appearance of the instrument and the accessories.
If you find any damage of appearance and/or the lack of accessories, contact the dealer you
bought from.
[ACCESSORIES]
Voltage Clip Sensor (Red, White, Black, Green, 1 each) 1 set
Clamp-on CT (CT-40PB) (for R Phase, S Phase, and T Phase, 1 each) 1 set
AC Adapter (UIA312-0716) 1 pce.
CD-ROM(MPR-601W Data Viewer) * 1 pce.
Instruction Manual 1 pce.
Hand Carrying Case 1 pce.
USB Memory Stick (4GB formatted) 1 pce.
* MPR-601W Data Viewer can comply with the following software:
windows7 (32 Bit, 64Bit), windows8, windows8.1, windows10

~ 7 ~
3. NAME AND FUNCTION OF THE INSTRUMENT
Battery Compartment: install four AA batteries in correct polarity
AC Jack for ADP(Automatic Data Processing): to connect AC adaptor.
Contrast: for adjustment of light and shade of the LCD. When the display value or letter
can be hardly read, adjust lightness by turning this knob.
Display: 2 lines x 20 letters for the display of configured items for measurement
condition and measured values
LEFT, RIGHT, UP, and DOWN key: to move the cursor on the display and or to see the
values
Input Start and Stop Switch: switch to input the configured measurement conditions and
values into the internal memory
Menu key: press this key to go back to the initial display

~ 8 ~
USB Terminal: to insert USB flash memory (1GB or larger recommended). As USB
flash memory is not build in this instrument, USB flash memory will be needed to store
measured data at each interval when measuring by logging mode.
Current Input Terminals: for current input. Connect clamp CTs.
For single phase/2 wires, use I1 side.
For single phase/3 wires, use I1 and I3 side.
For 3 phase/3wires, use I1 and I3.
For 3 phase/4 wires, use I1, I2 and I3.
Voltage Input Terminals: for voltage input.
Connect red code to V1, white code to V2, black code to V3,and green code to N. For
single phase/2 wires, connect V1 and N. For single phase/3 wires, connect V1, V3 and
N. For 3 phase/4 wires, connect V1, V2, V3 and N.
Power Switch: for power on or off. Power will be turned off automatically 10 minutes
after last operation. When AC adaptor inserted, timer-set set out to on, and logging,
auto-power off won’t
Table des matières
Manuels Équipement d'enregistrement populaires d'autres marques

Strymon
Strymon NIGHTSKY Manuel utilisateur

Mitsubishi Electric
Mitsubishi Electric 16CH DIGITAL RECORDER DX-TL5000U Manuel utilisateur

Tews Technologies
Tews Technologies TPMC465 Manuel utilisateur

Honeywell
Honeywell Excel 50 Manuel utilisateur

SeaLevel
SeaLevel COMM+8.LPCI Manuel utilisateur

Arturia
Arturia AUDIOFUSE STUDIO Manuel utilisateur