
507277-03CPage 8 of 53 mrcool.com
Figure 4.
Inside
OPENINGS
(To Adjacent
Space)
NOTE : Each opening shall have a free area of at least one square inch
per 1,000 Btu(645 mm2per.29 kW)per hour ofthetotal inputratingof
all equipmentin the enclosure,but not lessthan 100 squareinches
(64516 mm
2
ROOFTERMINATED
EXHAUSTPIPE
SIDEWALL
TERMINATED
EXHAUSTPIPE
(ALTERNATE
LOCATION)
FURNACE
).
Air from Outside
(Inlet Air from CrawlSpace and Outlet Air toVentilated Attic)
NOTE: Theinletand outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645 mm
2per 1.17 kW)per
hour of the total inputrating of all equipment in the enclosure.
OUTLET
AIR
INLET
AIR
VENTILATION
LOUVERS
(Forunheated
crawl space)
FURNACE
ROOFTERMINATED
EXHAUSTPIPE
VENTILATIONLOUVERS
(Each end of attic)
SIDEWALL
TERMINATED
EXHAUSTPIPE
(ALTERNATE
LOCATION)
Figure 5.
Outside
Figure 6.
Outside
(All Air Through Ventilated Attic)
NOTE: Theinlet and outlet air openings shall each have a free area of
at least one square inch per 4,000 Btu (645 mm2per 1.17 kW) per hour
of the total input rating of all equipment in the enclosure.
OUTLET
AIR
VENTILATION LOUVERS
(Each end of attic)
INLETAIR
(Ends12"above
bottom)
ROOFTERMINATED
EXHAUSTPIPE
SIDEWALL
TERMINATED
EXHAUSTPIPE
(ALTERNATE
LOCATION)
FURNACE
Figure 7.
Outside
OUTLET AIR
INLETAIR
NOTE: Eachair duct opening shall have afree area of at least one
square inch per 2,000 Btu(645 mm2per .59 kW)perhour of the total
input rating of all equipment inthe enclosure. If the equipmentroom
is located against an outside wall and the air openings communi-
cate directly with the outdoors, each opening shall havea free area
of at least 1 square inch per4,000 Btu (645 mm2per 1.17 kW)per
hour of the total input rating of all other equipment in the enclosure.
ROOFTERMINATED
EXHAUSTPIPE
SIDEWALL
TERMINATED
EXHAUSTPIPE
(ALTERNATE
LOCATION)
FURNACE