Introduction
Panel descriptions
Setup Keypad
—In password entry mode, this keypad switches to next digit.
—Under PARAMETER setting, this keypad switches to the next parameter.
—In password entry mode, this keypad switches to previous digit.
—Under PARAMETER setting, this keypad switches to previous parameter.
—In CODE entry mode, this keypad increases the value
Under PARAMETER setting, this keypad increases the setting value.
—In CODE entry mode, this keypad decreases the value.
—Under the PARAMETER setting mode, this keypad decreases the setting
—Enter or exit the parameter setting mode
—Confirm and save the settings
—These keypads alternately change the display of Genset information,
evenlog, and error code.

[3]
Operational Keypad
【Manual】【Auto】【Off】【Reset】【Light】【Log】
1. Manual:In manual mode, the LCD shows pre-heat function; after pre-heat, engine starts
immediately. If engine fails to start, the GTR-680 returns to the OFF mode. The
pre-heat state may not perform, if parameter setting is disabled. If Pre-fuel is
activated, the fuel outputs before crank procedure.
2. AUTO:In theAuto mode, the GTR-680 starts the engine byATS signal and then the LCD
shows preheat, if pre-heat function is enabled. After pre-heat, the engine starts to
crank. If engine fails to start, the system returns to the pre-heat state and then start
to crank the engine again. For example, if the conditions and parameter settings
are given as follows: 1.stop duration is 10 seconds, crank attempt is 3 times. The
engine cranks for 10 seconds and then rest for 10 seconds, after 3 attempts, the
LCD shows the over crank and triggers the alarm.
3. OFF :Press OFF button stops the engine and then “stop”appears on the LCD. The idle
also appears on the LCD, if the idle function is enabled. After 10 seconds of delay
(depends on the setting), the engine stops completely and idle icon disappears.
RESET:When controller detects malfunction, system goes into protection mode and display
error message on the LCD or LED indicator. Press and hold reset button to clear
faults and reset alarm. The technician can start troubleshooting the faults.
4. Light :Press light button to test LED indicators.
5. LOG : Press LOG button to enter even logs.

[4]
Back Panel:
Pin
Description
Code
2
Battery +
B+
3
Battery -
B-
4
Ground
B_COM
5
Crank output
O_MOTOR
6
Fuel pump output
O_VALVE
7
Stop output
O_STOP
8
Preheat output
O_PREHEAT
9
Alarm output
O_ALARM
10
AUX output 1
O_OUT1 ( N.O.)
11
12
AUX output 0
O_OUT0 ( N.O.)
13
18
AUX input 4
I N.4
19
AUX input 3
I N.3
20
AUX input 2
I N.2
21
AUX input 1
I N.1
22
ATS input
A.T.S.
23
Emergency push button
I N.0
24
Low oil pressure switch
L. O. P.
25
High water temperature switch
H. W. T.
26
N/A
G . Switch

[5]
27
N/A
M . Switch
28
Pickup (RPM)
PICK-UP
29
32
Generator U input
U
34
Generator V input
V
35
Generator W input
W
37
Generator N input
N
41
N/A
R
42
N/A
S
44
N/A
T
46
N/A
N
49
CT 1 input
I 1 ( K )
50
CT 2 input
I 2 ( K )
51
CT 3 input
I 3 ( K )
52
CT Common input
Com.
53
Sensor V+ output
SENSOR V+
54
Sensor Common GND input
COMMON
55
Oil pressure sensor input
OIL PRESS.
56
Oil temperature sensor input
OIL TEMP.
57
Water temperature sensor input
COOLANT TEMP.
58
AUX sensor input
AUXILIARY
J1
CANBUS H
CAN H
J2
CANBUS L
CAN L
J3
CANBUS GND
CAN GND
J4
RS485 D+
RS485 D+
J5
RS485 D-
RS485 D-

[6]
Dimensions

[7]
Functions
Settings
A. System setup
B. Generator voltage
C. Generator current
D. Generator frequency
E. Engine
F. RPM
G. Battery
H. Exercisor
I. Senesors
J. Event logs
K. Error logs
Remote Network:
1. Start, stop, and reset
2. Parameter settings
3. Genset monitoring
4. Error records
Front Panel:
A. Manual / AUTO / OFF / RESET / LIGHT / LOGS
B. Setup Keypads

[8]
Protections
Engine
1.High water temperature
2.Low oil pressure
3.Low coolant
4.Over crank
5.Over speed
6.Low fuel
Generator
1.Over load
2.Short
3.High voltage
4.Low voltage
5.High frequency
6.Low requency
Battery
1.Low voltage
2.High voltage
3.Charge fail
4.Under voltage
.Specifications
DC input:8~36 VDC
Power consumption:Max. 24 W
Voltage measurement:0~500VAC(±0.2 %)
Current measurement:0~5 A * CT ratio (±0.2 %)
Frequency measurement:0~80 Hz(±0.02 %)
Charger or pickup voltage:5 V ~70 V(peak to peak)
Charger or pickup frequency:62 Hz ~5KHz
Relay output:10 A/30 VDC (Output 3 Max. 1 A).
Communication protocol:A. Power environment Communication protocol
B. Modbus master Communication protocol
Working temperature:-10 ℃~60 ℃
Dimension(W * H * D):216 mm * 144 mm * 89 mm
Opening(W * H):210 mm * 138 mm
Weight:1 Kg

[9]
A. Parameter Modify:
1........................................................................................................................
Crank Settings
1. Detect Frequency
Setting:Disable/ Enable
Default:Enable
Description:Check frequency value before cranking the engine.
2. Detect oil press
Setting:Disable/ Enable
Default:Enable
Description:Check oil pressure before cranking the engine.
3. Crank interval
Setting:5~40(seconds)
Default:10
Description:Set the duration of each crank.
4. Crank attempts
Setting:1~10
Default:3
Description:Set total number of crank attempts.
5. Escape up limit
Setting:15~30(Hz)
Default:20
Description:When frequency reaches setting, starter motor disconnects from engine.
6. Engage low limit
Setting:15~30(Hz)
Default:20
Description:If frequency is below setting allows crank procedure
7. OP build up time
Setting:0.2~2.0(Seconds)
Default:0.6
Description:Time delay before disconnecting starter motor after oil pressure switch
activates. (“Detect oil press”must be enabled.)
8. Idle interval
Setting:0~600(Seconds)
Default:0
Description:Duration of engine idle

[10]
2. .........................................................................................................................
Engine Settings
1. PreAdd Fuel Time
Setting:0.0~5.0(seconds)
Default:3
Description:Activates fuel pump before initiating crank procedure.
2. Pre-Heat Time
Setting:0~20(Seconds)
Default:0
Description:Duration of Preheat before crank.
3. Energied to Stop
Setting:1~30(seconds)
Default:10
Description:Output duration for stop solenoid to shut down the engine.
4. Failed to stop
Setting:1~10(Seconds)
Default:2
Description:Time delay before triggering engine shutdown failed alarm.
5. Trip then shut
Setting:Disable/ Enable
Default:Enable
Description:When error occurred, timer starts before shutdown the engine
6. Trip duration
Setting:30~900(Seconds)
Default:30
Description:When error occurred, controller outputs error signal, if error is not cleared
within setting, system initiates Genset shutdown.
7. Cooling time
Setting:0~1250(Seconds)
Default:30
Description:Set engine cooling time for normal Genset shutdown. Engine cooling time is
disabled during malfunction shutdown
8. Freq versus RPM
Setting:0~200
Default:30
Description: To conver RPM from frequency, divide RPM by frequency
(1800rpm/60HZ=30), 30 is the ratio for this setting.
9. Man Inst. Stop