Contents
Introduction
Installation procedure
Mechanical fixing
Identification of terminals TP-10-06 (6 channel)
Identification of terminals TP-06-09 (9 channel)
Mains supply wiring
Output wiring TP-10-06 (6 channel)
Output wiring TP-06-09 (9 channel)
Control wiring - low voltage
Control module settings
Power module functions
Indicator identification
Technical specification TP-10-06 (6 channel)
Technical specification TP-06-09 (9 channel)
Spares and Maintenance
Circuit/Load schedule
1
The Maltings, 63 High Street, Ware, Herts, England. SG12 9AD.
Tel : +44 (0)1920 462121 Fax : +44 (0)1920 466881
e-mail: [email protected]
()
Mode Lighting UK Limited.
TIGER INSTALLATION MANUAL
TP-10-06 and TP-06-09

INTRODUCTION
2
FOUNDATION: Mode was established in 1970 as an Original Equipment
Manufacturer in Hertfordshire, England. Mode designs and manufacturers in
the U.K. Architectural Lighting Control Equipment, Electronic Transformers,
Cold Cathode (Neon) Convertors and many other Electronic Lighting
products. Mode is a subsidiary of a privately owned Holding Company known
as TCL and has four associated electronic companies who together trade as
"The Mode Group".
PREMISES: The Mode Group occupies well equipped factories, offices and
large warehouses in Ware and Hertford, having a commercial area of
2
10,000m . We are situated 40Km from London, 50Km from Heathrow Airport
and 20Km from Stansted Airport.
STAFF: The Mode Group employs more than 140 persons, including thirty
Managers, twenty Engineers and Technicians and over eighty Manufacturing
Staff. There are three Principal Directors and seven other Directors who
between them own all of the issued share capital of the Holding Company.
CLIENTS: The Mode Group has over 500 clients in over 30 countries.
MODE POLICY: To create superior products and to provide our customers
with long term reliability, serviceability and value for money. The Company
does not make economies which are of short term benefit only.
"Reliability from Mode"
The Maltings, 63 High Street, Ware, Herts, England. SG12 9AD.
Tel : +44 (0)1920 462121 Fax : +44 (0)1920 466881
e-mail: [email protected]
()
Mode Lighting UK Limited.

3
INSTALLATION PROCEDURE
1. Remove all packaging.
2. Read instructions and retain for future reference.
3. Fit unit to wall and observe spacing instructions.
4. Remove front plate and store in a safe place.
5. Fit trunking (4" minimum) to desired option.
6. Install all input supply wiring to National Wiring Regulations
and other applicable Regulations.
7. Install all output load wiring to National Wiring Regulations
and other applicable Regulations.
8. Install all low voltage control wiring.
9. Set all switches and jumper links.
10. Ensure that all wiring is tidy and that all ventilation grilles are
unobstructed.
11. Switch on supply to unit.
12. Test all loads are operating correctly.
13. Set "start" address.
14. Program operating system.
15. Test operation.
16. Re-fit front plate.
The Maltings, 63 High Street, Ware, Herts, England. SG12 9AD.
Tel : +44 (0)1920 462121 Fax : +44 (0)1920 466881
e-mail: [email protected]
()
Mode Lighting UK Limited.

MECHANICAL FIXING
Mark positions, drill holes and fit screws to wall, see diagram below.
Dimensions in millimetres.
Hang unit on screws and tighten.
TRUNKING OPTIONS
Connect unit to trunking (4" trunking min.) using up to five 32mm couplers. These are
pitched 48mm apart and centred 62mm from the wall. See diagram below.
OR
Cut notch in trunking 250mm wide as shown in the diagram below. Remove the knockout
plate from the Tiger Power Unit underside and fit trunking to wall, butting up underneath the
Power Unit. Ensure all sharp edges are covered to prevent damage to cable insulation.
WALL
WALL
250
62
39
302
322
Use screws with minimum size No.8 x 1 1/2"
NOTE :
When positioning holes, take into account
that the unit will drop 10mm lower due to
the keyhole fixing slots
452
534
4
48 48 48 48
PLAN VIEW
PLAN VIEW
TRUNKING
TRUNKING
WARNING:
Allow 300mm top and at least 40mm side clearance
between the side flanges and any other object.
This unit must be mounted vertically.

IDENTIFICATION OF TERMINALS TP-10-06 (6 CHANNEL)
5
PHASE INPUT NEONS DMX / SCENARIO
INPUT TERMINALS
ANALOGUE INPUT /
OUTPUT TERMINALS
START ADDRESS
AND FUNCTION SWITCHES
MAINS INPUT
TERMINALS
CHANNEL OUTPUT
TERMINALS
EMERGENCY
TERMINALS
AND MCBÌS

IDENTIFICATION OF TERMINALS TP-06-09 (9 CHANNEL)
PHASE INPUT NEONS DMX / SCENARIO
INPUT TERMINALS
ANALOGUE INPUT /
OUTPUT TERMINALS
START ADDRESS
AND FUNCTION SWITCHES
MAINS INPUT
TERMINALS
CHANNEL OUTPUT
TERMINALS
EMERGENCY
TERMINALS
AND MCBÌS
6

MAINS SUPPLY WIRING
CONNECTION
Connect three live input feeds using wire of between the values stated above and in
accordance with the calculated loadings. The live feeds do not have to be from different
phases. Any combination of phases is acceptable.
Connect Neutral feed using wire of between the values stated above and in accordance
with the calculated loadings.
Connect Earth using wire of between the values stated above and in accordance with the
calculated loadings.
TERMINALS
Three Live phase input terminals (20 amp max.).
One Neutral input terminal (60 amp max.).
One Earth input terminal (60 amp max.).
TERMINAL SPECIFICATIONS
2
Terminal Wire sizes mm Strip length Tightening torque
Stranded Solid mm Nm lb/in
Phase 1 4 - 16 4 - 25 14 1.2 - 1.4 10.6 - 12.3
Phase 2 4 - 16 4 - 25 14 1.2 - 1.4 10.6 - 12.3
Phase 3 4 - 16 4 - 25 14 1.2 - 1.4 10.6 - 12.3
Neutral 10 - 35 10 - 50 17 2.8 - 3.0 21.8 - 26.1
Earth 10 - 35 10 - 50 17 2.8 - 3.0 21.8 - 26.1
7
This unit is to be wired by a suitably qualified electrician in accordance
with National Wiring Regulations and other applicable Regulations.

This unit is to be wired by a suitably qualified electrician in accordance
with National Wiring Regulations and other applicable Regulations.
OUTPUT WIRING TP-10-06 (6 CHANNEL)
CHANNEL OUTPUT TERMINALS
6 Live output terminals (10 amp max.).
6 Neutral output terminals (10 amp max.).
One 15 way Earth common bars (10 amp max.).
CONNECTION
Connect loads using wire of between the values stated
below and in accordance with the calculated loadings.
Live, Neutral and Earth wires of the same channel must
pass out through the same coupler.
EMERGENCY OUTPUT TERMINALS
Live monitor output terminals for all channels are
located adjacent to the channel MCB's.
These terminals provide a live monitor for emergency
light fittings. If the channel MCB trips the emergency
fittings switch over to battery operation.
CONNECTION
Connect emergency fittings using wire between the
values stated above and in accordance with the
calculated loadings. Live, Neutral and Earth wires of the
same channel must pass out through the same coupler.
NOTE : The emergency current and channel load
current added together should not exceed the maximum
channel current.
TERMINAL SPECIFICATIONS
2
Terminal Wire sizes mm Strip length Tightening torque
Stranded Solid mm Nm lb/in
Live outputs 1 - 61 - 10 12 0.8 - 1.0 7.1 - 8.9
Neutral outputs 1 - 61 - 10 12 0.8 - 1.0 7.1 - 8.9
Earth outputs 1 - 61 - 10 12 0.8 - 1.0 7.1 - 8.9
Emergency outs 1 - 2.5 1 - 2.5 10 0.5 - 0.7 4.4 - 6.2