Mircom FX-LOCR Manuel utilisateur

LT-6039 Rev 1
Install ation and O peration Manual June 2015
FX-LOC(R)
Local Operating Console
MGC Network
Fire Alarm Control Panel
Normal Condition
June 17, 2015


FX-LOC Local Operating Console
i
Table of Contents
Mass Notification System........................................................................................................ 1
Applicable Standards: UL 2572, UL 864, NFPA 72, ULC.................................................... 1
FX-LOC(R) Local Operating Console ..................................................................................... 2
Module Placement within the FX-LOC(R) .............................................................................. 3
Wiring the Microphone and Selector Panel........................................................................... 4
QMP-5101N Network Paging Wiring for Mass Notification .................................................. 5
RAX-1048TZDS Audio Indication for Mass Notification ....................................................... 6
RAX-1048TZDS Zone Display Module................................................................................. 6
Configuration for Mass Notification....................................................................................... 7
FX-LOC(R) Active................................................................................................................. 9
Reset..................................................................................................................................... 9
FX-LOC(R) Emergency Response Operation ........................................................................ 9
Electrical Specifications.......................................................................................................... 10
Current Drain for Battery Calculations (Example)................................................................. 10
Warranty & Warning Information............................................................................................ 11


FX-LOC Local Operating Console
1
Mass Notification System
The FX-LOC(R) Local Operating Console along with the Mircom FleX-NetTM Network Fire Alarm system facilitates a
Mass Notification System. The FX-LOC(R) provides critical emergency (as well as fire) information to be
communicated within buildings.
The FX-LOC(R) Local Operating Console along with the FleX-NetTM Network Fire Alarm provides compliance with the
Mass Notification System (MNS) UL 2572 requirements.
The MNS portion of a complete Mircom FleX-NetTM Network Fire Alarm system consists of a BBX-FXMNS Enclosure
(see Node 2 in Figure 1). The BBX-FXMNS includes a RAXN-LCD Annunciator which is designated an ACU
(Autonomous Control Unit) and a Master Microphone to provide emergency audio. Below the ACU is another RAXN-
LCD which annunciates the fire alarm system along with a Master Telephone for emergency use. Below this is a
display LCD such as the DSPL-420 or DSPL-2440 which may be used for service; this display will show all messages.
Up to seven FX-LOC(R)s can be connected to any MNS node.
Applicable Standards: UL 2572, UL 864, NFPA 72, ULC
Figure 1: In-Building Mass Notification Sample System
Node 1
Node 2
MIC &
PTT
24V DC
RS-485
SLC
MNS
CACF
FX-LOC (R) (#7)
FX-LOC(R) (#1)
RAXN-LCD used as
part of ACU
(Autonomus Control
Unit)
RAXN-LCD used as
Fire Alarm Display
DSPL-2440 Graphic
Display used for service Up to 7 LOCs are
allowed per node
Central Alarm and Control Facility Mass Notication System
FX-LOC(R)s
(Local
Operating
Control) can
be located on
each oor
IN-BUILDING MASS NOTIFICATION SYSTEM

Mircom
2
FX-LOC(R) Local Operating Console
The FX-LOC(R) consists of a remote main display (RAXN-LCD), an audio indication panel RAX-1048TZDS and a
master paging microphone QMP-5101N within a small compact enclosure. The complete enclosure dimensions are
approximately 15” wide by 25” long by 5.5” deep. Refer to figure below for accurate dimensions. The FX-LOC model
provides a white door and the FX-LOCR model comes with a red door.
Summary of Parts:
1. FX-LOC(R) Enclosure consists of backbox, inner door and outer door.
2. Main Display such as RAXN-LCD.
3. Audio indication panel RAX-1048TZDS.
4. Master paging microphone, model QMP-5101N.
Figure 2: FX-LOC(R) Enclosure
The FX-LOC(R) is made upof a mechanical backbox, a middle metal chassis which the modules are attached toand
afront door with a Lexan window. The backbox may be mounted either surface or flush mount.
Surface Mount
For surface mounting the backbox is secured to thewall using six #8 screws with the six mounting holes provided.
The mounting holes are 8 1/2” apart in width and 9.4” apart in length from the top two mounting holes to the middle
mounting holes and 9” apart in length from the middle two mounting holes. Refer to figure above for all the
dimensions.
Flush Mount
For flush mount, cut out a hole 12 1/2” wide by 23” long and 5” deep. Allow at least 2.5” around the cutout for the lip
of the backbox and door placement. Place the backbox into the hole and the bent edge of the box will frame the wall.
12 1/2” 14 23/32”
5 5/16”
23” 23”
9.4”
9”
24 7/8”
8 1/2”

FX-LOC Local Operating Console
3
Module Placement within the FX-LOC(R)
Once the backbox has been mounted, the RAXN-LCD, the audio annunciation panel and the paging microphone are
fastened to the inner door chassis as shown below. Once the modules have been mounted to the inner door, wire the
modules as instructed in the following sections. After wiring is complete, hook the door with the Lexan window and the
inner door chassis onto the backbox. Refer to figure below for assembly instructions.
Figure 3: FX-LOC(R) Mechanical Assembly
BACKBOX
DOOR WITH
LEXAN WINDOW
INNER DOOR
(ALL MODULES
MOUNT TO THIS
INNER DOOR)
EXAMPLE OF
MOUNTING.
MODULES ARE
MOUNTED FROM
BEHIND TO THIS
INNER DOOR
NOTE: Inner door can be removed, the
backbox and outer door rotated 180
degrees and the inner door is fastened
on the left side.
The front door will now open left to
right while the inner door opens right
to left.

Mircom
4
Wiring the Microphone and Selector Panel
Figure 4: QMP-5101N Network Master Paging Control Module Connections and Terminal Blocks
The interface wiring between the QMP-5101N, ANC-5000 and FX-LOC(R) is as follows:
The maximum wiring run from the QMP-5101N and the ANC-5000 is 20 feet or 6 metres.
MIC+, MIC-, SHLD: 18-22 AWG Twisted Shielded Pair
PTT+, PTT-: 18-22 AWG Twisted Pair
Note: The Common Trouble LED on the QMP-5101N Paging Module is configured as MIC Active for
FX-LOC(R). Replace the Common Trouble label with the MIC Active label and re-configure the Common
Trouble LED using the FleX-Net TM configurator MSW-025.
TO P1 OF RAX-1048TZDS
CABLE CONNECTS TO
RAXN-LCD
FACTORY WIRED
TO MICROPHONE
FROM PREVIOUS
MICROPHONE
OR ANC-5000
TO NEXT
MICROPHONE
(IF LAST MICRO-
PHONE PLACE TWO
EOL 3K9 ohm
RESISTORS HERE
BETWEEN + and -
OF MIC AND PTT
TERMINALS.
This drawing is a
representation of the
terminals. Follow wiring
as labelled. Location of
terminals may vary.

FX-LOC Local Operating Console
5
QMP-5101N Network Paging Wiring for Mass Notification
Figure 5: QMP-5101N Network Master Paging Control Module Wiring to the ANC-5000 Audio
Network Controller Module
JW7
JW8
+ - + -
S - + S - +
S - +S - + L - +
PAGING BUS MIC
PTT
OUT IN
ANC-5000 Audio
Network Controller
Module in the
MNS (ACU)
+
+
-
-
S
PTT MIC
QMP-5101N Network
Master Paging Module
+
+
-
-
S
PTT MIC
QMP-5101N Network
Master Paging Module
Remote
Power
Input
G.A.
Input
IN
RS-485
NOT USED
Wire the Paging Bus
to all other ANC-5000
Audio Network
Controller Modules
OUT to IN. See
document LT-894
for more details.
TWISTED
SHIELDED
PAIR CABLE
TWISTED
SHIELDED
PAIR
CABLE
Jumpers JW7 and JW8
must be installed at all
times.
This connec-
tion to Aux
Power is not
required when
ANC-5000 is
installed in the
Audio Card
Cage
Daisy chain PTT and MIC
to next FX-LOC(R).
At the last FX-LOC(R)
QMP-5101N Paging
Module, connect EOL
resistors (3K9 ohms
value) to + and - of
both the MIC and PTT
terminals.
MNS - ACU FX- LOC(R)

Mircom
6
RAX-1048TZDS Audio Indication for Mass Notification
Connect the RAX-1048TZDS by connecting P1 cable into P2 on the QMP-5101N Master Microphone.
RAX-1048TZDS Zone Display Module
Figure 6: Zone Display Module (RAX-1048TZDS)
Table 1: RAX-1048TZDS Zone Display Module Cable Function
Connector Function
P1 P1 Cable connects to P2 of previous display module QMP-5101N.
P2 P2 is not connected.
Note: The zone display module comes with laser printer-compatible slide-in paper labels for labelling.
P2
P1