Notification Appliances—ET Series Speakers and Strobe Speakers 5
!
CAUTION: Equipment damage hazard. Although UL testing has
verified these products function at 80% of their minimum
rating and 110% of their maximum rating, Johnson Controls
recommends that the voltage applied to these products be
within their rated input voltage range. The application of
improper voltage may result in degraded operation or damage
to these products.
!
CAUTION: Equipment damage hazard. Only the ET-1010 model is
suitable for outdoor use.
To verify that the signaling device is operating at rated voltages, determine the voltage
drop caused by the resistance of the Notification Appliance Circuit (NAC) wiring. Then,
subtract this voltage from both the maximum and minimum power supply and battery
voltages.
Table 1: ET Series Speakers and Strobe Speakers Specifications
Speaker Strobe
Model dBA at 10 Feet Input Strobe Mounting
Number Per UL 14804Voltage Candela Options3
(Rated Watts) (VDC) (cd)
1/8 1/4 1/2 1 2 418 Min Nom Max
ET-1010-R 78 81 84 87 90 93 96 ---- ---- ---- ---- E, F, G, H
ET-1070-R 78 81 84 87 90 93 96 ---- ---- ---- ---- A, D
ET-1080-R 78 81 84 87 90 93 96 ---- ---- ---- ---- C, D
ET-1090-W 78 81 84 87 90 93 96 ---- ---- ---- ---- B
ET-1070-LS-24-VFR 78 81 84 87 90 93 96 20 24 31 15 A, D
ET-1070-LSM-24-VFR 78 81 84 87 90 93 96 20 24 31 152A, D
ET-1070-MS-24-VFR 78 81 84 87 90 93 96 20 24 31 30 A, D
ET-1070-IS-24-VFR 78 81 84 87 90 93 96 20 24 31 75 A, D
ET-1080-LS-24-VFR 78 81 84 87 90 93 96 20 24 31 15 C, D
ET-1080-LSM-24-VFR 78 81 84 87 90 93 96 20 24 31 152C, D
ET-1080-MS-24-VFR 78 81 84 87 90 93 96 20 24 31 30 C, D
ET-1080-IS-24-VFR 78 81 84 87 90 93 96 20 24 31 75 C, D
ET-1090-LS-24-CFW 78 81 84 87 90 93 96 20 24 31 15 B
ET-1090-MS-24-CFW 78 81 84 87 90 93 96 20 24 31 30 B
ET-1090-IS-24-CFW 78 81 84 87 90 93 96 20 24 31 75 B
Notes: 1. The 4 watt rating is only available with 70 VRMS input.
2. The 15 cd models are listed at 15 cd and meet the Americans with Disabilities Act (ADA)
requirement of 75 cd on the axis.
3. Refer to Figures 3 through 10 in the
Mounting
section of this document.
4. UL 1840 measures dBA sound power levels in a reverberant test room.
Table 2: Strobe Current Requirements (amperes)
Rated Average
Current Rated Peak Current Rated Inrush Current