Viewing and Checking of System parameters
Press button once or twice for the display of parameters, press or button to move the cursor
displaying the various parameters as below:
1. Battery Type: Sealed /Wet/ LiFePo4
2. Bulk Voltage:
3. Float Voltage:
4. Time Absorption:
5. LVD Low Voltage Disconnect:
6. T_LVD Time Delay before disconnect:
7. LVR Low Voltage Reconnect:
8. Load Control: Two Programmable Loads for day and two for Night
9. Equ. Equalization Charge: Manual / Auto / Off
10. BL: Back light of display on-time
11. Clear AH: Yes or No
12. USB: charge port On or Off /
13. Night V: setting of solar voltage to define Sun Set and start of night (to off set city light)
14. Float Charge: Y or N: In no Float Charge setting, Controller recharge again when battery voltage drops
below the set Float Voltage for more than 5 minutes.
15. Default: Y or N: Yes will reset all the parameter settings to factory default values.
The programming steps for the above 15 parameters (except 8. Load Control )
Follow the same 5 logical steps:
1. Short presses of button to the list of parameters
2. Short presses of or button to move the cursor to the desired parameter.
3. Long press (5 second) then release to activate the parameter. (flickering)
4. Short presses of or button to change the setting value.
5. Long press (5 second) then release to confirm new setting. (no flickering)
The Load Terminal (Menu 8: Load control)
Caution:
The voltage at the load terminal changes with the voltage of the battery terminal, under LOAD OUT or Day Light
Mode the voltage can be as high as the absorption charge voltage or equalization voltage.
Load Control Programming
[ ] LOAD OUT => Always on Mode
[ ] NLM => Night Light Mode
[ ] DLM => Day Light Mode
Save & Exit => long press ready to save entry and exit from Load Control Programming.
Remark:
The programming procedure is quite different from the other 14 system parameters programming as given in the
preceding section 3 and 4.
A tick in the box [ ] indicates the mode has been programmed, it is possible to have tick in NLM and DLM at the
same time .When no tick is in any of the boxes, no load program has been set.
Only NLM and DLM can be further programmed and once LOAD OUT has been set, you cannot set either NLM or
DLM.