Meanings of faults and corresponding soluons are as follows:
Alarm MeaningTroubleshoong
Bat comfailure Inverter fails to communicate with baery
Check ifthe communicaon cable is correctly installed and if
youhave chosen the correct baery brand on the M Smart
Screen. Ifall is correct but this error persists, please contact
your supplier.
AFCI comfailure Inverter fails to communicate with AFCI module Restart inverter. Ifthe error persists, contact your supplier.
AFCI high PVarcfault is detected
Check each PVstring for correct open circuit voltage and
short circuit current. Ifthe PVstrings are in good condion,
please clear the fault on the M Smart Screen.
1. Check ifthe communicaon cable is connected correctly
and in good condion.
2. Restart inverter. Ifthe fault persists, contact your supplier
1. Check the baery communicaon cable for the correct
pinout on both the inverter and baery.
2. Check ifyouhave chosen an incorrect baery brand.
3. Check ifthere is a fault on the baery's indicator. Ifthere
is a fault, please contact your baery supplier.
Auto test failure Auto test failed Only applied to Italian model
LCD comfailure M Smart Screen fails to communicate with M3
microprocessor
Fwm mismatchFirmware version mismatch between the
microprocessors
Fan stuckCooling fan(s)are stuck
Tripby gfci high Inverter detected leakage current on ACside 1. Check ifthere is a ground fault on the grid and load side.
2. Restart inverter. Ifthe fault remains, contact your supplier.
Tripby dci high
Inverter detected high DC injecon current on grid
port
Restart inverter. Ifthe fault remains, contact your supplier.
1. Check ifeach PVstring is connected correctly.
2. Restart inverter. Ifthe fault remains, contact your supplier.
GFCI module fault GFCI module is abnormal Restart inverter. Iffault sll exists, contact your supplier
Bat volt high Baery voltage too high Check ifbaery voltage exceeds 59.9V, baery voltage
should be within inverter specificaons.
Bat volt lowBaery voltage too lowCheck ifthe baery voltage is under 40V, baery voltage
should be within inverter specificaons.
Bat open Baery is disconnected frominverter Check baery breaker or baery fuse.
Offgrid overload Overload on BACKUP LOADport Check ifload power on the inverter EPSport is within
inverter specificaons.
Offgrid overvoltage BACKUP voltage is too high Restart inverter. Iffault sll exists, contact your supplier
Meter reversed Meter is connected reversely Check ifthe meter communicaon cable is connected
correctly on the inverter and meter side.
Offgrid dcv high
High DC voltage component on EPSoutput when
running off-grid
Restart inverter. Iffault sll exists, contact your supplier.
RSD Acve Rapid shutdown acvated Check ifthe RSD switch is pressed.
PVshort circuit Inverter detected short circuited PVinput
Meter comfailure PVarcfault is detected
Bat Fault Inverter fails to communicate with the meter
Restart inverter. Iffault sll exists, contact your supplier.
Inspect inverters every 6 months for anomalies in operaon, heat, or noise parameters.
Inspect inverters every 6 months to ensure that the radiator of the inverters is not covered by anything. If it is,
stop the inverter and clean its radiator.