LUNATONE DALI Manuel utilisateur

© 2016, Lunatone Industrielle Elektronik GmbH DALI Display
DALI Display 7”
Quick Start Guide
Control Device
DALI Input- and ontroldevice with
7” Display and Touchpanel
Version 1.0.6

DALI Display, Manual V1.0.6 © 2016, Lunatone Industrielle Elektronik GmbH
DALI Display
ontrol Device
Content
1. DALI Display – Features and Installation ......................................................................................... 3
1.1 Intended Use ....................................................................................................................... 3
1.2 Safety Instructions ............................................................................................................... 3
1.3 Features ............................................................................................................................... 3
1.4 Specification ........................................................................................................................ 4
1.5 Installation ........................................................................................................................... 5
2. Elementary Operating Functions ..................................................................................................... 6
3. Extended Operating Functions ........................................................................................................ 9
4. onfiguration and Settings ............................................................................................................ 10
4.1 Design ................................................................................................................................ 12
4.2 Screensaver and Pincode Protection ................................................................................. 13
4.3 Date and Time ................................................................................................................... 14
4.4 Menu Bar ........................................................................................................................... 14
4.5 Site Numbering .................................................................................................................. 14
5. ommissioning .............................................................................................................................. 15
5.1 Adressing/Grouping ........................................................................................................... 15
5.2 Scenes and olor Scenes ................................................................................................... 18
5.3 Sequence (SQ), day-schedules (SDL), week-schedules (SDLL) ........................................... 23
5.4 Human entric Lighting – ircadian daylight progression ................................................ 26
6. Ethernet – Remote ontrol ........................................................................................................... 27
7. System Update .............................................................................................................................. 31
8. ustom design ............................................................................................................................... 32
8.1 Photo of room with integrated luminary control .............................................................. 32
8.2 Room overview of a floor with controllable luminaries .................................................... 32
9. Additional Information and Equipment ........................................................................................ 34
10. Disclaimer .................................................................................................................................. 34
11. Glossary ..................................................................................................................................... 34

DALI Display, Manual V1.0.6 © 2016, Lunatone Industrielle Elektronik GmbH
1. DALI Display – Features and Installation
1.1 Intended se
The DALI Display can be used for commissioning and control of DALI lighting systems. DALI is a
standardized digital protocol for the control of electronic ballasts for lighting systems according to
standard IE 62386. Exclusively ballast with DALI interface may be connected to one of the DALI-lines.
1.2 Safety Instructions
When operating the DALI display the following precautions must be considered:
Each user must carefully read and follow the instructions given in the manual.
The operator must ensure that the wiring instructions and specifications for DALI lines are
considered, the installation of the display must be performed by an qualified technician, who can
perform the required tasks and recognize potential danger due to professional training, knowledge
and experience, in particular the knowledge of pertinent regulations and standards.
Touching the screen with sharp objects can result in damage of the display.
1.3 Features
The DALI Display has connectors for two DALI lines (DALI A, DALI B). This allows installing up to 128
DALI ballasts.
Light control commands are based on DALI Scenes and Groups and are sent to both DALI lines
simultaneously. Scene commands are sent broadcast, group commands only to an individual DALI
group.
There are 16 Scenes and 16 Groups available for both DALI busses:
Number of DALI short addresses: 128
Number of DALI Groups: 16
Number of DALI Scenes: 16
Multi-Master apability: Multiple control devices can be used on the DALI-lines.

DALI Display, Manual V1.0.6 © 2016, Lunatone Industrielle Elektronik GmbH
DALI ommands received on DALI line A are mirrored to DALI line B, this means that control devices
connected to DALI A can also control ballasts on DALI B.
ommands received on DALI B are not mirrored to DALI A, this allows to install controllers that only
affect one of the two DALI busses.
The DALI Display is a commissioning, control and input device for DALI controlled electronic ballasts.
Beside scene and group commands, algorithms for commissioning (addressing, grouping and scene
configuration) and automatic running processes (sequences, schedules and schedule lists) are
provided. Special methods like human centric lighting (circadian daylight trend) and colour control of
RGB-Dimmers is supported with the help of DALI Device Type 8 (DT8) standard.
By naming groups, scenes and automatic processes, custom backgrounds and screen saver image,
the device can be individually adapted to the application. Furthermore custom designed layouts are
offered as a manufacturer service.
The display can be controlled via the 7” touch control panel, but also via remote access through
Ethernet and hence can be operated via browser.
1.4 Specification
type DALI Display 7”
article number 86458626
Rated supply voltage mains adapter (included) 230-240VA
Mains frequency mains adapter 50/60Hz
Rated supply voltage DALI Display 7” 24-48V D (power supply)
or Power over Ethernet (PoE)
Power consumption 10W
Number of DALI lines 2
urrent consumption of each DALI-line 2mA
Ambient temperature 0-50°
Touchscreen size 7”
Touchscreen pixel 800 x 640
olours 64k
Interface 2xDALI, USB, Ethernet
Dimensions L x W x H 200 x 150 x 20 mm
Type of protection IP20
Firmware (last recent version) V104

DALI Display, Manual V1.0.6 © 2016, Lunatone Industrielle Elektronik GmbH
1.5 Installation
The DALI Display does not provide any power supply for the DALI-lines. Therefore an external DALI
power supply (e.g. DALI PS) has to be installed for each DALI-line. The D power supply (PS36V),
which is included in the delivery package, is meant to supply the display only. It is not suitable for the
supply of a DALI-Line. Instead of using a PS36V the display can also be powered via POE.
typical installation

DALI Display, Manual V1.0.6 © 2016, Lunatone Industrielle Elektronik GmbH
2. Elementary Operating Functions
The control of groups and scenes, using the buttons of predefined pages, is summarized under the
term of “elementary operating functions”. There are sites available for recalling scenes as well as for
switching and dimming of groups (unused pages can be disabled in the settings).
1) Recall Scenes
onfiguration OFF-Button (Long Press): Selection of effective range for OFF- md (the setting is valid
for any OFF-Button and does not depend on active site). Up from V1.0.6 the scheduler function can
be selected to be stopped as well as a scene can be recalled by the OFF-Button
Dim P/DOWN
Sent Broadcast or to
individual groups.
(Selectable on the layout
configuration page)
Previous / Next
Page
Displayed pages can be
configured on the layout
configuration page.
Goto SceneX
Additional settings: long
press on button
OFF
Sent Broadcast or to
individual groups.
(Settings: long press
on button)
Settings
Page
Home

DALI Display, Manual V1.0.6 © 2016, Lunatone Industrielle Elektronik GmbH
onfiguration of Scene-Button (Long Press): Selection of Goto Scene, yclic Scene Recall, Start of
Sequences, Schedules or Schedule List. Up from V106 it is possible to start/stop the circadian
function. Due to assigning of special functions to a scene the function can be controlled from another
device that recalls the corresponding scene.
2) Group Control
Dim P/DOWN
Send UP or DOWN
commands as long as the
button is pressed. (Only
available if the group is
ON)
Grou
p ON/OFF
Sends Recall MAX or OFF
to switch group ON / OFF
Previous Next
Page
Displayed pages can be
configured on the layout
configuration page.
OFF
Sent Broadcast or to
individual groups.
(Settings: long press
on button)
Home
This design symbolizes
that the group is OFF
Settings
Page

DALI Display, Manual V1.0.6 © 2016, Lunatone Industrielle Elektronik GmbH
3) 16 Groups - Control and Status Display
4) Cleaning Page (Deactivation of Touchscreen)
Group ON/OFF
Sends Recall MAX or OFF
to switch group ON / OFF
It is also possible to dim
the group by pressing
and holding a group
button.
This design symbolizes
that the group is ON
This design symbolizes
that the
group is OFF
Deactivate the touch
panel for 20 seconds to
clean the screen.

DALI Display, Manual V1.0.6 © 2016, Lunatone Industrielle Elektronik GmbH
3. Extended Operating Functions
Extended operating functions offer additional control methods, which require either a set-up
procedure before usage or a control gear with specific DALI device type (DT8).
1) Automatic Processes (sequences, schedules, schedule lists)
2) Color Control for RGB-devices (DT8-Type: RGBWAF)
On this site a color can be selected and is immediately sent to the selected operating range.
Selection of
sequence,
schedule or
schedule list
Hold the button to open
the pop-up window to
load other processes
Dim P/DOWN
Sent Broadcast or to
individual groups.
(Selectable on the layout
configuration page)
operating range
Short press: ON/OFF operating
range
Selection of operating range
Each group with DT8 (RGB) control gears
or Broadcast can be selected.
Color selection
color information is sent
to operating range
immediately after tipping
on the color
Start/Stop/Pause
control of the selected
process
indicator for running process
This symbol is shown on each site, when
process is active
RGBWAF - Details
Enter PopUp for detailed
settings

DALI Display, Manual V1.0.6 © 2016, Lunatone Industrielle Elektronik GmbH
RGBWAF Details:
For each group which has been identified as DALI DT8 color type RGBWAF and for broadcast the
channels can be configured in detail [allowed range: 0…254, MASK). Furthermore the operating
range can be selected.
4. Configuration and Settings
Via the gear wheel button in the menu bar the setting page can be entered.
The menu “ onfiguration” and the button with the clock-symbol refer to display and layout related
settings, whereas the other menus are either used for commissioning or for activating functions.
Please find a overview of the display-related settings below.
Date, Time &
Timezone
Configuration
Display
Operating Range
Channels
Switch / Dim Operating Range
Table des matières
Autres manuels LUNATONE Panneau de contrôle