LG GVH282PAB Manuel utilisateur

SPECIFICATION for APPROVAL
Rotary Compressor
MODEL: GVH282PAB
Doc. No. LGETH -180704-054
Rev. No. 0
Date Jul. 04. 2018
Page 1 / 24
LG Electronics
Please return one copy on your approval.
Please read this specification thoroughly before installation or operating.
Designed Approved
Sign
Date
APPROVAL
Sign
Date
EMBRITAL

LGETH -180704-054 / Rev. 0LG Electronics
No Date Article Description Writer
Revision History
Contents
1. Specification
1.1 Compressor
1.2 Motor
1.3 Wire Diagram
1.4 Electrical Component
1.5
Performance
Page 2 / 24GVH2 2PAB
1.5
Performance
1.6 Noise, Vibration
1.7 Minimum Starting Voltage
1.8 Voltage Range
1.9 Others
2. Delivered Parts List
3. Operating Limit
4. Label
5. Attachment
5.1 Compressor Drawing
5.2 Accessory Fitting
5.3 Part Drawings
5.4 OLP Characteristic Curve
5.5 Guideline for using R410A

LGETH -180704-054 / Rev. 0LG Electronics
1.Specification
1.1 Compressor
1 Model Name GVH282PAB
2 Compressor Type Hermetic Motor Compressor
3 Compression Type Rotary Type (Rolling Piston Type)
4 Application Refrigeration system (Cooling & Heating)
5 Refrigerant R410A
6 Safety Approval VDE
7 Oil / Oil Charging Amount PVE or Equivalent / 600 cc
8 Displacement 28.2 ㎤ / rev
9 Painting Black Color Paint
10
Net Weight ( Including Oil )
20.1
kg
Page 3 / 24GVH2 2PAB
1.2 Motor
10
Net Weight ( Including Oil )
20.1
kg
11 Suction Tube I.D Ø 12.8 mm
12 Discharge Tube I.D Ø 9.7 mm
Motor Type / Starting Type Single Phase Induction Motor / PSC
Pole / Rated Output 2 Pole / 1,950 Watts
Power Source 220 - 240V~ 50 Hz
Rated Revolution 2,872 rpm
Insulation Class E Class
Windings Resistance
( at 25 ℃ )
Main 1.53 ± 7% [ Ω ]
Sub 2.10 ± 7% [ Ω ]
Locked Rotor Ampere 51 A (At 240V)

LGETH -180704-054 / Rev. 0LG Electronics
1.3 Wiring diagram
1. Electrical Component
Running Capacitor 55 MFD / 400 VAC
Overload Protector INTERNAL TYPE
※Make Sure to connect right way same with the wiring diagram.
Line
Running Capacitor Compressor
C
S
R
O.L.P
Page 4 / 24GVH2 2PAB
1.5 Performance
☞Rated Conditions (ASHRAE-T Condition)
Cond. Temp. : 54.4 ℃( 130 ℉)
Evap. Temp. : 7.2 ℃( 45 ℉)
Return Gas Temp. : 35.0 ℃( 95 ℉)
Liquid Temp. : 46.1 ℃( 115 ℉)
Ambient Temp. : 35.0 ℃( 95 ℉)
Voltage 220V 240 V
Cooling Capacity (-5%↑) [ BTU/h ] 24,200 24,400
[ W ] 7,092 7,150
Power Input (+5%↓) [ Watts ] 2,315 2,335
EER (-5%↑) [ BTU/Whr ]
[ W / W ]
10.45 10.45
3.06 3.06
Running Current [ A ] 10.8 10.1

LGETH -180704-054 / Rev. 0LG Electronics
1.6 Noise, Vibration
Voltage At 240 V
Sound Level [ dB(A) ] 75 Max
Vibration [ µm ] 230 Max
Noise & Vibration Measuring Points
300mm
Page 5 / 24GVH2 2PAB
● Measuring points for specification approval
- Noise : 2 points ( X , Y )
- Vibration : 2 points ( A , B )
● Compressor vibration is measured by a vibration meter which is
contacted compressor A ~ B
● Test Condition :
- Standard Condition (Ps/Pd = 9.12 / 33.45 kg/cm²G)
Microphone
X
Y
300mm
300mm
Microphone
H/4
H/4H/4
H/4
H
B
A

LGETH -180704-054 / Rev. 0LG Electronics
1.7 Minimum Starting Voltage (V2) *note 1
1.8 Voltage Range (V2) *note 1
Cold Start
- Temp. Condition : 35℃
- Balanced pressure : Pd – Ps ≤ 0.5 ㎏f/㎠
Below 187 Volts
at Standard Condition 187 ~ 264 Volts
at Overload Condition 198 ~ 264 Volts
☞ Test Conditions
Standard
Con. Temp (℃)
Eva. Temp (℃)
Return Gas. Temp (℃)
54.4
7.2
35.0
Overload
63.8
10.4
25.0
Page 6 / 24GVH2 2PAB
Leak Tight Pressure
High Pressure Side 32 ㎏f / ㎠ G
Low Pressure Side -
Hydrostatic trength
Pressure
High Pressure Side 170 ㎏f / ㎠ G
Low Pressure Side 69 ㎏f / ㎠ G
Insulation Resistance
( with 500V D.C Mega Tester ) 50 ㏁ Min.
Withstand Voltage At 2,200 V / 1 Sec.
Leakage Current is less than 5 ㎃
Residual Moisture ( Karl Fisher Method ) 60 mg Max.
* Residual Impurities 70 mg Max
*)Each part was measured separately
1.9 Others
Return Gas. Temp (℃)
Ambient Temp (℃)
35.0
35.0
25.0
43.0

LGETH -180704-054 / Rev. 0LG Electronics
2.Delivered Parts List
Parts Name Type ( Model ) EA Parts Dwg. NO. Supply
LG
Compressor GVH282PAB 1 -YES NO
O.L.P INTERNAL TYPE - -YES NO
Cover, Terminal - 1 3550U-L005D YES NO
Gasket - 1 4986UHL004A YES NO
Nut, Common - 1 FAD30241201 YES NO
Washer, Customized - 1 FAF30240201 YES NO
Damper, Rubber - 3 MCQ61847401 YES NO
Sleeve, Damper - 3 4816U-L001G YES NO
Page 7 / 24GVH2 2PAB
※ ) Refer to Attachments ( Accessory Parts Drawings. )
Washer, Plain - - -YES NO
Nut, Hexagon - - -YES NO
Capacitor - - -YES NO
Screw, Earth M4*0.7 ,
Length : Max 6 mm. --YES NO

LGETH -180704-054 / Rev. 0LG Electronics
3. Operating Limit
3.1 Operation Range
Discharge Pressure [ ㎏f / ㎠G ] 42 Max
Suction Pressure [ ㎏f / ㎠G ] 3.0 ~ 13.0
Discharge Pipe Temp. [ ℃] 120 Max.
Motor Coil Temp. [ ℃] 135 Max.
Page / 24GVH2 2PAB
Area A : Normal Operating Zone
Area B : High Density Flow Zone
-During Starting within 3 minutes
Area C : During defrosting & re-starting
-Running time within 3 minutes

LGETH -180704-054 / Rev. 0LG Electronics
Refrigerant Charge Limit Max 2,500g
(Charge limit depends on Oil Dilution Rate**note 2 & accumulator ‘K’)
Liquid Refrigerant Back
System should be designed not to allow the liquid to go back to
compressor which cause knocking noise , current increase or
undesirable vibration and make short compressor life time.
Δ T : Temp. Difference Δ T = Case Bottom Temp.- Condensing Temp.
It must be kept Δ T ≥ 5℃
Pressure Difference
in Operating
The Pressure difference in operating shall be 5.0㎏f/㎠ or more,
but 3 minutes starting excluded.
ON/OFF Operation Each cycle should be at least 6 minutes
(ON Time : at least 3 minute , OFF Time : at least 3 minutes)
3.2 Application Limit
※This guide contains many important safety messages. Always read and obey all safety messages.
You can be killed or seriously injured if you don’t follow instructions.
Page 9 / 24GVH2 2PAB
(ON Time : at least 3 minute , OFF Time : at least 3 minutes)
Pressure Difference
at Starting
When starting, discharge pressure is balanced with suction pressure.
( Pd – Ps ≤ 0.5 ㎏f/㎠ )
Tilt in Operation The allowable tilt of the compressor in operation shall be 5˚ or less.
System Accumulator
The Accumulator volume should be enough to cover 50% of
maximum system refrigerant volume.
Ratio coefficient ‘K’ should be over 0.6(heating system) or 0.4(cooling
system)
Effective Volume of Accum. × Specific gravity of Refrigerant
K = --------------------------------------------------------------------------
Charged Weight of Refrigerant
※ Effective Volume of Accumulator = 580 ㎤
※ Specific Gravity of Refrigerant (R410A) = 1.085 g/㎤ ( at 20℃ )
If coefficient “K” does not meet recommendation, refrigerant system
must check liquid back phenomenon at accumulator.
Protecting Reverse
Operation
The compressor must be operated by proper voltage in accordance
with the frequency without reverse revolution condition. The reverse
revolution condition can be avoided by just keeping right order of
phase supplied power source.

LGETH -180704-054 / Rev. 0LG Electronics
Frequency Range Rated Frequency ±2%
Pipe Stress Don’t allow any force on discharge & suction pipe .
The piping stress must be less than 300㎏f/㎠at starting and stopping.
And less than 153㎏f/㎠at running.
Oil Level It must be checked oil level by the compressor with
sight glass we supply. And oil level must be kept over
guide line level **note 3. at any condition.
Protection device Refrigeration system must has the compressor protection device like
over pressure, high temperature, sensing locked pump in the controller.
When starting & running fail by abnormal overload, controller must be
able to cut off power of compressor before motor burn out.
An earth terminal should be installed to prevent electrical accidents.
3.2 Application Limit
Page 10 / 24GVH2 2PAB
Pump down
refrigerant
If pump down time is too long, compressor can be damaged due to
excessive temperature increase or poor lubrication.
Guideline of pump down process.
- Time : less than 30 seconds
- Suction Pressure : It should not run under below 1㎏f/㎠G.
And before closing a service valve, compressor running for more than 5
minutes is recommended.
※If gas charge amount of refrigerant specified is exceeded,
both parties should discuss the matter to determine compressor specification.
(accumulator volume, lubricating oil amount) and system specifications (crank case
heater, oil separator , additional accumulator, etc)
This document will be effective after LG’s receipt with your authorized signature.
When design modification is approved by the customer , the current document is
unavailable.
* Effective Period of This Document *
Table des matières
Manuels Compresseur populaires d'autres marques

Emerson
Emerson Copeland Scroll Digital HLR Series Mode d’emploi

Drawmer
Drawmer 1968 MKII Manuel utilisateur

Badger Air-Brush
Badger Air-Brush X-Air 80-8 Mode d’emploi

Omnitronic
Omnitronic CL-166 Manuel utilisateur

Scheppach
Scheppach HC24V Instructions de montage

Ingersoll-Rand
Ingersoll-Rand centac C950 Manuel technique