Lennox 21L07 Manuel utilisateur

©2021 Lennox Industries Inc.
Dallas, Texas, USA
INSTALLATION
INSTRUCTIONS FOR
WIRELESS SENSOR AND
REPEATER KITS
TEMPERATURE / RELATIVE HUMIDITY
SENSOR
CATALOG # 21L07
WIRELESS REPEATER
CATALOG # 21L09
Table of Contents
...........................................2
Overview........................................................................3
Sensor (21L07)..............................................................5
Sensor – Power Options..................................................................6
Sensor – S-Bus Wired Installation Setup.........................................6
Sensor – Wired Standalone / NCP Setup........................................6
Sensor – Operation with BACnet Network (M3/M4 ONLY)............12
Sensor – Wiring Troubleshooting...................................................14
Sensor – Wireless Installation Setup.............................................15
Sensor – Wireless Standalone ......................................................16
Sensor – Placement and Conrming Location (Test) ....................17
Sensor – Wireless Checkout / Troubleshooting.............................18
Sensor – Signal Strength Alert Indication ......................................18
Sensor – Low Battery Indication....................................................18
Sensor – After Hour Override (AHO) .............................................18
Sensor – Data Verication .............................................................19
Sensor – Network Removal and Reset .........................................19
Repeater (21L09).........................................................20
Repeater – 24VAC Line Power......................................................20
Repeater – Wireless Installation Setup..........................................20
Repeater – Signal Strength Alert Indication...................................21
Repeater – Placement and Conrming Location (Test).................21
Repeater – Network Removal and Reset ......................................22
Repeater and Sensor Placement Requirements......23
FCC Compliance Statement ......................................26
FCC RF Exposure Information .................................26

2
CAUTION
Electrostatic discharge can aect electronic
components. Take precautions during unit
installation and service to protect the unit’s
electronic controls. Precautions will help
to avoid control exposure to electrostatic
discharge by putting the unit, the control
and the technician at the same electrostatic
potential. Neutralize electrostatic charge by
touching hand and all tools on an unpainted
unit surface before performing any service
procedure.
IMPORTANT
Improper installation, adjustment, alteration,
service or maintenance can cause personal
injury, loss of life, or damage to property.
Installation and service must be performed by
a licensed professional installer (or equivalent)
or a service agency.
Shipping and Packing List
Please note that wireless temperature sensor and
wireless repeater are sold separately.
Wireless Temperature / Relative Humidity
Sensor (21L07) 106924-01
Package 1 of 1 contains:
1 - Wireless Sensor
4 - AA Lithium batteries
2 - Wall anchors
2 - Screw #6 X 1.25 SMS
1 - Warranty and Installation instruction
Wireless Repeater (21L09) 106926-01
Package 1 of 1 contains:
1 - Wireless Repeater
2 - Wall anchors
2 - Screw #6 X 1.25 SMS
1 - Warranty and Installation instruction

3
Overview
The wireless system employs the following
components:
M4/W4 Wireless Gateway System:
• Plenum-rated Bluetooth Low Energy (BLE)
antenna which will assist in boosting the sig-
nal from to Lennox CORE Unit Controller to:
»CORE Service App
»Wireless room sensors (wireless
mode)
»Wireless repeaters
• Ecient design allows for use in vertical and
horizontal applications
• Return air mounted antenna reduces signal
loss from roof and connected to gateway sys-
tem via coax cable.
Wireless Repeater (21L09)
• Used to “repeat” signal to sensors
• Increases eective range
• Up to ve repeaters can be used per rooftop
unit
• Powered by external 24VAC only
• Used in wireless application only
• Locking captive screw
Wireless Temperature / Relative Humidity
Sensor (21L07)
• TMP / RH / After hours override
• Unit powered by either 24VAC or four AA bat-
teries. Batteries provided but not installed.
Greater than two year battery life using AA
Lithium batteries.
NOTE: Please allow for a 45 minute adjustment
period on 24VAC powered sensors on
temperature readings
NOTE: Battery life of greater than two years is
subject to the sensor operating under
good signal coverage. If signal is weak or
the RTU is o for long periods the signal
strength LED will be on and the battery
will be depleted
• Wireless or S-BUS
• Locking captive screw
• Up to ve sensors can be used per rooftop
unit

4
Lennox®CORE Service Application Used for
adding Sensors and Repeaters)
• Connects to the Lennox®CORE Unit Control-
ler via the wireless gateway (W4)
• Pairs with a simple button press (requires
physical access)
• Used for installation of wireless sensors
and repeaters, service, and maintenance of
Model L rooftop units

5
Sensor (21L07)
RESET button
BEACON enable button
BATTERY status LED
SIGNAL strength LED
Air Circulation Vents
CAPTIVE screw
After Hour Override
(AHO) enable switch
LCS-5030 TMP/RH SENSOR
CATA LOG # 21L07
Figure 1. Wireless Sensor Buttons and
Indicators
Figure 2.
(Factory Defaults) Label
NOTE: Changed switch settings only take af-
fect after a sensor power reset. Remove
24VAC or battery power after switch set-
ting changes.
NOTE: Switch settings are 1 = ON and 0 = OFF
Example:
S1 switch 6 (MODE)
ON = 1 – STAND ALONE
OFF = 0 – NETWORK/BAS (DEFAULT)
NOTE: S2 switches 4 and 5 are for future use
and have not aect on sensor operations.

6
• Battery Power: When the wireless sensor is
powered by the included four AA Lithium bat-
teries the sensor has a typical operational life
of two years.
• Line Power: When the wireless sensor is
powered by external line power (24VAC).
Battery Compartment
(4 AA Lithum Batteries)
Figure 3. Wireless Sensor Battery
Compartment
S-Bus connections can be used with M1-8 (IMC),
M2, M3 and M4 Unit Controllers. The sensor can
be used in the following congurations:
• By itself with a controller (Wired Standalone)
• In a network with a Lennox Network Control
Panel (NCP)
• In a network with a third party BACnet Con-
troller – M3/M4 Unit Controllers ONLY.
Standalone operation is a consist of (1) Unit
Controller and (1) sensor without a building
automation system (BAS). See Figure 4. Wired
Standalone for wiring connection detail example.

7
NCP
The sensor can also function with a unit controller
with an NCP/L-Connection System. The 21L07 is
compatible in standalone or with an NCP with the
following unit controllers:
• M1-8
• M2
• M3
• M4
See Figure 5. NCP Wiring Conguration on page
8 for wiring connection detail example..
RTU BUS
Address = 2
S-BUS OPERATION IN STANDALONEMODE
SENSOR BUS
Address = 2
NOTE: Wireless sensor S-Bus address MUST
match RTU S-Bus address.
DRAIN WIRE
NOTE: Use 22AWG, one twisted pair shield cable
(100% aluminium shield with strain wire with Teflon jacket.
Recommend Lennox Catalog numbers 94L63, 27M19, 68M25
or Beld Type 88761 or equivalent.
Figure 4. Wired Standalone

8
NCP
RTU
S-Bus Address = 1
RTU
S-Bus Address = 2
RTU
S-Bus Address = 3
RTU
S-Bus Address = 4
Sensor
S-Bus
Address = 1
S-BUS OPERATIONS WITH NETWORK CONTROL PANEL (NCP)
NOTE: Use 22AWG, 1 twisted pair shielded cable (100% aluminum shield with strain wire with Teflon™
jacket). Recommend Lennox catalog numbers 94L63, 27M19, 68M25 or Belden Type 88761 or
equivalent.
Drain
Wire
Drain
Wire
Drain
Wire
Drain
Wire
Drain
Wire
NOTE: Wireless Sensor S-Bus address MUST match RTU S-BUS address.
Sensor
S-Bus
Address = 2
Sensor
S-Bus
Address = 3
Sensor
S-Bus
Address = 4
Drain
Wire
Drain
Wire
Drain
Wire
Figure 5.

9
NOTE: The following S1 and S2 switches need
to be set before power is applied to the
sensor.
STAND ALONE AND S-BUS
SETTINGS
NETWORK/BAS AND S-BUS
SETTINGS
NOTE: S2 switches 4 and 5 are for future use
and have not aect on sensor operations.
1. Set S1 (switches 1 through 5) for S-BUS Ad-
dress to match the S-BUS address of the
RTU. In operation with an NCP, each RTU
must have a unique address.
NOTE: Lennox M3/M4 unit controllers use a de-
fault S-BUS address of 2. If the sensor
and unit controller are both congured
to use address 2, there is no need to go
through S-BUS setup to change the unit
S-BUS address.
2. Set S1 (switch 6) for Mode to the ON position
to enable STAND ALONE or OFF (factory de-
fault) for NETWORK/BAS.
3. Set S2 (switch 3) Operation Mode to ON, for
wired S-BUS mode.
4. Connect sensor and RTU controller using rec-
ommended wire (two conductor, twisted-pair,
shielded, 22AWG). See Figure 5. NCP Wiring
Conguration on page 8 for further details.
5. For setup with the M4 Unit Controller use the
following procedure:
a. Download the CORE Service app.
b. Apply power to the sensor.
c. Using the CORE Service app, go to the
Rooftop Unit menu and select Network
Integration under Setup.
d. Select the Network Setup Wizard.
e. Select S-Bus / Wireless Sensor under
Network Setup Wizard and select Next.
f. Enter the S-Bus Address and select
Next.

10
g. Select the Control Source as Room
Sensor then select Next.
h. Select CO2 sensor source as Local or
None.
i. Select Relative Humidity Sensor
Source as Network and select Next.
j. Select Temperature Sensor Source
as Network and select Next.
k. Set Occupied Blower Mode as Auto
cycling/Continuous depending on
ventilation need and select Next.
l. Select Backup Mode as None/Wired
Thermostat/Return Air Backup and
then select Next.
m. The summary is displayed and then se-
lect Next after checking the displayed
setting information.
n. Select Finish.
6. For setup with the M3 Unit Controller use
the following procedure:
a. Navigate on the M3 Unit Controller
screen to Setup > Network Integration.
b. Select L-CONNECTION and select
SAVE.
c. Enter the S-Bus address and select
SAVE.
d. Select the Control Mode as Room
Sensor then select SAVE.
e. Select CO2 network sensor source
as NO, then select SAVE.
f. Select Relative Humidity Network
Source as YES, then select SAVE.
g. Select Temperature Network Source
as YES, then select SAVE.
h. Set Occupied Blower Mode as Auto
Cycling/Auto-Continuous 1/2/3 and
select SAVE.
i. Select Backup Mode as None/Wired
Thermostat/ Return Air Backup and
then select SAVE.
NOTE: Lennox recommends selecting backup
mode (Return Air Backup).
j. Finish the wizard and return to the main
menu.
7. For Setup with the M2/M1-8 Unit Control-
lers: Refer to the application manual for
these controllers. Setup will be similar to the
M3 Unit Controller.