MICRO COMPUTER
Digital PID Controller
User' s Manual
K30-SERIES
PID CONTROLLER

75
Preface
Pay attention to the followings!
Safety requirements!
WARNING
CAUTION
Thank you for purchasing the K30 series from Koino.
The K30 series is a precision industrial controller that uses an advanced
2 degree-of-freedom (DOF) algorithm.
The K30 series consists of 5 models, which are K32, K33, K34, K37, and K39.
This manual explains the installation, the functions, the operation,
and the handling of the products.
Please read the manual thoroughly before using the products.
If any difficulties arise while using our products, please call our customer service
at +82-2-2242-1275.
Use the products under the conditions specified in this manual.
Please heed the cautions and warnings listed in this manual.
The contents of the manual may be changed without notice.
The product is designed to be used installed on a control panel.
This manual is copyrighted, and may not be copied in part or in whole without
permission.
The manufacturer takes no responsibility for direct or indirect damages caused by
careless operation or operation under unpredictable or risky environments
Safety requirements are intended to prevent accidents and dangers through the proper use of the products, so
please heed them at all times.
The safety requirements are divided into “cautions” and “warnings”, which indicate the following.
△
!
△
!
Serious injury or death may be caused if instructions are not observed.
Failure to observe these instructions may cause damage to the instrument or some injury to the user.
PID CONTROLLER

76
WARNING
△
!
CAUTION
△
!
1. Use a separate safety device when this product is used to control a device
that could harm lives or expensive property in the event of a malfunction
or a breakdown. (This may cause fires, deaths, or damage to property)
2. Do not use this controller at place where there are flammable or
explosive gas. (It may cause a fire or explosion.)
3. Before turning the power on, please check that wiring is correct to the
number of terminal. (It may cause a fire)
4. Turn off the power during wiring and maintenance to avoid an electric shock.
5. Do not touch the terminals when it is power on.
(It may give an electric shock.)
6. This controller must be mounted on the panel to avoid an electric shock.
7. Do not attempt to disassemble, modify and repair.
1. Please conduct an inspection when water has entered the product.
(It may cause short circuits, fires, and malfunction.)
2. This controller should be used indoors.
(It may shorten the controller’s life or give an electric shock.)
3. Observe the rated voltage and specification.
(It may cause a fire or shorten the controller’s life.)
4. Be careful that any of foreign materials do not inflow into the controller.
(It may cause a fire or malfunction of the controller.)
5. Do not give direct vibration or shock to the controller.
(It may cause of malfunction of the controller.)
6. Do not use chemical detergent or solvent, but use a dry towel in cleaning the controller.
(It may cause an electric shock or a fire.)
7. Please check the polarity of power before wiring and connecting the sensor.
(It may cause an electric shock or explosion.)
PID CONTROLLER

77
Contents
1. Ordering Information
2. Input ranges & Output constitutions
3. Dimensions & Panel cutouts
4. Terminal Arrangements & wirings
5. Ratings & Specifications
6. Name & Function
7. Check points before using
8. Initial installation & Min. operation procedures
9. Flow chart (Parameter structure)
10. Setting mode
11. Alarm(ALARM1, 2) setting
12. Details explanation of primary function
12-1. Auto tuning(AT) function
12-2. Manipulated variable(Mvn) check mode
12-3. Alarm(ALARM1, 2) function
12-4. Retransmission output
12-5. Input function
12-6. SV1, 2 set up control by external contact signal
12-7. Set value “LOCK” function
78
80
82
85
87
88
89
90
91
92
94
96
96
96
97
98
98
99
99
PID CONTROLLER

78
K3 -
①Size
②Control mode
③Optional function
④Power supply voltage
④Power supply voltage
①Size
Code Model Size Remarks
2 K32-SERIES 48(W) × 96(H) × 77(D) No option (Basic function)
3 K33-SERIES 96(W) × 48(H) ×77(D) No option (Basic function)
4 K34-SERIES 48(W) × 48(H) ×99(D) Option : 0, 1, 2, 3
7 K37-SERIES 72(W) × 72(H) ×77(D) Option : 0, 3
9 K39-SERIES 96(W) × 96(H) × 77(D) No option (Basic function)
②Control mode
Code Description Remarks
S SINGLE : Standard Heating or Cooling control
Code Description Remarks
0 100 ~ 240 V AC General-purpose usage
1 24 V AC or DC Alternating or Direct current usage
PID CONTROLLER
1. Ordering Information

79
③Optional function
Model Code Description Remarks
K32, K33
SERIES
Basic function
(0)
RELAY output 1, Alarm output 2,
No function
(Basic function S0x)
SCR(4~20mA), SSR(Voltage pulse) 1,
RET(4~20mA Retransmission output)
D.I(SV2, 3) External input
K34
SERIES
Basic function
(0)
RELAY output 1 (ALARM or MAIN), Basic function +
Option code
(0 : No option)
SCR(4~20mA), SSR(Voltage pulse) 1
1 RET(4~20mA Retransmission), Alarm 2 Ex) K34-S10
3 D.I(SV2, 3) External input, Alarm output 2 Ex) K34-S30
K37
SERIES
Basic function
(0)
RELAY output 1, Alarm output 2, Basic function +
Option code
(0 : No option)
SCR(4~20mA), SSR(Voltage pulse) 1
3 D.I(SV2, 3), RET(4~20mA Retransmission) Ex) K37-S30
K39
SERIES
Basic function
(0)
RELAY output 1, Alarm output 2, Basic function +
Option code
(0 : No option)
SCR(4~20mA), SSR(Voltage pulse) 1,
RET(4~20mA Retransmission)
Example of model building
K34-S00
①Size : 48(W)×48(H)×99(D) ☞“4”
②Control mode : SINGLE ☞“S”
③Optional function : Basic function ☞“0”
④Supply voltage : 100~240V AC ☞“0”
K37-S30
①Size : 72(W) ×72(H) ×77(D) ☞“7”
②Control mode : SINGLE ☞“S”
③Optional function : DI(SV1,2), RET ☞“3”
④Supply voltage : 100~240V AC ☞“0”
K34-S00
K37-S30
PID CONTROLLER

80
2. Input ranges and output constitutions
2-1. Input ranges ※The K30 series has multiple inputs, which may be set and changed by the user.
Input type Signal Setting
Code Temperature range Accuracy Remarks
Thermocouple
(T.C)
K1 -200 ~ 1370
±0.3% of F.S +1Digit
* F.S is max. value to min. value
of each range
* Digit is minimum of display
①0~400℃range : ±10% of
F.S+1Digit
2 -199.9 ~ 999.9
J15 -200 ~ 1000
3 -199.9 ~ 999.9
E16 -200 ~ 1000
4 199.9 ~ 999.9
T 5 -199.9 ~ 400.0
R 6 0 ~ 1700
B ①7 0 ~ 1800
S 8 0 ~ 1700
L17 -200 ~ 900
9 -199.9 ~ 900.0
N 10 -200 ~ 1300
U 11 -199.9 ~ 400.0
C (W5) 12 0 ~ 2300
D (W3) 13 0 ~ 2400
RTD
JPt100
(JIS,KS)
20 -199.9 ~ 500.0
22 -200 ~ 500
Pt100
(DIN,IEC)
21 -199.9 ~ 640.0
23 -200 ~ 640
Voltage
(VDC/mVDC)
0~100 mV DC 33 0 ~ 100mV DC
-10~20 mV DC 32 -10 ~ 20 mV DC
1~5V DC 30 1~5V DC
Current 4~20mA DC 30
When using current input, use
the resistor 250on input
terminal.
How to change the interior switch when using 1~5V input
①Remove the jumper cover
on the underside of the K30,
or remove the rear case.
②Detach the jumper using
tweezers and move it to the
1-2 pins to the left.
③Once this has been com-
pleted, put the jumper
cover back on, as shown
on the picture above.
※When using 1~5V input (30),
the interior jumper switch must be
relocated.
OTHER TYPES 1~5V DC INPUT ONLY
PID CONTROLLER

81
2-2. Output constitutions
The K30 series
has multiple outputs.
※The figure on the left uses the
terminal
socket of K37-S30 as an example
to illustrate the output response
relationship.
General type Setting
number
OUTPUT-1 OUTPUT-2 (ALARM1,2)
Relay output SSR/SCR OUTPUT AL1 AL2 SCR output
SSR output SCR output
K30-Sxx
0 OUT(ON/OFF) ALM1(34-S0x) -
ALARM1 ALARM2 RET
1 ALM1(34-S0x) OUT(PID) -
2 ALM1(34-S0x) - OUT(PID)
3 OUT(PID) ALM1(34-S0x) -
Summary and explanation of output settings
Relay output of ON/OFF control [ Output setting number : 0 ]
This is a simple on/off control, mainly used to control cooling devices.
SSR output of PID control (Voltage pulse) [ Output setting number : 1 ]
This is the most widely used setting, and the default value at the point of manufacture.
SCR output of PID control (4~20mA current output) [ Output setting number : 2 ]
This setting is used mainly with thyristor power regulator (TPR) modules, and is capable of
precision control.
Relay output of PID control [ Output setting number : 3 ]
This is the most cost-efficient method of implementing PID control and is used mainly with
magnetic switches (electric switches). However, it may wear the contact point, and is
difficult to use in places that require fast response.
Alarm output of K34(48´48) basic type(S00)
With the basic model of K34 (48x48), caution is required when using it alarm output. When control output is being used as a relay, the
alarm output will be SSR output (voltage pulse). In this case, use SSR or alarm option (S10, S30) enabled models.
1(SSR) or 2(SCR) 0(ON/OFF) or 3(RELAY)
ALARM1
output
ALARM1
output
Control output Control output
※It is only for K34-S00!
PID CONTROLLER

82
1) K32 (48×96 mm) Dimensions
45±0.5
92±0.5
Min. 20
Min. 30
K32 / K33 (48×96)
Panel cutouts
(Unit : mm)
2) K33 (96 ×48 mm) Dimensions
3) K34 (48×48 mm) Dimensions
(Unit : mm)
45-0
+0.5
45-0
+0.5
Min. 17
Min. 17
K34 (48×48) Panel cutouts
3. Dimensions and panel cutouts