Product Description
DU0/5 and DU0/25 Differential Pressure Sensors
Application
Differential pressure sensors with power output DC 0 V to 10 V for
measuring the pressure or differential pressure in ventilation and air
conditioning systems.
The sensors convert the measured pressure/differential pressure into
a proportional voltage signal between DC 0 V and 10 V.
The voltage signal can be used directly for closed-loop control and/or
display.
■DU0/5 has three adjustable pressure ranges: 0 mbar to 1 mbar,
0 mbar to 3 mbar or 0 mbar to 5 mbar.
■DU0/25 has three adjustable pressure ranges: 0 mbar to 10 mbar,
0 mbar to 16 mbar or 0 mbar to 25 mbar.
Content Page
Important Information Regarding Product Safety ..................................................................................................2
Item........................................................................................................................................................................3
Technical Data.....................................................................................................................................................3
Dimensions..........................................................................................................................................................3
Connection...........................................................................................................................................................4
Installation..............................................................................................................................................................4
Commissioning ......................................................................................................................................................6

APage 2 / 6
Product DescriptionDU0/5, DU0/25
Datasheet 1.50-22.025-01-EN Issue 2010-07-22
Important Information Regarding Product Safety
Safety Instructions
This data sheet contains information on installing and commissioning the product "DU0/5, DU0/25".
Each person who carries out work on this product must have read and understood this data sheet. If
you have any questions that are not resolved by this data sheet, you can obtain further information
from the supplier or manufacturer.
If the product is not used in accordance with this data sheet, the protection provided will be impaired.
Applicable regulations must be observed when installing and using the device. Within the EU, these
include regulations regarding occupational safety and accident prevention as well as those from the
VDE (Association for Electrical, Electronic & Information Technologies). If the device is used in other
countries, it is the responsibility of the system installer or operator to comply with local regulations.
Mounting, installation and commissioning work on the devices may only be carried out by qualified
technicians. Qualified technicians are persons who are familiar with the described product and who
can assess given tasks and recognize possible dangers due to technical training, knowledge and
experience as well as knowledge of the appropriate regulations.
Legend
WARNING
Indicates a hazard of medium risk which can result in death or severe bodily injury if it is not avoided.
CAUTION
Indicates a hazard of low risk which can result in minor or medium bodily injury if it is not avoided.
!NOTICE
Indicates a hazard of medium risk which can result in material damage or malfunctions if it is not
avoided.
NOTE
Indicates additional information that can simplify the work with the product for you.
Notes on Disposal
For disposal, the product is considered waste from electrical and electronic equipment (electronic
waste) and must not be disposed of as household waste. Special treatment for specific components
may be legally binding or ecologically sensible. The local and currently applicable legislation must be
observed.

A
Page 3 / 6
Datasheet 1.50-22.025-01-EN
DU0/5, DU0/25Product Description
Issue 2010-07-22
Item
Technical Data
Dimensions
DU0/5 Differential pressure sensor, 3 adjustable measuring ranges
DU0/25 Differential pressure sensor, 3 adjustable measuring ranges
Nominal voltage DC 13.5 V to 33.0 V;
AC 24 V ± 15%
Power consumption <10 mA
Output DC 0 V to 10 V
Measuring range Adjustable with DIP switch
■DU0/5
0mbarto1mbar;0mbarto3 mbar; 0 mbar to 5 mbar
■DU0/25
0 mbar to 10 mbar; 0 mbar to 16 mbar; 0 mbar to 25 mbar
Overload pressure ■Application in the overpressure range:
100 mbar at P1; 4 mbar at P2
■Application in the low pressure range:
-4 mbar at P1; -100 mbar at P2
Burst pressure 2 x overload at room temperature
1.5 x overload at 70 °C
Pressure connections Hose connections ∅6.2 mm
Medium Air, neutral gasses
Electrical connection 3-conductor, screw terminals for lines max. 1.5 mm2
Cable bushing with an integrated strain relief device
Included: Connection set with PVC hose, length: 2 m
Degree of protection IP54
Protection class III in accordance with EN 60730
Ambient and medium tem-
perature
0 °C to 70 °C
Dimensions WxHxD mm 92x75x47.9
Weight 0.090 kg
92
80
58,2
37,1
27,6
75
10,6
18
P1 P2
∅ 5,5
4
47,9

APage 4 / 6
Product DescriptionDU0/5, DU0/25
Datasheet 1.50-22.025-01-EN Issue 2010-07-22
Connection
Installation
The installation position is to be selected so that the permitted conditions for the differential pressure
sensor are maintained (see Section Technical Data).
The system must be depressurized before installation and removal.
The differential pressure sensor should not be installed at a point where it may be affected by high
pressure pulses.
The installation position is variable. The recommended installation position is vertical with the
pressure connections at the bottom (factory calibration).
!NOTICE
If the differential pressure sensor is not installed vertically, a zero point reset should be performed.
The sensor is installed on a mounting bracket on a vibration free surface, with the pressure connec-
tions at the bottom.
The connection hose for the higher pressure is connected at P1 for measuring the differential
pressure. The connection for the lower pressure is connected at P2.
The hose connections at the ventilation duct and at the differential pressure sensor are to be
connected depending on their function: for measuring differential pressure, overpressure or low
pressure.
0+
24 V AC/DC
0..10 V DC
0 V AC/DC
Differential pressure measure-
ment
Overpressure measurement Low pressure measurement
P2
P1 P1 P2

A
Page 5 / 6
Datasheet 1.50-22.025-01-EN
DU0/5, DU0/25Product Description
Issue 2010-07-22
A connection set is provided for connecting the differential pressure sensor.
►Drill a hole for the ventilation duct Ø 16 mm.
►Insert a rubber grommet.
►Push the connection nozzle into the grommet.
►Cut the PVC hose to the required length, attach it to the connection nozzle and connect the differ-
ential pressure sensor.
NOTE
The pressure transmitter should be installed a minimum distance of 10 mm from magnetic materials.
If this is not possible, an error of up to -1 Pa may occur when the pressure transmitter is mounted on
sheet steel.

APage 6 / 6
Product DescriptionDU0/5, DU0/25
Datasheet 1.50-22.025-01-EN Issue 2010-07-22
Commissioning
Adjusting the measuring range
Zero point reset button (2)
A zero point offset may occur due to a strong thermal change in the sensor environment. This means
that the displayed measured value is not zero when there is no pressure.
Pressure deviations are set to zero by pressing the zero point reset button (2).
!NOTICE
After electrical commissioning, press and hold the button on the depressurized device until the LED
(1) flashes. If the LED (1) remains lit, the reset has not worked due to pressure in the device.
(1) LED
(2) Zero point reset button
(3) DIP switch
(4) Pressure connection at P2 (lower pressure/
bigger vacuum)
(5) Pressure connection at P2 (higher pressure/
smaller vacuum)
DIP switch (3) setting Measuring range
DU0/5 DU0/25
00 0 mbar to 5 mbar 0 mbar to 25 mbar
01 0 mbar to 3 mbar 0 mbar to 16 mbar
10 0 mbar to 1 mbar 0 mbar to 10 mbar