This guide is a pictorial progression through the various display screens with basic
descriptions of each display field and brief definitions of each.
More detailed information on the JC Systems Model 620A manufactured by TMC
Services is also available in the Model 620A Manual.

Model 620A by TMC Services Training
By Compass Services
The front panel displayed is referred to as the “Home or Run” Screen.
Overview: Front Panel displays, and indicators.
1: CH1 & CH2 Inc/Dec LED’s. Indicate “ON/OFF” Time Proportioned output.
INC, up arrow (heat, humidify, climb, etc.) and DEC, down arrow (Cool, de-humidify, dive, etc.)
2: Displays Program # (1 – 99), Step # (1 – 200), and Time Remaining in current program step.
3: Displays Interface, LCL (Local, front panel) or RMT (Remote, external computer) and Mode
(RUN, STP, EOP, GS1, GS2, etc.)
4: Line 1: Displays CH1 & CH2 SP (Setpoint) and status of first eight event outputs (1 – 8)
Line 2: Displays CH1 & CH2 PV (Process value) and status of next eight event outputs (A – H)
(SP and PV are displayed in units configured for that channel (deg C, F, %RH, Alt/FT etc.)
5: ALM – 4 possible flashing displays: S1 – S2 – L1 – L2.
S1 & S2 – Setpoint Alarm. Setpoint is out of configured controller span or input is open.
CH1 or CH2 PV will display “RANGE” setpoint out of range or “P.OP” – Probe Open.
L1 & L2 – DEV Limit Alarm. Channel is out of programmed +/- DEV span.
Each channel can be configured for the program to continue running or stop during alarm,
and for the alarm display and output to reset manually or automatically.
CH1 & CH2 share a common Logic low output from the 620A.

Overview: Front Panel Keypad.
NOTE: Keypad is fully functional for entry or
change only in the LCL mode.
Screens can be viewed but parameters
can not be changed in RMT mode.
RUN: Push to run a new program or resume a program after the Stop/Hold button is pushed.
STOP/HOLD: STOPS the running program and HOLDS the parameter values, Setpoints, Events and Time.
Push RUN to resume operation or RESET to reset current program back to step # 1.
RESET: In STOP (STP) mode resets program pointer to step 1 of selected program.
Returns display to the “HOME/RUN” screen from “any” screen or menu selection.
If the operator is on a screen they do not recognize or are unsure of, it is recommended to push
RESET. This returns to the HOME/RUN screen and allows access to the Main Menu
Pushing any other button could result in changing an operating parameter.
HELP: Not much is available.
PAGE UP: Moves to previous page of menus, configurations, editing, calibration, PID tuning, etc.
PAGE DOWN: Moves to next page of menus, configurations, editing, calibration, PID tuning, etc.
In LCL_STP mode of the Home/Run screen, pushing Page Down accesses the Main Menu.
SEL: Used to scroll through selections of a field on a page.
CLR: Clears the value or selection of the selected field on a Page.
ALPHA NUMERIC: Used for entering numeric data or selecting lettered events.
Cursor must be in the letter event field to select letter events.
ARROW KEYS (Up, Dn, Right, Left): Used to navigate cursor to different fields on a Page.
ENTER: Enters value of current filed and advances cursor to next field on the Page, or to the next
Page if entering from the last field on that page.
EDIT ONLY KEYS:
DUP STEP: Insert a step into the next location and copy current step information. All following steps advance x1.
CLR STEP: Clears all information in the current step to default values.
INS STEP: Insert a blank step into the next location. All following steps advance x1.
DEL STEP/PRG: With cursor over step number deletes the step. All following steps move back x1.
With the cursor over the PRG number the entire program is deleted from memory.
Examples: Advance x1: Steps 3 now 4, 4 now 5, etc.. Back x1: Steps 3 now 2, 4 now 3, etc.

1 Main Menu Section 1 - The following section contains:
Pg1
Main Guide screen:
Main Menu structure (w/o Item 4 details)
Power on screen
Pg 2
Run screen
Run infor screen 1
Pg3
Run info screen 2
Run info screen 3
Pg4
Alarms
POP, Range, Deviation
Pg5
Response to Dev Alarm and Config.
Pg 6
Stop Screen
Main menu screen

Menu Guide
The menu for the Model 620A controller is a three level menu containing 6 major selection screens.
The figure below (Figure X-X) highlights the Model 620A Menu Structure.
POWER ON SCREEN
When the Model 620A is turned on or the power is cycled the following display appears for 10 to 15
seconds during boot up.
Firmware Version and Date: Please provide this information when contacting the factory regarding any
issues with the Model 620A
This information does not indicate the age of the instrument. The firmware version may have been
peviously updated.
The Model 620A will boot up into either the STP or RUN mode of operation and display screen.
If the unit was running a program when the power was removed. It will perform the operation selected
in the Power Fail Recovery Mode.
If a program was not running it will boot up on the Stop screen on the last program and step number accessed.
1

RUN SCREEN
This screen displays real time running information.
The Main Menu is not available from the Run Mode.
Pushing <Page Down> sequences the display through three Run Time Information screens (shown below).
The information screens will time out after appx. 15 seconds and the display returns to the Run Screen.
Line 1: CH1
Setpoint CH2
Setpoint Events
1 - 8
Line 2:
CH1
Process
Value
CH2
Process
Value
Events
A - H
Line 4:
Line 3:
Prog # Step # Time Remaining
in Step
INTERFACE:
LCL - Local
Front Panel
RMT -
Remote
Ext Computer
MODE:
RUN
STP
EOP
DEV
GS1(2)
MAN
OFF
ALM:
S1 - Setpoint Alarm CH1
S2 - Setpoint Alarm CH2
L1 - Deviation Alarm CH1
L2 - Deviation Alarm CH2
RUN INFORMATION SCREEN 1 - PAGE DOWN FROM RUN SCREEN
Line 1: CH1
DEV CH2
DEV CH1 FINAL
SP VALUE
Line 2:
CH1
UNITS CH2
UNITS CH1 FINAL
SP VALUE
Line 3:
DISPLAY ONLY
Line 4: NEXT PROGRAM# AND STEP#
<PAGE DOWN> FOR RUN SCREEN 2
2

Line 1: CH1 HI
Limit CH2 Hi
Limit CH1 %
output
Line 2:
CH1 Lo
Limit CH2 Lo
Limit CH2 %
output
Line 4:
Line 3:
PROG. MODE:
1 Channel
2 Channel
FASTTRAC
PASSTHRU
CH1 PID SET IN USE
STAG1 (SET 1)
STAG2 (SET 2)
RUN INFORMATION SCREEN 3
Line 1: Loops remaining in current nested Loop: *See note below.
Line 2:
Line 3:
Guarantee Soak CH1
Line 4:
RUN INFO SCREEN 2
CH2 PID SET IN USE
STAG1 (SET 1)
STAG2 (SET 2)
<PAGE DOWN> FOR RUN SCREEN 3
*NOTE: LOOP and CYCLE fields:
---- indicates the Loop or Cycle step has not been reached and the
counter has not been updated.
A number represents the Loops (in the current nested loop) or Program
Cycles remaining.
Cycles remaining in current program:
*See note below.
Guarantee Soak CH2
<PAGE DOWN> = no action <PAGE UP to SCREEN 2 or allow timeout.
3

4
Alarms Listings – What Alarms show Up
P.OP - Probe Open:
The control channels probe is disconnected, is defective, or has an open junction.
The control channel will read properly when the problem is corrected.
P.OP ACTION:
The PV field of the control channel will display P.OP and the controller INC and DEC
outputs will be disabled.
A running program will freeze. The time, events and unaffected control channel will
hold at their current values.
The program will resume operation when the problem is corrected.
RANGE (S1 OR S2):
The entered setpoint is outside the range allowed by the controller’s span.
Enter a valid setpoint or reconfigure the controllers span.
Note:
Changing the controller span is not recommended unless the attempted setpoints
are valid and within the prescribed range of operation.
Prior to changing the controller span, record the channel’s PBAND setting in the
PID tuning section. After the new span is entered, return to the PID tuning
section and enter the previously recorded PBAND value.
Do not change the PGAIN value. It will automatically adjust to the proper value.
RANGE ACTION:
The PV field of the control channel will display RANGE and the controller INC and DEC outputs will be
disabled.
A flashing S1 (CH1) or S2 (CH2) will be displayed in the ALM field of line 4 on the Home (Run) screen.
The “COMMON DEV ALARM” output on TB1-7 will go low.
A running program will freeze. The time, events and unaffected control channel will hold at their current values.
The program will resume operation when the problem is corrected.
DEVIATION (L1 OR L2): Programmer or Manual Modes.
The DEV is entered as a parameter of a program step or in the Manual Mode.
The DEV alarm function tracks the SP vs PV error.
If the PV is outside of the +/- range entered for the DEV the following actions occur.
DEVIATION ACTION:
A flashing L1 (CH1) or L2 (CH2) will be displayed in the ALM field of line 4 on the Home (Run) screen.
The “COMMON DEV ALARM” output on TB1-7 will go low.

5
PROGRAMMER CONFIGURATION AND RESPONSE TO DEVIATION ALARM:
The response to a DEV Alarm is independently configured for each channel In the
Model 620A’s programmer configuration section.
PROGRAMMER ACTION:
Stop during DEV: The programmer stops when a deviation conditon is
detected. The time display stops decrementing, the controller setpoints
and event outputs are latched.
The controllers continue operating and maintain the latched setpoints.
The alarm field display flashes and the alarm output TB1-7 goes low.
Run during DEV: The programmer continues to run.
The alarm field display flashes and the alarm output TB1-7 goes low.
ALARM RESET ACTION:
AUTOMATIC: If Stop during DEV is selected. The Model 620A will
automatically resume operation. The alarm display and output will be
automatically reset as soon and the out of limits condition has ended.
If Run during DEV is selected. The alarm display and output will be
automatically reset as soon and the out of limits condition has ended.
MANUAL: The reset action occures “only” when the out-of-limits conditon has
ended and the Model 620A RUN mode is enabled.
The Run mode is enabled by pushing the Front Panel <RUN>, providing
a run signal from the photoisolated Run input or issuing a Run command
via the computer (in RMT mode only).

STOP SCREEN
Pushing the <STOP/HOLD> button from the LCL_RUN screen will freeze the time, hold all operating
parameters at their current values, and display STP in the Mode Field.
Active Setpoint (S1 or S2) or Dev Limit (L1 or L2) alrams will display in the ALM field.
Push <RUN> to resume operation.
Push <PAGE DOWN> to access the Main Menu.
MAIN MENU Selection Menus
The menu of the 620A controller has 6 major selection screens. In the next sections each of these major menu screens
will be explained in detail. The major selection screens are broken down as follows:
1. SELECT PROGRAM TO RUN Screen
2. CHANGE CURRENT VALUE Screen
3. EDIT PROGRAMS Screen
4. CONFIG-TUNE CALIBRATE
4-1 CONFIGURE PROGRAMMER
4-2 CONFIGURE CONTROLLERS
4-3 CALIBRATE INPUTS
4-4 CALIBRATE OUTPUTS
5. MANUAL MODE
Manual % OUTPUT
6. DELAY_START