Issue: 01.06.2023 Page 4
Alternative mounting arrangement for ambient cooler
Spigot can be placed at bottom of unit to enable external
ducting to be used. This is the alternative arrangement of
the unit where the rear hole is blanked by plate.
Note:
1. The hole through wall can be drilled in another
location.
2. Ducting is not provided.
Figure 6: Spigot Positions
Electrical Connection
The mains electrical supply to the JABC-1 unit
must be via a suitably rated isolator and
circuit breaker or fuse. There is no isolator
fitted to the unit. It requires a 230 volt / 1
phase / 50Hz supply which must include a
Neutral and Earth. It is not suitable for any other supply
voltages (other than a deviation of +/- 10% of the above
values) and is not suitable for 60 Hz supplies.
1. Ensure that all power supplies have been isolated
before starting any electrical work.
2. Only a qualified electrician should carry out any
electrical work.
3. Ensure that indoor cellar unit is fully isolated before
carrying out this section.
4. Make sure that the supply to the JABC-1 unit and the
control circuit from the main cellar cooler are using the
same electrical phase, otherwise there is potential for
400V at the JABC-1 unit.
5. Where the main cellar evaporator has only one fan,
this should be wired to run continuously (whether the
JABC-1 unit is running or not) to maintain proper air
circulation within the cellar. For evaporators fitted with
multiple fans, it is possible to leave one fan running
and switch additional fans off for energy saving when
not required (cellar at desired temperature) through
relay K2R on the JABC-1 unit. This may require a
wiring change to the fans on the evaporator.
6. Maximum allowable load to relay K2R is 1250VA
(Resistive: 5A/250VAC; Inductive 1.5A/250Vac).
Probe Positioning
•Cable glands are provided for the mains supply cable
and the cellar temperature probe cable on the right-
hand side of the unit. Use the provided M12 cable
gland for the mains supply cable and the cellar
temperature probe.
•The cellar temperature probe is coiled up in the control
box. Remove the front lower panel on the unit to gain
access to the control box.
•The ambient temperature probe is coiled and stored
behind the air damper on the rear of the unit.
•Connect the mains supply cable (provided) to the unit
as per the Figure 8: Wiring Diagram. Do not switch on
the supply yet.
•Isolate the main cellar cooler supply and break the
control circuit as per the wiring diagram. Using a 2-
core cable, connect the control circuit from the main
cellar cooler to terminal A on the JABC unit and return
via terminal B to feed either the main cellar cooler
contactor coil or the solenoid valve.
•Position the JABC cellar temperature probe unit in a
suitable position within the cellar (ideally next to the
temperature sensor for the main cellar cooler). The
probe cable length is 3m, but this can be extended
with 2 x AWG22 if required.
•Position the JABC ambient temperature probe. This can
be run down the inside of the air inlet ducting and
secured within the external air inlet grille. Ensure sensor
is protected from direct sunlight which may affect the
temperature reading and the operation of the unit.
Commissioning
•Ensure that all covers are fitted on the unit.
•Ensure that all electrical connections have been
made as per Figure 8: Wiring Diagram
•The controllers are fully preset and the settings
should not be altered.
1. Switch on power supply to both main cellar unit and
JABC-1.
2. The JABC-1 unit should now display outside ambient
temperature on the Ambient controller (top) and the
cellar temperature on the Cellar controller located
below.
3. The cellar temperature set point of the JABC-1 unit is
preset to 10°C. This must not be altered.
4. The temperature set point of the main cooling should
be set at 10°C to match the JABC controller or it can
be set 1°C lower than JABC-1 setting if required. The
set point of the main cellar cooler should not be set
above 10°C.
5. Allow the system to run and ensure that the unit is
functioning correctly.
There are 2 external status lights on the front of the JABC-1
unit giving a clear visual display of current operating
condition of unit.
Table 7: Pilot Light Indication