BSC-50D User Guide 10
4.3 Configuring the Temperature channel
The default command (fixed) for the temperature channel configuration is:
1200,1,Temperature,164,3276,-40,150,-40,150,oC,0
1200: Command ID
n: 1, Analog input number
s: Up to 15 characters, AI name (Text, may include space characters)
ssl: 0-4095, Sensor Scale Low (Raw value)
ssh: 0-4095, Sensor Scale High (Raw value)
sl: User Scale Low
sh: User Scale High
al: Alarm Limit Low in physical Scale values
ah: Alarm Limit High in physical Scale values
u: Physical Unit
d: 0-255, Alarm delay in minutes
Scope: LP-MCU, COMM_MCU
4.3.1 Temperature Alarm actions
The parameter selects the actions for each Temperature Alarm Limit.
1206,n,lo,hi
1206: Command ID
n: 1, AI number
lo: 0/1, Selection for Low Alarm Limit
1Send logged data after the Alarm Message
0Plain Alarm Message without Data Transfer
hi: 0/1, Selection for High Alarm Limit
1Send logged data after the Alarm Message
0Plain Alarm Message without Data Transfer
Scope: COMM_MCU
4.3.2 Temperature Alarm Dead Band
The parameter defines the Alarm Dead Band (hysteresis) for the Temperature
channel. Alarm Dead Band is a small range of the total Scale, where the Alarm state
remains indifferent, by registering the last value.
1290,d
1290: Command ID
d: 0-50 for an Alarm Dead Band of 0-5% in steps of 0.1%
Scope: LP-MCU