ICT PRT-ISO16-DIN Manuel utilisateur

PRT-ISO16-DIN
Protege DIN Rail 16 Input Opto-Isolated
Expander
Installation Manual

The specifications and descriptions of products and services contained in this document were correct at the time
of printing. Integrated Control Technology Limited reserves the right to change specifications or withdraw
products without notice. No part of this document may be reproduced, photocopied, or transmitted in any form or
by any means (electronic or mechanical), for any purpose, without the express written permission of Integrated
Control Technology Limited. Designed and manufactured by Integrated Control Technology Limited, Protege® and
the Protege® Logo are registered trademarks of Integrated Control Technology Limited. All other brand or product
names are trademarks or registered trademarks of their respective holders.
Copyright © Integrated Control Technology Limited 2003-2022. All rights reserved.
Last Published: 15-Jun-22 5:11 PM
PRT-ISO16-DIN | Protege DIN Rail 16 Input Opto-Isolated Expander | Installation Manual 2

Contents
Introduction 4
Installation Requirements 5
Grounding Requirements 6
Safety Grounding 6
Earth Ground Connection 6
Mounting 8
Removal 8
DC Power & Encrypted Module Network 9
Opto-Isolated Inputs 10
Trouble Inputs 10
Programmable Outputs 11
Open Collector Outputs 11
Address Configuration 12
LED Indicators 13
Status Indicator 13
Fault Indicator 13
Power Indicator 13
Output Indicators 13
Input Status Indicators 14
Error Code Indication 15
Error Code Display 15
Mechanical Diagram 16
Mechanical Layout 17
Technical Specifications 18
New Zealand and Australia 19
European Standards 20
UK Conformity Assessment Mark 22
FCC Compliance Statements 23
Industry Canada Statement 24
Disclaimer and Warranty 25
PRT-ISO16-DIN | Protege DIN Rail 16 Input Opto-Isolated Expander | Installation Manual 3

Introduction
The Protege DIN Rail 16 Input Opto-Isolated Expander extends the number of inputs on the system by 16, allowing
monitoring of a wide range of open contact sensors for security, elevator control and building automation
purposes.
Flexible module network architecture allows large numbers of modules to be connected to the RS-485 module
network. Up to 250 modules can be connected to the Protege system in any combination to the network, over a
distance of up to 900M (3000ft). Further span can be achieved with the use of a network repeater module.
The current features of the isolated input expander include:
⦁Secure encrypted RS-485 module communications
⦁16 opto-isolated inputs
⦁Industry standard DIN rail mounting
⦁Online and remote upgradeable firmware
PRT-ISO16-DIN | Protege DIN Rail 16 Input Opto-Isolated Expander | Installation Manual 4

Installation Requirements
This equipment is to be installed in accordance with:
⦁The product installation instructions
⦁The Local Authority Having Jurisdiction (AHJ)
PRT-ISO16-DIN | Protege DIN Rail 16 Input Opto-Isolated Expander | Installation Manual 5

Grounding Requirements
An effectively grounded product is one that is intentionally connected to earth ground through a ground
connection or connections of sufficiently low impedance and having sufficient current-carrying capacity to
prevent elevated voltages which may result in undue hazard to connected equipment or to persons.
Grounding of the Protege system is done for three basic reasons:
1. Safety
2. Component protection
3. Noise reduction
Safety Grounding
The object of safety grounding is to ensure that all metalwork is at the same ground (or earth) potential.
Impedance between the Protege system and the building scheme ground must conform to the requirements of
national and local industrial safety regulations or electrical codes. These will vary based on country, type of
distribution system and other factors. The integrity of all ground connections should be checked periodically.
General safety dictates that all metal parts are connected to earth with separate copper wire or wires of the
appropriate gauge.
Earth Ground Connection
The DIN rail enclosure and the DIN rail modules must be grounded to a suitable single-point earth ground
connection in the installation. A minimum 14AWG solid copper wire (or thicker, in accordance with local
authorities) shall be used from the Protege system's earth connection points.
The DIN rail enclosure includes an earth ground single-point link connection via the metallic enclosure. This single-
point link is the Protege system's earth ground. All modules that have earth ground connections and that are
installed in the same enclosure shall be connected to this single point. A single-point earth ground connection
avoids the creation of ground loops in the system and provides a single reference point to earth ground.
Reader Expander
Input Expander
Output Expander
Controller
Dialer’s Earth
Ground Connection
Power Supply
V-
DIN Rail Ground Connections (one or more cabinets installed in the same room)
DIN Rail Enclosure Additional DIN Rail Enclosure(s)
Module Network
(RS-485 N+, N-, NA, NB)
AC Mains Wiring
Earth Ground
Link Connection
PRT-ISO16-DIN | Protege DIN Rail 16 Input Opto-Isolated Expander | Installation Manual 6

Sector or Building #2Sector or Building #1 Sector or Building #3
Input Expander
Input Expander
Input Expander
Reader Expander
Input Expander
Output Expander
Power Supply
Controller
Dialer’s Earth
Ground Connection
V-
Earth Ground
Link Connection
DIN Rail Enclosure DIN Rail Enclosure DIN Rail Enclosure
Module Network (RS-485 N+, N-, NA and NB)
DIN Rail Ground Connections (multiple cabinets in different rooms, sectors, or buildings)
The Dialer's Earth Ground Connection applies to modem model controllers only.
Note that the DIN rail enclosure earth terminal is connected to the power supply V- terminal.
There must be only one single earth grounding point per system.
PRT-ISO16-DIN | Protege DIN Rail 16 Input Opto-Isolated Expander | Installation Manual 7

Mounting
Protege DIN rail modules are designed to mount on standard DIN rail either in dedicated DIN cabinets or on
generic DIN rail mounting strip.
When installing a DIN rail module, ensure that there is adequate clearance around all sides of the device and that
air flow to the vents of the unit is not restricted. It is recommended that you install the module in a location that
will facilitate easy access for wiring. It is also recommended that the module is installed in an electrical room,
communication equipment room, secure cabinet, or in an accessible area of the ceiling.
1. Position the DIN rail module with the labeling in the correct orientation.
2. Hook the mounting tabs (opposite the tab clip) under the edge of the DIN rail.
3. Push the DIN rail module against the mount until the tab clips over the rail.
Removal
A Protege DIN rail module can be removed from the DIN rail mount using the following steps:
1. Insert a flat blade screwdriver into the hole in the module tab clip.
2. Lever the tab outwards and rotate the unit off the DIN rail mount.
PRT-ISO16-DIN | Protege DIN Rail 16 Input Opto-Isolated Expander | Installation Manual 8

DC Power & Encrypted Module Network
The expander incorporates encrypted RS-485 communications technology, and both module and network power
are supplied by the N+ and N- terminals.
NA NB
Network communications input
from the Controller or previous
module
N+ N-
Connection of the communications and DC supply should be performed according to the diagram shown above. It
is important that the N+ network communications power be 12VDC supplied from an independent battery backed
power supply unit capable of supplying the required voltage to all devices on the RS-485 network.
Warning:
⦁The 12V N+ and N- communication input must be supplied from only one point. Connections from more
than one 12V supply may cause failure or damage to the unit or the device supplying network power.
⦁The 330 ohm EOL (End of Line) resistor provided in the accessory bag must be inserted between the NA
and NB terminals of the first and last modules on the RS-485 network. These are the modules physically
located at the ends of the RS-485 network cabling.
End of Line Resistors:
330R 330R
First Module on RS-485 Network Last Module on RS-485 Network
To
Next
Module
From
Previous
Module
NAN+ N- NB
NAN+ N- NB
PRT-ISO16-DIN | Protege DIN Rail 16 Input Opto-Isolated Expander | Installation Manual 9

Opto-Isolated Inputs
The isolated input expander can monitor the state of up to 16 opto-isolated inputs, with each input completely
isolated electrically from the others. In order for the inputs to be activated, power needs to be externally provided
to the required input terminals.
Devices connected to these opto-isolated inputs can be installed to a maximum distance of 300m (1000ft) from
the expander when using 22 AWG wire. Each opto-isolated input may be individually configured for normally
opened and normally closed configurations.
Input Circuit Examples:
Trouble Inputs
Each isolated input expander can monitor up to 16 trouble inputs.
Trouble inputs are used to monitor the module status and in most cases are not physically connected to an
external input.
The following table details the trouble inputs that are configured in the system and the trouble type and group
that they activate.
Input Number Description Type Group
ZXxxx:01-03 Reserved None None
ZXxxx:04 Aux Failure Power Fault General
ZXxxx:05-15 Reserved None None
ZXxxx:16 Module Offline Module Offline System
Replace 'xxx' with the appropriate address of the module that you are programming.
When this module is added by the expanders wizard in Protege WX, the 'Module Offline' trouble input is
incorrectly programmed with address 4. For correct operation, change the trouble input address to 16. This is a
known issue.
PRT-ISO16-DIN | Protege DIN Rail 16 Input Opto-Isolated Expander | Installation Manual 10
Ce manuel convient aux modèles suivants
1
Table des matières
Autres manuels ICT Extenseur

ICT
ICT PRT-ZX8-DIN Manuel utilisateur

ICT
ICT PRT-F2F8-DIN Manuel utilisateur

ICT
ICT PRT-RDM2-DIN-485 Manuel utilisateur

ICT
ICT Protege PRT-PX8-DIN Manuel utilisateur

ICT
ICT PRT-ADC4-DIN Manuel utilisateur

ICT
ICT PRT-IO84-DIN Manuel utilisateur

ICT
ICT PRT-HPX8-DIN Manuel utilisateur

ICT
ICT PRT-HRDM-DIN Manuel utilisateur

ICT
ICT Protege PRT-PX8-DIN Manuel utilisateur

ICT
ICT Protege PRT-RDI2-PCB Manuel utilisateur