1. Introduction
Doc No: T13 144 1C Data is subject to change without notice. More information at: www.helvar.com
µDim Microwave Sensors
The µDim series of miniature microwave presence detectors provide automatic control of lighting loads with optional manual control. The unit comes
complete with a selection of fixing clips, allowing unobtrusive flush mounting of the sensor head into ceiling tiles or on to solid surfaces. It has been
designed so that it can be used for ceiling mounted or wall mounted applications. As microwave radiation penetrates plastic and glass, this unit has
been specifically designed to be mounted inside a luminaire.
Three versions are available: switched, 1-10V analogue, and DALI. All of which will switch incandescent, fluorescent and compact fluorescent
lighting.
The unit detects movement using a microwave sensor and turns the load on. When an area is no longer occupied the load will switch off after an
adjustable time out period has elapsed.
Table of Contents Page
Introduction 2
Technical data 3
Dimensions and mounting options 9
Connections 10
Setup 11
Programmming 12
Fault finding 14
Feature SL-MW-SW SL-MW-AN SL-MW-DA
Up to 8m microwave sensing
Lux sensor
Presence detection
Infrared remote setting
Relay output
1-10 V Dimming output - -
DALI Dimming output - -

3
µDim
2. Technical Data
Doc No: T13 144 1C
Data is subject to change without notice. More information at: www.helvar.com
SL-MW-SW µDim Microwave Switching Sensor
The SL-MW-SW miniature microwave presence detector
provides automatic control of lighting loads. The unit comes
complete with a flush-mount bracket, allowing unobtrusive
mounting of the sensor head into ceiling tiles or onto solid
surfaces. It has been designed so that it can be used for
luminaire mounted or ceiling mounted applications. As
microwave radiation penetrates plastic and glass, this unit has
been specifically designed to be mounted inside a luminaire.
The product consists of the following :
• Sensor head with integral RJ11 sensor lead
• Power supply unit
• Flush mount bracket
Presence detection: when movement is detected the load will
automatically turn on; when the area is no longer occupied the
load will automatically switch off after an adjustable time period.
1) No presence detected, daylight, lights OFF
3) Presence detected, insufficient daylight, lights ON 4) No presence detected, night time, lights OFF
2) Presence detected,sufficient daylight, lights OFF

4
µDim
2. Technical Data
Doc No: T13 144 1C Data is subject to change without notice. More information at: www.helvar.com
SL-MW-SW µDim Microwave Switching Sensor
5m
12m
8m
2.8m
Recommended mounting location
Detection area
Sensor head
• Avoid direct sunlight entering the sensor
• Do not site within 1m of forced air heating or ventilation.
• Do not fix to a vibrating surface.
• Avoid metallic objects directly in front of the sensor head.
• Do not fit to a suspended luminaire
• When installing the sensor head behind a glass /
polycarbonate diffuser will reduce the detection range by
approximately 20%.
Note: On maximum sensitivity, the detector unit is extremely sensitive
to movement and may detect through glass, thin walls or partitions.
If this causes a problem, reduce its sensitivity using the SA-IR-PROG
Programmer.
Technical specifications
• Supply voltage 220 - 240 V AC, 50 Hz
• Max load capacity 2 A
• Light level Light to dark
• Connections Integral RJ11 cable between
supply unit and sensor head
• Terminals (supply unit) 1.5mm2 (solid core cable only)
Material
• Sensor head, surface mount baseplate ,
flush bracket — Flame retardant ABS
• Flange mount bracket & Lens—PMMA (Clear acrylic)
• Power supply unit housing — Flame retardant polycarbonate
• Type Class 2
• Operating Temperature -10°C to 50°C
SAFETY
The microwave radiation emitted by these units is extremely
low power. At a distance of > 50mm the power density is <6%
of the ANSI IEEE C95.1 –1991 recommended microwave
power density. At a distance of 5mm from the unit it is <84% of
recommended power density.
Conformity EMC-89/336/EEC
LVD-73/23/EEC
Lens
Green LED - time
Red LED - lux / presence setting indicator
Yellow LED - sensitivity / absence setting indicator

5
µDim
2. Technical Data
Doc No: T13 144 1C
Data is subject to change without notice. More information at: www.helvar.com
SL-MW-AN µDim Microwave 1-10V Sensor
The SL-MW-AN miniature microwave presence detector provides
automatic control of lighting loads. The unit comes complete
with a flush-mount bracket, allowing unobtrusive mounting of
the sensor head into ceiling tiles or onto solid surfaces. It has
been designed so that it can be used for luminaire mounted or
ceiling mounted applications. As microwave radiation penetrates
plastic and glass, this unit has been specifically designed to be
mounted inside a luminaire.
The product consists of the following :
• Sensor head with integral RJ11 sensor lead
• Power supply unit
• Flush mount bracket
Presence detection: when movement is detected the load will
automatically turn on; when the area is no longer occupied the
load will automatically switch off after an adjustable time period.
1) No presence detected, daylight, lights OFF 4) Presence detected, insufficient daylight. Detector measures
and implements maintained illumininance
3) Presence detected some daylight.
Lights on and dimmed to maintain lux level
5) No presence detected, night time, lights OFF2) Presence detected,sufficient daylight, lights OFF

6
µDim
2. Technical Data
Doc No: T13 144 1C Data is subject to change without notice. More information at: www.helvar.com
SL-MW-AN µDim Microwave 1-10V Sensor
5m
12m
8m
2.8m
Recommended mounting location
Detection area
Sensor head
• Avoid direct sunlight entering the sensor
• Do not site within 1m of forced air heating or ventilation.
• Do not fix to a vibrating surface.
• Avoid metallic objects directly in front of the sensor head.
• Do not fit to a suspended luminaire
• When installing the sensor head behind a glass /
polycarbonate diffuser will reduce the detection range by
approximately 20%.
Note: On maximum sensitivity, the detector unit is extremely sensitive
to movement and may detect through glass, thin walls or partitions.
If this causes a problem, reduce its sensitivity using the SA-IR-PROG
Programmer.
•
Lens
Green LED - time
Red LED - lux / presence setting indicator
Yellow LED - sensitivity / absence setting indicator
Technical specifications
• Supply voltage 220 - 240 V AC, 50 Hz
• Max load capacity Relay Output - 2 A
Dimmed Output - 4 x 1-10V ballasts
• Light level Light to dark
• Connections Integral RJ11 cable between
supply unit and sensor head
• Terminals (supply unit) 1.5mm2 (solid core cable only)
Material
• Sensor head, surface mount baseplate ,
flush bracket — Flame retardant ABS
• Flange mount bracket & Lens—PMMA (Clear acrylic)
• Power supply unit housing — Flame retardant polycarbonate
• Type Class 2
• Operating Temperature -10°C to 50°C
SAFETY
The microwave radiation emitted by these units is extremely
low power. At a distance of > 50mm the power density is <6%
of the ANSI IEEE C95.1 –1991 recommended microwave
power density. At a distance of 5mm from the unit it is <84% of
recommended power density.
Conformity EMC-89/336/EEC
LVD-73/23/EEC

7
µDim
2. Technical Data
Doc No: T13 144 1C
Data is subject to change without notice. More information at: www.helvar.com
SL-MW-DA µDim Microwave DALI Sensor
The SL-MW-DA miniature microwave presence detector provides
automatic control of lighting loads. The unit comes complete
with a flush-mount bracket, allowing unobtrusive mounting of
the sensor head into ceiling tiles or onto solid surfaces. It has
been designed so that it can be used for luminaire mounted or
ceiling mounted applications. As microwave radiation penetrates
plastic and glass, this unit has been specifically designed to be
mounted inside a luminaire.
The product consists of the following :
• Sensor head with integral RJ11 sensor lead
• Power supply unit
• Flush mount bracket
Presence detection: when movement is detected the load will
automatically turn on; when the area is no longer occupied the
load will automatically switch off after an adjustable time period.
1) No presence detected, daylight, lights OFF 4) Presence detected, insufficient daylight. Detector measures
and implements maintained illumininance
3) Presence detected some daylight.
Lights on and dimmed to maintain lux level
5) No presence detected, night time, lights OFF2) Presence detected,sufficient daylight, lights OFF

8
µDim
Doc No: T13 144 1C
2. Technical Data
Data is subject to change without notice. More information at: www.helvar.com
5m
12m
8m
2.8m
Recommended mounting location
Detection area
Sensor head
• Avoid direct sunlight entering the sensor
• Do not site within 1m of forced air heating or ventilation.
• Do not fix to a vibrating surface.
• Avoid metallic objects directly in front of the sensor head.
• Do not fit to a suspended luminaire
• When installing the sensor head behind a glass /
polycarbonate diffuser will reduce the detection range by
approximately 20%.
Note: On maximum sensitivity, the detector unit is extremely sensitive
to movement and may detect through glass, thin walls or partitions.
If this causes a problem, reduce its sensitivity using the SA-IR-PROG
Programmer.
Lens
Green LED - time
Red LED - lux / presence setting indicator
Yellow LED - sensitivity / absence setting indicator
SL-MW-DA µDim Microwave DALI Sensor
Technical specifications
• Supply voltage 220 - 240 V AC, 50 Hz
• Max load capacity Relay Output - 2 A
Dimmed Output - 4 x DALI ballasts
• Light level Light to dark
• Connections Integral RJ11 cable between
supply unit and sensor head
• Terminals (supply unit) 1.5mm2 (solid core cable only)
Material
• Sensor head, surface mount baseplate ,
flush bracket — Flame retardant ABS
• Flange mount bracket & Lens—PMMA (Clear acrylic)
• Power supply unit housing — Flame retardant polycarbonate
• Type Class 2
• Operating Temperature -10°C to 50°C
SAFETY
The microwave radiation emitted by these units is extremely
low power. At a distance of > 50mm the power density is <6%
of the ANSI IEEE C95.1 –1991 recommended microwave
power density. At a distance of 5mm from the unit it is <84% of
recommended power density.
Conformity EMC-89/336/EEC
LVD-73/23/EEC

9
µDim
3. Dimensions
Doc No: T13 144 1C
Data is subject to change without notice. More information at: www.helvar.com
Dimensions & Mounting options
Flush mounting the sensor head using the flush mount bracket
Sensor head
Power supply unit
39
18
3
1.5
19
300
Fixing lugs for
bulkhead fitting
Details for using bulkhead fixing lugs
Bulkhead plate
max. thickness 1mm
o 4mm
o 11mm
19
22.5
20.5
133
145
44 mm
6 mm
The product can be mounted into a flat panel of a luminaire using the flush mount bracket as shown below. If flush mounting in a panel that is
greater than 6mm thick, remove bottom of retention arms with side cutters. A 44mm diameter hole will be required in the panel to mount the
flush mount bracket.
44

10
4. Connections
µDim
Doc No: T13 144 1C
Connections
Sensor head
LOAD
max 2A
N
L
SL-MW-SW
Power supply unit
Sensor head
LOAD max 2A
N
L
1-10V
Ballast
C1(+)C0(-)
L
N
SL-MW-AN
Power supply unit
Sensor head
LOAD max 2A
N
L
DALI
Ballast
DA-DA+
L
N
SL-MW-DA
Power supply unit
• Connect the power supply via the terminal block on the power supply unit as shown overleaf. Live supply to the L terminal,
Neutral to the N terminal and the load to the LIVE OUT (L/out) terminal.
• Connect the sensor head to the power supply unit using the RJ11 connector, ensuring it “clicks” in place.
• In the case of dimming applications, connect the D+ and D_ connections to the corresponding terminals on the luminaire
dimming ballast.
• On power up, the load should come on immediately.
• Vacate the room or remain very still and wait for the load to switch off (on the factory preset, this should take approximately
15 minutes, but the timing out period can be adjusted down to 1 minute to help speed up the setup procedure — please
see next section for details on set-up & adjustment).
• Check that the load switches on when movement is detected.