Haes AOV Series Mode d’emploi

Installation, Commissioning &
Operating Manual
Automatically Opening Vent Control Panel
Approved Document UI-AOV-01 Issue 7.0

IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
E.S.D
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions
and used in accordance with this manual.
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualied and authorised
to do so. There is no need to open the panel’s enclosure except to carry out commissioning, maintenance
and remedial work. This work must only be carried out by competent service personnel who are fully
conversant with the contents of the panel’s installation manual and have the necessary skills for maintaining
this equipment.
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this control panel for any
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The
manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to
product specications at our discretion and without prior notice. E & O E.
IMPORTANT SAFETY NOTES
Haes Systems Ltd, Unit 3 Horton Industrial Park, UB7 8JD
15
Model Number
3 Amp, Automatically Opening Vent control panel, AOV-3 (standard spec) & AOV-3H (high spec)
5 Amp, Automatically Opening Vent control panel, AOV-5 (standard spec) & AOV-5H (high spec)
10 Amp, Automatically Opening Vent control panel, AOV-10 (standard spec) & AOV-10H (high spec)
In accordance with the following directives:
2006/95/EC - The Low Voltage Directive
2004/108/EC - The Electromagnetic Compatibility Directive
Is in conformity with the applicable requirements of the following documents:
BSEN 50130-4 +A1, 2014. Product family standard immunity requirements for components of re, intruder and social alarm
systems.
BSEN 61000-6-3, 2011. Electromagnetic Compatibility (EMC) General Standards. Emission standard for residential,
commercial & light industrial environments.
BSEN 62368-1, 2014. Audio/video information and communication technology equipment safety requirements.
ATTENTION

AOV Installation, Commissioning & Operating Manual Approved Document Ref: UI-AOV-01 Issue 7.0
1
CONTENTS
Page
ABOUT THIS PANEL 2
PRODUCT OVERVIEW 2
CABINET DETAILS 4
CIRCUIT BOARDS 6
MAIN PCB TERMINALS 7
TECHNICAL SPECIFICATION 8
POWER SUPPLY MODULES 9
PANEL FUNCTIONS 12
CIRCUIT DESCRIPTION/FUNCTIONS 12
DETECTOR CIRCUIT CONVENTIONAL WIRIING SCHEMATIC 16
DETECTOR CIRCUIT TWIN WIRE WIRIING SCHEMATIC 17
INSTALLATION 18
SAFETY 18
ESD PRECAUTIONS 19
GENERAL 19
MOUNTING THE CABINET 19
MAINS CONNECTIONS 20
CONNECTING THE BATTERIES 21
SETUP & PROGRAMMING 22
TWIN WIRE MODE 22
DIL SWITCH OPTIONS 23
LEVEL 3 ENGINEERING OPTIONS 23
OPERATING 29
PANEL CONTROLS & INDICATIONS 29
DISABLE MODE 32
TEST MODE 32
FUNCTIONALITY DURING A SYSTEM FAULT 33
USER INSTRUCTIONS 33

AOV Installation, Commissioning & Operating Manual Approved Document Ref: UI-AOV-01 Issue 7.0
2
ABOUT THIS PANEL
PRODUCT OVERVIEW
AOV is a range of single area Automatic Opening Vent control panels. The panels are available with three
different output capabilities, 3 Amp, 5 Amp & 10 Amp for controlling small, medium or larger loads.
The panels are supplied in two different enclosure sizes with the 3 Amp version in a smaller cabinet with
space for 3.2Ah batteries and the 5 & 10 Amp versions in a larger cabinet with space for 12Ah batteries.
Standard & high spec versions are available with the high spec version including additional control inputs
and outputs. See product codes and features table.
All variations are supplied in a sheet steel enclosure suitable for wall mounting with a hinged, lockable front
access door. The panels can be semi recessed using a suitable recessing bezel. Cable entry is via 20mm
knockouts located at the top and rear of the cabinet.
Different key types are used for the door lock and the ‘activate controls’ key switch. It is also possible
to enable the controls via a 4 digit code entry, if preferred. An eight button keypad is used to control the
system and allow access to the function options. The three main buttons, ‘OPEN VENT’ (red), ‘CLOSE
VENT’ (blue) & ‘RESET’ (green) being much larger and colour coded to assist the end users.
The panels are designed to control 24vdc motorised vents which use a polarity reversal to control direction.
A 1 Amp output is also provided for the control of magnetic vents or other purposes.

AOV Installation, Commissioning & Operating Manual Approved Document Ref: UI-AOV-01 Issue 7.0
3
ABOUT THIS PANEL
Quiesecent and alarm current details for standby battery calculations
Product codes and features
Input & output key
Model Standby Current Alarm Current
AOV-3 65mA 106mA
AOV-3H 75mA 116mA
AOV-5 65mA 106mA
AOV-5H 75mA 116mA
AOV-10 65mA 106mA
AOV-10H 75mA 116mA
Product Power Enclosure Size Batt Capacity Inputs Outputs
AOV-3 3 Amp 308W x 260H x 80D 3.2Ah A, S, E, F M, ACT(x1), CA, CF
AOV-3H 3 Amp 308W x 260H x 80D 3.2Ah A, S, R, P, E, F, B M, ACT(x2), CA, CF, BMS
AOV-5 5 Amp 460W x 310H x 110D 12Ah A, S, E, F M, ACT(x1), CA, CF
AOV-5H 5 Amp 460W x 310H x 110D 12Ah A, S, R, P, E, F, B M, ACT(x2), CA, CF, BMS
AOV-10 10 Amp 460W x 310H x 110D 12Ah A, S, E, F M, ACT(x1), CA, CF
AOV-10H 10 Amp 460W x 310H x 110D 12Ah A, S, R, P, E, F, B M, ACT(x2), CA, CF, BMS
Inputs Outputs
A Alarm input circuit M Magnetic vent
S Smoke detection circuit ACT Actuator
R Rain sensor CA Common alarm contacts
P PIR sensor CF Common fault contacts
E External control switch BMS BMS 0-10v status
F Firemans override
BBMS 0-10v control

AOV Installation, Commissioning & Operating Manual Approved Document Ref: UI-AOV-01 Issue 7.0
4
ABOUT THIS PANEL
Vent Control System
57mm 80mm
260mm
308mm
250mm
300mm
AOV-3 CABINET

AOV Installation, Commissioning & Operating Manual Approved Document Ref: UI-AOV-01 Issue 7.0
5
ABOUT THIS PANEL
AOV-5/10 CABINET
95mm 110mm
310mm
455mm
300mm
450mm
Vent Control System

AOV Installation, Commissioning & Operating Manual Approved Document Ref: UI-AOV-01 Issue 7.0
6
ABOUT THIS PANEL
CIRCUIT BOARDS
AOV panels comprise of two circuit boards, a master PCB and a display & controls PCB
+ -
12V
- -
PSU10A
+ + + -+ -
+ -
+ - + - + - + -
C NC NO C NC NO IP OP
OP CLCOM ON OFFCOM
COM
ALARM FAULT AUX ACT 1
+ -
ACT 2 INPUT DETECTOR RAIN PIR 0/10V
BATTERY VENT CONT FIREMAN SW
1 2 3 4 5 6 7
ON
1 2 3 4 ENTER
OPEN
VENT
CLOSE
VENT RESET
1 2 3 4 ENTER
OPEN
VENT
CLOSE
VENT RESET
TPCA016V(H) Master PCB
TPCA02-AOV - LED Display & Controls PCB for AOV-3 control panels
TPCA03-AOV - LED Display & Controls PCB for AOV-5/10 control panels

AOV Installation, Commissioning & Operating Manual Approved Document Ref: UI-AOV-01 Issue 7.0
7
ABOUT THIS PANEL
MAIN PCB TERMINALS (drawing shows high spec version with all available inputs and outputs tted)
28v input from power supply module (max 10A)
Common alarm VFCO relay. Unfused max 3A @ 30v dc
Common fault VFCO relay maintained (fail safe). Unfused max 3A @ 30v dc
0/10v control input/output
100mA @ 12v dc supply output for PIR
Magnetic vent output (maintained). Max 1A @ 28v dc
Conventional/Twin Wire smoke detector input
Actuator motor drive outputs, fused @ 10A (subject to PSU ratings)
4K7 Ω
470 Ω Trigger alarm input
4K7 Ω
470 Ω Rain sensor input
PIR sensor input
Vent
control
switch
inputs
Firemans
switch
inputs
+ -
12V
- -
PSU10A
+ + + -+ -
+ -
+ - + - + - + -
C NC NO C NC NO IP OP
OP CLCOM ON OFFCOM
COM
ALARM FAULT AUX ACT 1
+ -
ACT 2 INPUT DETECTOR RAIN PIR 0/10V
BATTERY VENT CONT FIREMAN SW
1 2 3 4 5 6 7
ON

AOV Installation, Commissioning & Operating Manual Approved Document Ref: UI-AOV-01 Issue 7.0
8
ABOUT THIS PANEL
General Specication
Enclosure Steel IP30. Epoxy powder coated Interpon Radon, silver grey
Temperature range -5 deg C to +40 deg C max RH 95%
Number of conventional/Twin Wire detection circuits 1
Conventional/Twin Wire detector compatibility Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
TECHNICAL SPECIFICATION
Electrical Specication Inputs & Outputs - TPCA016-V
Cabling Fire resistant screened cable, minimum
size 1mm2. Max cable length 1Km (20
Ohm). FireBurn, FP200 or equivalent
(max capacitance 1uF, max inductance 1
millihenry).
Suitable cable glands must be used.
Terminal capacity 0.5mm2to 2.5mm2solid or stranded wire.
PSU Input, 10A - - + + 28vdc supply input. Diode protected for
reversal and independent short circuit.
Max current 10 amps.
Max input current 10 amps. Input voltage
22vdc to 32vdc.
Common Alarm Relay Alarm relay contact. Clean C/O.
Max 3A @ 30vdc.
Unfused.
Common Fault Relay Maintained fault relay contact. Clean
C/O. Max 3A @ 30vdc.
Unfused.
Aux + - Maintained magnetic vent output, 28v
dc. Max 1 amp.
Fused 1 amp, 20mm glass quick blow
fuse.
ACT1 + - Dual polarity reversal actuator drive
outputs, 28v dc. Max 8 amps.
Fused 10 amp, 20mm glass quick blow
fuse.
Input + - Alarm activating input, 470R alarm. 4K7
Ohm 5% 0.25W EOL resistor.
Monitoring current limit 14mA, unfused.
Detector + - Fire alarm zone circuit. Conventionally
wired detection circuit or Twin Wire
combined detection / sounder circuit.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 50mA, fused
@ 500mA. Typical max load 22 alarm
devices @ 18mA each.
12v + - 12v dc supply output for PIR power. 12v dc, fused @ 100mA resettable fuse.
Additional Inputs & Outputs on High Spec Version - TPCA016-VH
ACT2 + - Dual polarity reversal actuator drive
outputs, 28v dc. Max 8 amps.
Fused 10 amp, 20mm glass quick blow
fuse.
Rain + - Rain sensor signal input. 470R alarm.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 14mA, unfused.
PIR + - PIR input N/C contacts. Alarm = 8K, 4K7
Ohm 5% 0.25W EOL resistor.
Monitoring current limit 14mA, unfused.
0/10v Input Positional voltage input, 10% steps of
motor time.
Max 10v dc, 75K Ωimpedance.
Com Common 0v output. Reference ground.
0/10v Output Positional voltage output, 10% steps. 680R impedance, max 10v dc 2mA. Max
20K Ωload.
Ce manuel convient aux modèles suivants
6
Table des matières
Autres manuels Haes Panneau de contrôle

Haes
Haes ELAN HS-5100 Manuel utilisateur

Haes
Haes ELAN HS-5000 Series Manuel utilisateur

Haes
Haes Excel-EN Mode d’emploi

Haes
Haes FUSION 0832-CPD-1431 Manuel utilisateur

Haes
Haes AlarmSense Mode d’emploi

Haes
Haes SZAOV Mode d’emploi

Haes
Haes ELAN HS-5200 Instructions de montage

Haes
Haes Excel-32 Series Mode d’emploi

Haes
Haes ESENTO MARINE Mode d’emploi

Haes
Haes Excel-32 Series Manuel utilisateur