Global Fire Equipment ORION PLUS Mode d’emploi

OVERVIEW
INTRODUCTION
This document covers the installation and commissioning of an ORION PLUS fire alarm panel. This document is intended
for use by a competent and qualified, fire alarm installation engineer. .
The ORION PLUS fire alarm system should be tailored to the building requirements. The complete system should be
designed to meet all applicable regulations. The installation must then be performed in accordance with the system
design. This manual not only clarifies the components and connections during installation but will also assist in
commissioning and maintenance. .
This manual covers the installation and commissioning of a complete system. .
All PCBs contain Electrostatic Sensitive Devices. .
Take suitable ESD (Electrostatic Discharge) precautions when removing or installing printed circuit boards
(PCBs).
ORION PLUS FIRE ALARM PANEL - KEY FEATURES
8 Zone Conventional Panel - Expandable up to 16 zones.
Supports connection to Repeater via RS485, Fibre-Optic or TCP/IP
32 devices per zone
Compatible with all our own low cost ancillary modules
1 Fire output relay (change-over) and 1 Fault relay (change-over)
2 conventional alarm outputs (Individually programmable)
All detection zones monitored for integrity
Backlit Graphical LCD display
Programming by integrated keypad or Loader PC software
ELECTRO-STATIC SENSITIVE DEVICES (ESD)
TAKE SUITABLE ESD PRECAUTIONS WHEN REMOVING OR
INSTALLING PRINTED CIRCUIT BOARDS.
INSTALLATION & COMMISSIONING MANUAL - 05/2016
ORION PLUS - CONVENTIONAL FIRE ALARM CONTROL PANEL
Manufacturers of Fire Detection Equipment
www.globalfire.pt

ACCESS LEVEL 1 - General User
Unless otherwise indicated, in order to enable the operation of a particular switch, either a valid User or Programming
Access Code is required.
The only exceptions are the following:
1- LampTest Switch
2- Queue Review Switches( Fire, Fault, Test and Disabled)
3- Delays Active Switch. During an alarm condition and while delays are active.
By entering a valid User Access Code (Factory default ppppp), the authorized user gains access to the operation
of all switches at the front of the panel display. Authorized User Access also grants the possibility of enabling or
disabling zones.
ACCESS LEVEL 2 - Authorized User Controls
Access to this level is accomplished by the introduction of a code using the panel keypad.The user code is factory set to
pppppand after entering each digit in turn, press OK to confirm entry.
INTERNAL BUZZER SILENCE
The occurrence of any new fire or fault condition will initiate the operation of the internal buzzer. By pressing this
switch, the operation of the buzzer will be stopped until a new fire or fault appears on the system.
ALARM SILENCE/RESOUND
Activates all sounders. A second press deactivates all sounders.The button LED (red) is illuminated whilst the sounders
are activated.
SOUNDERS ENABLE/DISABLE
Pressing this button will enable/disable all conventional sounder circuits .
DELAYS ACTIVE
Pressing this button will activate any preprogrammed delays. The yellow LED associated with this button and the
general disablements LED will both be lit. A second press of this button will deactivate the delays and the LED. Under
any fire condition the delays will be activated. If during the course of these delays, at access level 1(General User - code
entry not required), this button is pressed, the delays will be overridden and the sounders and together with any other
fire indicating equipment, will be activated.
USER & INSTALLER ACCESS CODES
To enter both codes use the arrow keys upqand when finished press ENTER.
Access Level 2 - Press ENTER, then Authorized User Access Code pppppand then press ENTER to confirm entry.
Access Level 3 - Press ENTER, then Installer Access Code pqpqpand then press ENTER to confirm entry
MAIN PANEL KEYPAD INSTRUCTIONS
ENTER Used to confirm entry of any data or selection.
pUsed to increase selection or number. Also used for code entry.
qUsed to decrease selection or number. Also used for code entry.
uUsed to change data entry field/ location.
ESC Escape key. Used to exit a particular function.
It is not possible to introduce text for labels using the front panel keypad.NOTE:
INSTALLATION & COMMISSIONING MANUAL - 05/2016
ORION PLUS - CONVENTIONAL FIRE ALARM CONTROL PANEL
Manufacturers of Fire Detection Equipment
www.globalfire.pt

TYPICAL SYSTEM SCHEMATIC
MANUAL
CALL
POINT
SMOKE
OR HEAT
DETECTOR
SMOKE
OR HEAT
DETECTOR
MANUAL
CALL
POINT END OF LINE
CAPACITOR
END OF LINE
RESISTOR
10K Ohm
POLARIZED
SOUNDER
POLARIZED
SOUNDER
POLARIZED
SOUNDER
Auxilliary
Relay
Outputs
Auxilliary
Supply
Outputs
Remote
Inputs
INSTALLATION & COMMISSIONING MANUAL - 05/2016
ORION PLUS - CONVENTIONAL FIRE ALARM CONTROL PANEL
Manufacturers of Fire Detection Equipment
www.globalfire.pt

Voltage
EMC Standard EN55022 class B
EN61000-4-2,3,4,5,6,8,11
EN61000-3-2,3
Current
2.4 A PSU’s recommended for 8-16 zones panels.
The maximum alarm sounder current is 400mA for both conventional sounder circuits.
Battery
Internal maximum 24V / 7AH
Primary supply voltage 85 - 264 V A.C.
POWER REQUIREMENTS
NEUTRAL
LIVE
MEANWELL
DANGER
220 VOLTS
MODEL: PS-65-27
EARTH
POWER SUPPLY SPECIFICATION - MEANWELL Model: PS-65-27
MAINS SUPPLY VOLTAGE
INTERNAL POWER SUPPLY
TOTAL OUTPUT CURRENT
SUPPLY AND BATTERY CHARGER MONITORED?
BATTERIES MONITORED
MAX BATTERY SIZE
MAINS FUSE
BATTERY FUSE
MAX CURRENT DRAW FROM BATTERY (MAINS FAIL)
85-264 V 50/60 Hz
Min. 20 V DC - Max. 30 V DC
(28.5 V DC nominal) Max. Ripple 1 V peak-peak
2.4 A @ 230 Vac
YES
YES
2 x 12 V 7AH VRLA
4 A - 250 V Slow Blow - 20 mm
1.6 Amp Resettable - Electronic Fuse
1.5 Amp Max. @ Max. Operating Temperature
INSTALLATION & COMMISSIONING MANUAL - 05/2016
ORION PLUS - CONVENTIONAL FIRE ALARM CONTROL PANEL
Manufacturers of Fire Detection Equipment
www.globalfire.pt

Min battery capacity 2 x 2 Ah 12 V DC
Max Battery capacity 2 x 7 Ah 12 V DC
Always use Lead- acid VRLA Batteries
The battery Ah required for a given installation is calculated from the following formula:
Quiescent current of the panel with everything is found by adding the standby current of all connected
devices to the standby current of the panel (38 mA).
Consult the manual for the individual devices to confirm the standby current.
Quiescent current in
mA of the panel with
everything connected
Alarm current in Amps
(sounder load)
Standby time
required in hours
divided by 1000
Alarm time in
hours
XX
( () )
+ + 20%
Round up to the next available battery size.
BATTERY REQUIREMENTS
INSTALLATION & COMMISSIONING MANUAL - 05/2016
ORION PLUS - CONVENTIONAL FIRE ALARM CONTROL PANEL
Manufacturers of Fire Detection Equipment
www.globalfire.pt

ABS BOX INFORMATION
106 mm
33 70 3
273 mm
403 mm
VIEW FROM SIDE
VIEW FROM TOP
VIEW FROM FRONT VIEW FROM REAR
DIMENSIONS
SIZE
WEIGHT WITHOUT BATTERIES
273 (W) x 403 (L) x 106 (H) mm
1,6 Kgs
INSTALLATION & COMMISSIONING MANUAL - 05/2016
ORION PLUS - CONVENTIONAL FIRE ALARM CONTROL PANEL
Manufacturers of Fire Detection Equipment
www.globalfire.pt

FITTING ORION PLUS EXPANSION ZONE CARD
1 - This operation should only be performed by qualified personnel.
2 - Power to the panel should be completely removed, both primary and secondary (batteries)
supplies, before the installation process of the card is initiated.
3 - Use 5-way flat cable assembly provided to interconnect expansion board and panel’s main board.
After process is complete re-apply power to the panel.
4 - Panel should be in installation mode. Green (Status) LED should be flashing. See function 8.4.1
5 - Confirm using function 7.1 that expansion zones have been detected.
6 - No programming is required in order to enable the zone expansion card. This card is automatically detected by
the panel.
IDENTIFYING COMPONENTS
.
INSIDE ORION PLUS
4-ZONE
EXPANSION
BOARD
CONNECTOR
4-ZONE
EXPANSION
BOARD
CONNECTOR
POWER
SUPPLY
UNIT
4-ZONE
EXPANSION
BOARD
4-ZONE
EXPANSION
BOARD
INSTALLATION & COMMISSIONING MANUAL - 05/2016
ORION PLUS - CONVENTIONAL FIRE ALARM CONTROL PANEL
Manufacturers of Fire Detection Equipment
www.globalfire.pt

J-NET-INT-FO
FIBRE OPTIC INTERFACE
J-NET-INT-485-NEW
INTERFACE FOR RS485
COMMUNICATION
J-NET-INT-TCP/IP
INTERFACE FOR TCP/IP
COMMUNICATION
NOTE: ORION PLUS can only be networked with repeater panels.
Typical cable form (one end)
VIEW FROM TOP
THROUGHOUT THE MANUAL,
THE PIN ON THE 5 WAY MOLEX
INDICATES WHICH PIN IS
RED
Nº1
VIEW FROM FRONT
MALE FEMALE
NOTE:
INSTALLATION & COMMISSIONING MANUAL - 05/2016
ORION PLUS - CONVENTIONAL FIRE ALARM CONTROL PANEL
Manufacturers of Fire Detection Equipment
www.globalfire.pt
Autres manuels pour ORION PLUS
1
Table des matières
Autres manuels Global Fire Equipment Panneau de contrôle

Global Fire Equipment
Global Fire Equipment NODE+ Manuel utilisateur

Global Fire Equipment
Global Fire Equipment JUNIOR MINI-REP Manuel utilisateur

Global Fire Equipment
Global Fire Equipment Junior V4 Manuel

Global Fire Equipment
Global Fire Equipment ORION PLUS Manuel utilisateur

Global Fire Equipment
Global Fire Equipment JUNO NET Manuel d'instructions