GEK-106465A CIO Remote CAN Digital I/O Module 1
1. OVERVIEW 3
1.1. IMPORTANT PROCEDURES 3
1.1.1. INSPECTION CHECKLIST....................................................................................................................4
1.1.2. SAFETY INSTRUCTIONS.....................................................................................................................6
1.2. OVERVIEW 7
1.2.1. INTRODUCTION TO F650 AND F600 FAMILY OF RELAYS...............................................................7
1.2.2. HARDWARE ARCHITECTURE.............................................................................................................7
1.2.3. SOFTWARE ARCHITECTURE.............................................................................................................7
1.2.4. COMMUNICATIONS ARCHITECTURE................................................................................................8
2. PRODUCT DESCRIPTION 9
2.1. OVERVIEW 9
2.2. SUMMARY OF FEATURES 9
2.3. ORDERING CODE 10
2.4. TECHNICAL SPECIFICATIONS 11
2.4.1. INPUTS................................................................................................................................................11
2.4.2. OUTPUTS............................................................................................................................................11
2.4.3. CONTROL POWER SUPPLY .............................................................................................................11
2.4.4. CAN BUS.............................................................................................................................................11
2.4.5. ENVIRONMENTAL CHARACTERISTICS...........................................................................................11
2.4.6. PACKAGING AND WEIGHT ...............................................................................................................12
2.4.7. TYPE TESTS.......................................................................................................................................12
2.4.8. APPROVALS.......................................................................................................................................12
3. HARDWARE 13
3.1. MODULE DESCRIPTION 13
3.2. MECHANICAL DESCRIPTION 14
3.2.1. MOUNTING .........................................................................................................................................14
3.2.2. REAR COVER DESCRIPTION ...........................................................................................................16
3.3. WIRING 17
3.3.1. EXTERNAL CONNECTIONS..............................................................................................................17
3.4. BOARDS 19
3.4.1. BOARD OPTION 1..............................................................................................................................19
3.4.2. BOARD OPTION 2..............................................................................................................................20
4. USER INTERFACES 29
4.1. SOFTWARE 29
4.2. FRONT INDICATORS 29

TABLE OF CONTENTS
2 CIO Remote CAN Digital I/O Module GEK-106465A
5. INPUT/OUTPUT MODULES DESCRIPTION 31
5.1. CIRCUIT SUPERVISION AND CONTACT SEAL-IN CIRCUITS 31
5.1.1. CIRCUIT SUPERVISION.....................................................................................................................31
5.1.2. CONTACT SEAL-IN ............................................................................................................................31
5.2. CONTROL SETTINGS FOR INPUTS/OUTPUTS 32
5.2.1. INPUT/OUTPUT BOARDS SETTINGS...............................................................................................32
5.2.2. INPUTS/OUTPUTS STATUS..............................................................................................................36
6. ACCEPTANCE TESTS 39
6.1. VISUAL INSPECTION 39
6.2. GENERAL CONSIDERATIONS ON THE POWER SUPPLY NETWORK 39
6.3. ISOLATION TESTS 40
6.4. INDICATORS 40
6.5. POWER SUPLY TESTING 40
6.6. COMMUNICATION WITH THE MASTER UNIT 41
6.7. INPUTS AND OUTPUTS 41
6.7.1. DIGITAL INPUTS.................................................................................................................................41
6.7.2. CONTACT OUTPUTS.........................................................................................................................42
6.7.3. CIRCUIT CONTINUITY SUPERVISION INPUTS...............................................................................42
6.7.4. LATCHING CIRCUITS.........................................................................................................................42

OVERVIEW
GEK-106465A CIO Remote CAN Digital I/O Module 3
!
1. OVERVIEW
1.1. IMPORTANT PROCEDURES
To help ensure years of trouble free operation, please read through the following chapter for information to help guide
you through the initial installation procedures of your new relay.
BEFORE ATTEMPTING TO INSTALL OR USE THE RELAY, IT IS IMPERATIVE THAT ALL WARNINGS AND
CAUTIONS IN THIS MANUAL ARE REVIEWED TO HELP PREVENT PERSONAL INJURY, EQUIPMENT
CAUTION: THE OPERATOR OF THIS INSTRUMENT IS ADVISED THAT IF THE EQUIPMENT IS USED IN A
MANNER NOT SPECIFIED IN THIS MANUAL, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE
IMPAIRED
FIGURE 1-1 CIO FRONT VIEW
Installation must be according to the national electric code of the appropriate country

OVERVIEW
4 CIO Remote CAN Digital I/O Module GEK-106465A
1.1.1. INSPECTION CHECKLIST
- Open the relay packaging and inspect the relay for physical damage.
Refer to the label on the side of the relay verifies that the model number is the correct model ordered.
FIGURE 1-2 IDENTIFICATION LABEL (A4454P5)
- Please ensure that you receive the following items with your CIO unit:
- Mounting screws for rear terminals and for fixing the relay to a cabinet
- Wiring diagram
For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin
Home Page www.GEMultilin.com.

OVERVIEW
GEK-106465A CIO Remote CAN Digital I/O Module 5
Note: If there is any physical damage detected on the relay, or any of the contents listed are missing, please
contact GE Multilin immediately at:
EUROPE, MIDDLE EAST AND AFRICA:
GE MULTILIN
Avda. Pinoa, 10
48170 Zamudio, Vizcaya (SPAIN)
Tel.: (34) 94-485 88 00, Fax: (34) 94-485 88 45
E-mail: [email protected]
AMERICA, ASIA AND AUSTRALIA:
GE MULTILIN
215, Anderson Avenue
L6E 1B3 Markham, ON (CANADA)
Tel.: +1 905 294 6222, Fax: +1 905 201 2098
E-mail: [email protected]
The information provided herein does not intend to cover all details of variations of the equipment nor does
it take into account the circumstances that may be present in your installation, operating or maintenance
activities.
Should you wish to receive additional information, or for any particular problem that cannot be solved by
referring to the information contained herein, please contact GENERAL ELECTRIC MULTILIN.

OVERVIEW
6 CIO Remote CAN Digital I/O Module GEK-106465A
1.1.2. SAFETY INSTRUCTIONS
The CIO ground screw located on the rear of the unit must be correctly grounded.
This is required not only for personal protection, but also for avoiding a voltage difference between the CIO serial port
and the master unit port, which could produce anomalies in communication.
GE Multilin will not be responsible for any damage in the relay or connected equipment whenever this elemental
safety rule is not followed.

OVERVIEW
GEK-106465A CIO Remote CAN Digital I/O Module 7
1.2. OVERVIEW
1.2.1. INTRODUCTION TO F650 AND F600 FAMILY OF RELAYS
This platform of relays has been designed to meet the goals that are appearing nowadays in the environment of new
substations. Historically, protection, control and metering functions have been performed by electromechanical
elements at the beginning, then static devices, and finally by digital equipment able to integrate all these functions in
a single device, called IED (Intelligent Electronic Device).
Due to the huge number of signals to be controlled and monitored nowadays in a substation environment, there is a
new need for a great number of digital inputs and outputs to retrieve states and to signal or perform all different
operations. CIO units respond to this need, allowing connection to F650 and F600 IEDs, and increasing the number
of available inputs and outputs depending on the connected equipment.
1.2.2. HARDWARE ARCHITECTURE
CIO units incorporate a series of interconnected modules to operate. These modules are a power supply and
input/output boards.
FIGURE 1-3 HARDWARE ARCHITECTURE
As shown on the diagram above, Contact Inputs/Outputs are signals associated to physical input/output contacts in
the relay, and their status is sent/received through the CAN BUS of the associated equipment, F600 or F650.
This CAN connection to the master unit can be made through fiber optic cable or through copper cable.
CIO units can incorporate up to two I/O boards, each of which must have a unique address in the system. For this
purpose, there is a switch at the rear of the unit with 16 positions (0 to F), that allows indicating the address for board
H. The address of board J is fixed to “board H address + 1”.
1.2.3. SOFTWARE ARCHITECTURE
Each I/O board includes a microprocessor that manages communication with the master unit, as well as sampling
and activation of the corresponding inputs and outputs.
The firmware (software embedded in the boards) has been designed using object oriented programming techniques
(ODD/OOP). These techniques are based on the use of objects and classes, and provide the software architecture
with the same characteristics as the hardware architecture, i.e., modularity and flexibility.
Contact Out
p
uts
Contact In
p
uts
BUS
CIO

OVERVIEW
8 CIO Remote CAN Digital I/O Module GEK-106465A
1.2.4. COMMUNICATIONS ARCHITECTURE
CIO units incorporate a CAN BUS port in two physical media: glass fiber optic and cable. The fiber optic port allows
connection to the master unit for a single CIO unit. For connections including several CIO units, the cable port must
be used. If the master unit is a F650, then communication must always be in fiber optic.

PRODUCT DESCRIPTION
GEK-106465A CIO Remote CAN Digital I/O Module 9
2. PRODUCT DESCRIPTION
2.1. OVERVIEW
The CIO module is an input/output extension for F650 and F600 units. Using this module, the number of available
inputs/outputs can be increased, these inputs/outputs operation being identical to the one of the original I/Os in
the master unit.
The CIO module has been designed to be installed close to the substation switchgear, and connected to the main
unit through a CAN bus in fiber optic or cable. Fiber optic connection provides total immunity against
electromagnetic disturbances, as well as simplified wiring and commissioning.
CIO module I/O configuration and management are performed exclusively from the master unit. This master unit
manages the CIO inputs and outputs in the same way as its own.
2.2. SUMMARY OF FEATURES
INPUTS
Inputs programmable from the master unit.
Programmable activation voltage level
Programmable debounce time for each inputs group
Possibility to select positive or negative activation logic
Possibility to select pulse or level activation.
OUTPUTS
Outputs programmable from the master unit
Possibility to select positive or negative activation logic
Selectable pulse mode activation
Selectable latched configuration
Breaker tripping and Closing circuits supervision
Ce manuel convient aux modèles suivants
1
Table des matières
Autres manuels GE Unité de distribution d'énergie

GE
GE AF-600 FP Series Manuel utilisateur

GE
GE L30 Manuel utilisateur

GE
GE Multilin 489 Manuel utilisateur

GE
GE 745 TRANSFORMER MANAGEMENT RELAY Manuel utilisateur

GE
GE D90 Plus Manuel utilisateur

GE
GE ALPS Manuel utilisateur

GE
GE L90 Manuel utilisateur

GE
GE SPM Series Manuel utilisateur

GE
GE D30 series Manuel utilisateur

GE
GE QuiXtra 4000 Guide de démarrage rapide