GE Multilin MM200 Manuel utilisateur

LISTED
52TL
IND.CONT. EQ.
E83849
Title page
GE Multilin's Quality
Management System is
registered to ISO9001:2000
QMI # 005094
Digital Energy
Multilin
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet: http://www.GEmultilin.com
QuickStart Guide
MM200 revision: 1.11
Manual P/N: 1601-9030-A4
GE publication code: GEK-113401C
Copyright © 2009 GE Multilin
IISO9001:2000
G
E
M
U
L
T
I
L
I
N
R
E
G
I
S
T
E
R
E
D
*1601-9030-A4*
MM200
Motor Management System
Low voltage motor protection and control

© 2009 GE Multilin Incorporated. All rights reserved.
GE Multilin MM200 Motor Management System QuickStart Guide for revision 1.1x.
MM200 Motor Management System, EnerVista, EnerVista Launchpad, EnerVista MM200
Setup, and FlexLogic are registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-9030-A4 (January 2009)

TABLE OF CONTENTS
MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE toc–1
Table of Contents
Overview ..........................................................................................................................1
Mechanical installation..................................................................................................................................2
Dimensions ......................................................................................................................................................... 2
Product identification..................................................................................................................................... 3
Mounting.............................................................................................................................................................. 4
Electrical installation.......................................................................................................................................5
Full-voltage non-reversing starter........................................................................................................... 9
RS485 connections .......................................................................................................................................10
Control panel...................................................................................................................................................11
Basic control panel .......................................................................................................................................11
Setpoints ........................................................................................................................13
Understanding setpoints ........................................................................................................................... 13
Configuration setpoints..............................................................................................................................13
Motor setpoints...............................................................................................................................................13
Common motor setpoints..........................................................................................................................13
Current transformers ...................................................................................................................................15
Protection elements.....................................................................................................16
Thermal protection....................................................................................................................................... 16
Overload curve................................................................................................................................................16
Communications interfaces .......................................................................................19
Specifications................................................................................................................20
Protection specifications ...........................................................................................................................20
Inputs specifications .................................................................................................................................... 21
Outputs specifications ................................................................................................................................22
Power supply specifications.....................................................................................................................22
Communications specifications.............................................................................................................22
Testing and certification ............................................................................................................................23
Physical specifications................................................................................................................................23
Environmental specifications .................................................................................................................. 24
MM200 order codes......................................................................................................25
Example of an MM200 order code........................................................................................................25
INDEX
SUMMARY OF CERTIFICATION

toc–2 MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
TABLE OF CONTENTS

MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 1
MM200 Motor Management System
QuickStart Guide
Digital Energy
Multilin
QuickStart Guide
1.1 Overview
The MM200 is a motor protection and control system designed specifically for low-voltage
motor applications. The MM200 provides the following key benefits.
• Protection, control, and communication options to suit low-voltage motor
applications.
• Small footprint designed specifically for IEC and NEMA MCC applications.
• DIN rail Mounting.
• Multiple communication protocols allows simple integration into monitoring and
control systems.
• Optional basic control panel interface provides local control and access to system
information.

2MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
OVERVIEW QUICKSTART GUIDE
Figure 1: Single line diagram
Table 1: MM200 protection functions
1.1.1 Mechanical installation
This section describes the mechanical installation of the MM200 system, including
dimensions for mounting.
1.1.1.1 Dimensions
The MM200 is packaged in a fixed format divided into three specific sections.
The dimensions of the MM200 are shown below. Additional dimensions for mounting are
shown in the following sections.
RS485 - Modbus RTU
Profibus/DeviceNet
52
METERING
A
51R 49 37 46
50G
MOTOR
LOAD
Temperature
Thermistor
Phase CT 3
Ground CT 1
Power Fuse
BUS
MM200
MOTOR MANAGEMENT SYSTEM
Contactor
888739A2.CDR
LO: 7 inputs and 3 outputs
HI: 6 inputs and 3 outputs
LO:24VDC
HI:84to250VDC/60to300VAC
ANSI device Description
37 Undercurrent and underpower
46 Current unbalance
49 Thermal overload
50G Ground instantaneous overcurrent
51R Locked/stalled rotor, mechanical jam

QUICKSTART GUIDE OVERVIEW
MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 3
Figure 2: MM200 dimensions
1.1.1.2 Product identification
The product identification label is located on the side panel of the MM200. This label
indicates the product model, serial number, firmware revision, and date of manufacture.
Figure 3: MM200 Identification label
888748A1.CDR
Model:
Serial Number:
Firmware: Mfg.Date:

4MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
OVERVIEW QUICKSTART GUIDE
Figure 4: MM200 ratings label
1.1.1.3 Mounting
The MM200 is DIN rail mounted.
The standard DIN rail mounting is illustrated below. The DIN rail conforms to EN 50022.
CAUTION
CAUTION: To avoid the potential for personal injury due to fire hazards, ensure the unit is
mounted in a safe location and/or within an appropriate enclosure.
Figure 5: DIN rail mounting
1.1.2 Electrical installation
This section describes the electrical installation of the MM200 system. An overview of the
MM200 terminal connections is shown below.

QUICKSTART GUIDE OVERVIEW
MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 5
CAUTION
CAUTION: MM200 is not to be used in any way other than described in this manual.
Figure 6: MM200 terminal connection overview
A Modbus RTU RS485 port, a thermistor input, and a 50:0.025 CBCT input are provided.
Profibus and Devicenet are provided as options.
Table 2: Slot position
Figure 7: MM200 terminal connection torque rating
CAUTION
CAUTION: Use gauge size appropriate for the voltage and current draw of the device.
Slot Type
A PSU/Inputs/Control Panel
BCPU/CTs
C Outputs/CBCT/Thermistor/RS485
Control Panel
Profibus or DeviceNet
Optional fieldbus protocols
888740A2.CDR
CTs
PSU
Inputs
RS485
Thermistor
CBCT
2 x Form A
1 x Form C
connector screw torque
CT 4.5 lb-in
IPS, output 5.0 lb-in
Fieldbus, 3.0 lb-in
Thermistor & RS485

6MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
OVERVIEW QUICKSTART GUIDE
Table 3: Wire Gauge Sizes
NOTE
NOTE: It is recommended that you install a circuit disconnection system for control power, near
the device, which should be easily accessible after installation of the unit. This is in case an
emergency power shut-down of the unit is required.
Figure 8: Top and Rear panel arrangement
The MM200 I/O terminals are labeled with a two-character identifier. The first character
identifies slot position and the second identifies the terminal.
Slot A PSU and Inputs 12 AWG (2.5 mm2) (5.00mm pitch terminals)1
1.Wire gauge size remains constant; increased pitch distance reflects higher voltage rating.
Slot B Fieldbus,
CT Connections
16 AWG (1.5 mm2) (3.50mm pitch terminals)12 AWG
(2.5 mm2) (7.62mm pitch terminals)1
Slot C RS485 & ThermistorOutput Relays,
CBCT 16 AWG (1.5 mm2) (3.50mm pitch terminals12 AWG
(2.5 mm2) (5.00mm pitch terminals)1
Autres manuels pour MM200
1
Table des matières
Autres manuels GE Multilin Dispositif de protection
Manuels Dispositif de protection populaires d'autres marques

nxt
nxt BIA-nXt-DPC 1-22 Manuel utilisateur

TFortis
TFortis SG-Switch Manuel utilisateur

BERNINI DESIGN
BERNINI DESIGN Be172 Manuel utilisateur

Rayleigh Instruments
Rayleigh Instruments RI-ENERGYSET-3P-ESS-50-100 Manuel utilisateur

GE
GE Multilin 3 Series Manuel utilisateur

E.K.T.
E.K.T. ke-DP01 Manuel utilisateur