GarrettCom Magnum IPS42 Manuel utilisateur

www GarrettCom com
..
www GarrettCom com
..
Corporate Headquarters
GarrettCom, Inc.
47823 Westinghouse Dr.
Fremont, CA 94539
Phone (510) 438-9071
Fax (510) 438-9072
Website: http://www.GarrettCom.com
Email: [email protected]om
Magnum IPS42 Internal Power Supply
for Edge Switch Family
Installation and User Guide
$5.00 USD

IPS42 Internal Power Supply Installation and User Guide (11/09)
i
www GarrettCom com
..
Magnum™IPS42 Internal Power Supply for
Edge Switch Family
Installation and User Guide
Part #: 84-00181Z Rev. B
Trademarks
GarrettCom is a registered trademark and Magnum, Dymec, DynaStar, Personal
Switch, Link-Loss-Learn, S-Ring, Convenient Switch and Converter Switch
are trademarks of GarrettCom, Inc.
Ethernet is a trademark of Xerox Corporation
NEBS is a trademark of Telcordia Technologies
UL is a registered trademark of Underwriters Laboratories

IPS42 Internal Power Supply Installation and User Guide (11/09)
ii
www GarrettCom com
..
Important: The Magnum IPS42 Series Internal Power Supply for Edge Switches
contains no user serviceable parts. Attempted service by unauthorized personnel shall
render all warranties null and void. If problems are experienced with Magnum IPS42
Internal Power Supply products, consult Section 4, Troubleshooting, of this User Guide.
Copyright ©2009 GarrettCom, Inc. All rights reserved. No part of this publication may
be reproduced without prior written permission from GarrettCom, Inc.
Printed in the United States of America.
GarrettCom, Inc. reserves the right to change specifications, performance characteristics
and/or model offerings without notice.

IPS42 Internal Power Supply Installation and User Guide (11/09)
iii
www GarrettCom com
..
Federal Communications Commission
Radio Frequency Interference Statement
This equipment generates, uses and can radiate frequency energy and if not
installed and used properly, that is in strict accordance with the manufacturer's
instructions, may cause interference to radio communication. It has been tested and
found to comply with the limits for a Class A computing device in accordance with the
specifications in Subpart J of Part 15 of FCC rules, which are designed to provide
reasonable protection against such interference when operated in a commercial
environment. Operation of this equipment in a residential area is likely to cause
interference, in which case the user, at his own expense, will be required to take
whatever measures may be required to correct the interference.

IPS42 Internal Power Supply Installation and User Guide (11/09)
iv
www GarrettCom com
..
Electrical Safety requirements:
1. This product is to be installed Only in Restricted Access Areas
(Dedicated Equipment Rooms, Electrical Closets, or the like).
2. 48VDC products shall be installed with a readily accessible disconnect
device in the building installation supply circuit to the product.
3. This product shall be provided with a maximum 10A DC Listed fuse or
circuit breaker in the supply circuit when connected to a 48V
centralized source.
4. The external power supply for DC units shall be Listed, Direct Plug In
power unit, marked Class 2, or listed ITE Power Supply, marked LPS,
which has suitably rated output voltage (i.e. 24VDC or 48VDC) and suitable
rated output current.
5. Product does not contain user replaceable fuses. Any internal fuses can
ONLY be replaced by GarrettCom personnel through the RMA process.

IPS42 Internal Power Supply Installation and User Guide (11/09)
v
www GarrettCom com
..
Contacting GarrettCom, Inc
Please use the mailing address, phone, fax numbers and email address listed below:
GarrettCom, Inc.
47823 Westinghouse Dr.
Fremont, CA 94539
Phone (510) 438-9071
Fax (510) 438-9072
Website: http://www.GarrettCom.com
Email: [email protected]

IPS42 Internal Power Supply Installation and User Guide (11/09)
vi
www GarrettCom com
..
TABLE OF CONTENTS Page
1.0SPECIFICATIONS ............................................................................... 1
1.1Technical Specifications...................................................................... 1
1.2Summary of models and descriptions for IPS42 Series:...................... 5
2.0INTRODUCTION ................................................................................. 8
2.1Inspecting the Package and the Product............................................... 8
2.2Product Description ............................................................................. 9
2.3Features and Benefits......................................................................... 10
3.0INSTALLATION................................................................................. 11
3.1Locating the IPS42............................................................................. 11
3.1.1Mounting Dimensions for IPS42 with metal brackets............... 12
3.1.2 DIN-Rail mounting option......................................................... 15
3.2Power Cord Installation ..................................................................... 16
3.3Hardware operated Alarm Contact .................................................... 20
4.0TROUBLESHOOTING...................................................................... 21
4.1Before Calling for Assistance............................................................ 22

IPS42 Internal Power Supply Installation and User Guide (11/09)
vii
www GarrettCom com
..
4.2When Calling for Assistance ............................................................. 24
4.3Return Material Authorization (RMA) Procedure............................. 25
4.4Shipping and Packaging Information................................................. 26
APPENDIX A: WARRANTY INFORMATION......................................... 28
Revisions
Rev. B 11/09: Updated DIN Rail mount photo (Sec. 3.1.2)
Rev. A 07/09: Initial Release

IPS42 Internal Power Supply Installation and User Guide (11/09)
1
www GarrettCom com
..
1.0 SPECIFICATIONS
1.1 Technical Specifications
AC/DC Power Supply (Model IPS42-AC/DC):
Power Input: DC: 100-250 VDC
AC: 100-250 VAC, 47 to 63 Hz, auto ranging
Surge Rating: IEC 61000-4-3, Class 3/4 (4KV for DC)
Std. Recessed Terminal Block: “-, GND, +”, UL Listed
Power Consumption: 10 Watts typical for a 4+2 port fiber model
DC Power Supplies for Dual Source DC:
125VDC: Input 100 to 250VDC nominal
48VDC: Input 44 to 57VDC
24VDC: Input 20 to 36VDC
Surge Rating: IEC 61000-4-3, Class 3/4 (4KV for DC)
Std. Terminal Block for DualSRC: A: “-, GND, +”, B: “-, GND, +”
Power Consumption: 10 Watts typical for a 4+2 port fiber model

IPS42 Internal Power Supply Installation and User Guide (11/09)
2
www GarrettCom com
..
AC Power Supply (Model IPS42-AC)
AC Power Connector: standard IEC 320 male, recessed
Power Input: 100-250 VAC, 47 to 63 Hz, auto ranging
Power Consumption: 10 Watts typical for a 4+2 port fiber model
Mechanical Specifications:
Enclosure: Rugged sheet metal (Aluminum).
Dimensions of the IPS42 unit:
6.0 in H x 5.5 in W x 1.7 in D (15.2 cm x 14.0 cm x 4.3 cm)
Weight: all models: 1.5 lbs. (0.68 kg)
Operating Environment:
IEC 60068 “Type Test” exceeds -40° to 185°F (-40° to 85°C)
Storage: -60°to 212°F (-50°to 100°C)
Relative Humidity: 5% to 95% (non-condensing)
Altitude: -200 to 13000FT (-60 to 4000M)
UL 60950 “Component Parts” rating: -40° to 140°F (-40° to 60°C)
Conformal coating (humidity protection): optional