FireClass FC430LPBSB Manuel utilisateur

FIRECLASS Fire Detection System EN54-23 Open Class—FC430LPBSB LP Loop Powered Beacon-Sounder Base
Product Information Doc. Version 2 1/14
EN54-23 Open Class—FC430LPBSB LP Loop
Powered Beacon-Sounder Base
Introduction
The EN54-23 Open Class—FC430LPBSB LP Loop Pow-
ered Beacon-Sounder Base is designed to be driven
from a FIRECLASS controller via the addressable loop.
The FC430LPBSB LP is designed to be fitted between
a detector and a 4" mounting flange.
A ‘Type A’ mounting flange is supplied with the base
and can be fixed to a flat surface or a suitable electrical
backbox with standard 50 mm, or 70 mm fixing centres.
Alternatively, a DAB3-4 mounting flange (to be ordered
separately, refer to “Order Information” on page 14)
can be used with surface mount trunking.
Fig. 1 shows a general view of the base.
The beacon-sounder base may be used without a detec-
tor by fitting a blanking cap (see “Order Information” on
page 14).
The detector or blanking cap must be locked onto the
beacon-sounder base by using a locking device (sup-
plied).
The sounder has four volume settings:
High (90 dB ±3),
Mid High (80 dB ±3),
Mid Low (70 dB ±3) and
Low (60 dB ±3).
The beacon emits a white flashing light and has two
flash rates:
Slow Flash (½ Hz), or
Fast Flash (1 Hz).
The FC430LPBSB LP Beacon-Sounder Base devices are
synchronised, but not synchronous with other sounders
(FC430SB/FC410SNM) and beacons (FC430SAB).
The first flash of the beacon is synchronised with the
start of the tone.
The FC430LPBSB LP Beacon-Sounder Base has a built
in two port isolator.
The FC430LPBSB LP Beacon-Sounder Base requires
two addresses, not including the associated detector.
Fig. 1: General View of EN54-23 Open Class—FC430LPBSB LP Beacon-Sounder Base
LOCKING DEVICE
FITS HERE
PROGRAMMING
PORT

2/14 Product Information Doc. Version 2
Technical Specification FIRECLASS Fire Detection System
Technical Specification
Mechanical Characteristics
The overall dimensions are shown in Fig. 2. All dimen-
sions are in mm.
.
Fig. 2: FC430LPBSB LP Beacon-Sounder with Mounting Flange—Overall Dimensions
44
11
50
11
FC430LPBSB LP WITH TYPE ‘A’ MOUNTING FLANGE
FC430LPBSB LP WITH DAB3-4 MOUNTING
Fig. 3: Mounting Flange—Fixing Dimensions
50
80
70
60
Mounting Beacon-Sounder
The beacon-sounder body clips onto the
mounting flange.

FIRECLASS Fire Detection System Technical Specification
Product Information Doc. Version 2 3/14
Environmental Characteristics
Performance Characteristics
EMC:
The FC430LPBSB LP Beacon-Sounder Base complies
with the following:
Product family standard EN50130-4 in respect of:
– Conducted Disturbances,
– Radiated Immunity,
– Electrostatic Discharge,
– Fast Transients and
– Slow High Energy.
EN61000-6-3 for Emissions
Parameter Value
Weight:
Beacon-Sounder
Base
160 g
Materials:
Beacon-Sounder ABS/PC FR
Mounting Surface mount or conduit
mount
Table 1: Technical Specification
Parameter Value
Temperature:
Operating
Storage
-10C to +55C
-25C to +70C
Humidity Up to 95% RH
(non-condensing)
Pressure Sounder output is quoted for
atmospheric pressure of
1000 mBar.
Vibration Meets the requirements of
EN 54-3 and EN 54-23.
Shock Meets the requirements of
EN 54-3 and EN 54-23*.
Corrosion Passes the SO2corrosion test
from EN 54-3 and EN 54-23.
IP Rating IP21C (EN 60529)
Table 2: Environmental Characteristics
*—The DAB3-4 mounting flange was not incorporated within
the scope of the EN 54-23 approval.
Parameter Value
Sound
Performance
SPL at 90° at a
distance of 1m:
High:
Mid high:
Mid low:
Low:
Note:
EN54-3:2001 does
not test at 90°.
90 dB±3
80 dB±3
70 dB±3
60 dB±3
Light
Performance:
Light colour:
Flash rate:
EN54-23 Category O:
White flashing light
Fast Flash 1 Hz, or
Slow Flash ½ Hz
Table 3: Performance Characteristics

4/14 Product Information Doc. Version 2
Technical Specification FIRECLASS Fire Detection System
Electrical Characteristics Alarm Current
Sounder Tones
Table 6 details the tones available for selection in FIRE-
CLASS Express.
Approved Tones
The tones shown in Table 6 are approved at volumes
‘High’, ‘Mid-high’ and ‘Mid-low’ to EN54-3 with the
exception of the Alternating (NF-S 32.001) tone, which
is only approved at volumes ‘High’ and ‘Mid-High’. The
approved tones meet the specification as shown in
Tables 7 to 21. The data applies to both horizontal and
vertical planes.
Parameter Value
Addressable Loop Voltage 20 - 40 Vdc
DC Loop Loading:
Quiescent
Alarm
350 A
See Table 5: “Alarm
Current”
Isolator:
Maximum Loop Voltage 40 Vdc
Minimum Loop Voltage 20 Vdc
Maximum Rated Continuous
Current (Isolator Closed)
2 A
Maximum Rated Switching
Current (s/c)
2 A
Maximum Leakage Current
(Isolator Open)
6 mA into zone
(10 mA into Isolator)
Maximum Series Impedance
(Isolator Closed)
0.25
Isolator Switching Threshold
(Isolator Closed to Open)
20 V or below
Isolator Switching Threshold
(Isolator Open to Closed):
2.9 V to 3.5 V from
s/c
Table 4: Electrical Characteristics
Parameter Low/
Mid-Low
Mid-High/
High
Unit
Sound Output 60/70 80/90 dB
Sounder Only 2.55 4.5 mA
Sounder and
Beacon 0.5 Hz
8.2 10 mA
Sounder and
Beacon 1 Hz
9.35 11.3 mA
Table 5: Alarm Current
NOTICE: Bell Tone
This is a simulated bell tone with a limited
bandwidth. It is not advisable to mix
conventional bells and electronic sounders
producing a simulated bell tone.

FIRECLASS Fire Detection System Technical Specification
Product Information Doc. Version 2 5/14
Device
Mode
Name Tone Description
Monitored
No pulsing in
FIRECLASS
Express
Monitored with
Pulse Pattern
Assigned in
FIRECLASS
Express
Pattern Frequency
(Hz)
Rate 60/
70db
80/
90db
60/
70db
80/
90db
1 Dutch Slow
Whoop
Sweep 500 to 1200 500 Hz rising to
1200 Hz over 3.5 s
silence 0.5s repeat
No Yes No No
2 7 Hz Fast
Sweep
Sweep 800 to 970 0.1428 s ramp @
7 Hz
No Yes No No
3BS1Hz
Sweep
Sweep 800 to 970 1 Hz No Yes No No
4 2 Tone Alternating 660 / 880 500 ms per tone No Yes No No
5 Temporal 4 Intermittent 880 500 ms on
500 ms off x 4
followed by 1.5 s
silence
No Yes No No
6 Australian
Sound
(AS 1670.4)
(Temporal 3
type tone)
Intermittent
+ Sweep
500 to 1200 500 ms on
500 ms off x 3
followed by 1.5 s
silence, sweep
during on periods
No Yes No No
7 March Time
Beep
Intermittent 880 500 ms on
500 ms off
No Yes No No
8 Continuous Continuous 970 Steady No Yes No Yes
9 DIN 1 Hz
Sweep
Sweep 1200 to 500 1200 Hz falling to
500 Hz over 1 s and
repeat
No Yes No No
10 Banshee LF
Buzzer
Sweep 800 to 950 120 Hz No Yes No No
11 3 Hz
Banshee Fast
Sweep
Sweep 800 to 950 3 Hz No Yes No No
12 9 Hz
Banshee Fast
Sweep
Sweep 800 to 950 9 Hz No Yes No No
13 Alternating
(NF-S 32.001)
Alternating 554 / 440 554 Hz for 100 ms
and 440 Hz for
400 ms
No Yes No No
14 Yodalarm Alternating 800 / 1000 250 ms for each
frequency
No Yes No No
15 Conventional
Bell (Refer to
notice below)
continuous 1450 As per Banshee
Multi-Tone (MT)
Sounder,
Tone No. 32
No Yes No Yes
Table 6: Sounder Tones

6/14 Product Information Doc. Version 2
Technical Specification FIRECLASS Fire Detection System
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 84.3 84.2 77.6 74.4 67.8 67.2
45° 82.7 82.1 76.5 75.5 66.6 65.1
75° 91.3 90.2 83.3 82.1 73.1 72.6
105° 89.1 87.7 79.8 78.7 69.0 68.2
135° 86.6 85.5 78.2 77.0 67.4 66.9
165° 88.6 87.4 80.2 79.1 69.6 69.0
Table 7: Dutch Slow Whoop Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 83.7 82.2 75.0 74.7 65.9 64.4
45° 82.3 82.1 73.8 73.2 63.5 65.4
75° 91.0 89.6 82.5 81.7 72.2 71.8
105° 87.6 86.6 78.8 78.3 68.1 67.8
135° 84.6 83.0 76.3 75.5 65.7 65.4
165° 86.9 85.5 78.4 77.6 67.9 67.6
Table 8: 7Hz Fast Sweep Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 84.3 82.6 76.4 74.8 66.0 65.4
45° 81.2 79.3 75.6 74.4 65.4 65.6
75° 90.4 89.0 83.3 81.8 73.1 72.3
105° 87.8 86.2 78.9 77.8 68.6 67.5
135° 84.8 83.4 76.7 75.7 65.8 65.6
165° 87.4 85.9 79.4 78.1 68.2 67.7
Table 9: BS 1Hz Sweep Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 83.0 81.5 74.6 73.8 63.5 63.1
45° 80.8 79.5 75.5 74.7 63.2 63.8
75° 89.4 85.5 82.0 81.5 71.9 70.8
105° 85.6 84.3 78.7 77.8 67.7 67.3
135° 85.2 83.8 77.2 77.0 66.6 66.2
165° 85.4 84.3 78.0 77.5 67.4 66.4
Table 10: 2 Tone Volume

FIRECLASS Fire Detection System Technical Specification
Product Information Doc. Version 2 7/14
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 82.9 81.5 74.2 73.8 63.5 63.4
45° 80.9 80.1 73.8 74.0 64.2 63.9
75° 89.2 87.9 81.8 81.2 71.8 71.1
105° 85.6 84.5 78.7 77.8 67.5 67.4
135° 85.1 83.4 77.5 76.5 66.5 66.0
165° 85.5 84.0 78.1 77.3 66.9 66.6
Table 11: Temporal 4 Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 82.8 81.4 75.4 74.9 65.7 64.9
45° 80.7 79.2 73.8 72.7 64.1 64.5
75° 89.6 88.3 81.8 81.0 71.9 71.1
105° 86.5 84.9 78.2 77.3 67.3 66.4
135° 83.6 82.1 76.2 75.4 66.1 65.4
165° 85.9 84.5 78.0 77.1 67.9 67.2
Table 12: Australian (AS 1670.4) (Temporal 3 Type) Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 82.1 80.2 74.4 73.8 63.6 63.3
45° 80.1 79.3 74.0 72.3 61.5 63.3
75° 88.8 87.8 82.0 81.3 71.0 70.6
105° 85.6 84.5 78.8 78.0 67.8 67.4
135° 85.5 83.8 76.8 77.1 66.9 66.5
165° 86.2 84.6 78.5 77.8 67.7 67.2
Table 13: March Time Beep Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 85.5 84.0 79.0 77.9 69.1 68.4
45° 80.4 78.7 73.7 72.0 62.6 63.0
75° 90.2 88.8 83.4 82.3 73.5 73.1
105° 83.7 83.2 77.8 76.8 67.3 67.9
135° 80.9 78.6 74.3 73.6 64.1 63.6
165° 82.0 80.6 76.0 75.0 65.8 65.6
Table 14: Continuous 970Hz Volume

8/14 Product Information Doc. Version 2
Technical Specification FIRECLASS Fire Detection System
Angle High Volume Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 82.9 81.4 76.4 75.3 66.2 65.9
45° 80.3 78.9 74.3 73.5 64.1 63.8
75° 89.6 88.2 82.4 81.3 72.1 71.8
105° 86.4 85.1 78.9 77.9 68.1 67.7
135° 83.7 82.2 76.9 75.9 66.1 65.7
165° 86.1 84.4 76.9 77.7 68.0 67.4
Table 15: DIN 1Hz Sweep Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 82.7 81.5 74.3 73.8 65.4 63.3
45° 80.1 79.5 73.6 72.4 61.9 61.6
75° 90.4 89.1 82.0 81.1 71.7 71.0
105° 87.5 86.4 79.0 78.0 69.5 67.3
135° 84.6 83.4 76.5 75.8 65.6 65.6
165° 86.5 85.5 78.6 77.7 67.7 67.1
Table 16: Banshee LF Buzzer Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 82.7 81.4 74.6 74.2 65.0 63.9
45° 81.3 79.9 75.4 75.3 62.5 62.4
75° 90.1 88.9 80.3 79.6 71.8 71.5
105° 87.2 85.9 78.8 78.8 68.6 68.2
135° 84.7 83.1 73.1 72.3 65.8 65.7
165° 86.9 85.3 76.8 76.0 67.9 67.5
Table 17: 3Hz Banshee Fast Sweep Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 82.4 81.6 74.2 73.6 65.0 64.7
45° 80.1 79.6 72.6 71.4 64.6 62.3
75° 90.1 89.2 82.0 80.8 71.4 71.3
105° 87.4 86.7 78.9 78.3 68.5 67.9
135° 84.4 83.4 76.4 75.9 66.2 65.4
165° 86.8 86.1 78.6 78.0 67.9 67.5
Table 18: 9Hz Banshee Fast Sweep Volume

FIRECLASS Fire Detection System Technical Specification
Product Information Doc. Version 2 9/14
Angle High Volume dB(A) Mid-High Volume dB(A)
40V 20V 40V 20V
15° 80.9 80.1 73.0 72.9
45° 82.1 79.6 73.4 72.7
75° 88.5 87.6 79.9 79.8
105° 85.7 84.7 76.5 76.7
135° 82.7 81.7 73.9 74.7
165° 83.7 83.0 75.3 75.4
Table 19: Alternating (NF-S 32.001) Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 83.9 82.5 79.0 77.7 68.6 68.2
45° 81.0 78.8 76.1 74.4 65.5 65.1
75° 88.5 87.0 83.0 81.8 71.9 71.8
105° 85.6 84.1 78.1 76.6 66.2 65.7
135° 84.3 82.8 77.9 76.9 66.8 66.0
165° 85.1 83.3 79.5 78.2 68.6 68.2
Table 20: Yodalarm Volume
Angle High Volume dB(A) Mid-High Volume dB(A) Mid_Low Volume dB(A)
40V 20V 40V 20V 40V 20V
15° 85.4 85.2 78.2 78.6 68.2 67.8
45° 81.0 78.5 76.5 76.7 62.5 62.0
75° 91.0 89.8 81.6 81.9 74.0 73.6
105° 84.8 84.0 74.6 75.2 66.7 68.5
135° 78.0 76.7 77.9 78.4 61.0 61.3
165° 80.7 79.0 78.8 78.3 63.3 62.8
Table 21: Conventional Bell Volume

10/14 Product Information Doc. Version 2
Technical Specification FIRECLASS Fire Detection System
Beacon Information
Category O - open class device (See Table 22 and
Fig. 4). The data applies to both the Slow Flash (1/2 Hz)
and the Fast Flash (1 Hz) while it is fitted with either a
detector or a blanking cap.
The light distribution is cylindrically symmetrical about
an axis at a right angle (Alpha of 90°) to the surface on
which the device is mounted, i.e. when the device is
mounted on a horizontal ceiling, the light distribution is
symmetrical about an axis extending vertically down-
wards through the centre of the device. The light distri-
bution in Fig. 4 represents a cross-section through the
volumetric shape using the values as indicated in
Table 22.
Alpha
[degrees]
Distance
[metres]
90 0
75 0
60 1
45 1.4
30 1.75
15 1.95
01.85
Table 22: FC430LPBSB LP Beacon-Sounder— 0.4 lm/m2
Illumination Distance
Fig. 4: FC430LPBSB LP Beacon-Sounder—Graphical Illustration of Ceiling Mount Light Distribution
0.5
011.5 2
0
90
o
o
DISTANCE [METRES]
LOCATION OF DEVICE
AXIS OFFF
SYMMETRY
ALPHA [DEGREES]
Table des matières
Autres manuels FireClass Système de sécurité
Manuels Système de sécurité populaires d'autres marques

EDM
EDM Solution 6+6 Wireless-AE Manuel utilisateur

Highway Safety Group
Highway Safety Group EA401 Manuel utilisateur

Siren
Siren LED GSM Manuel utilisateur

Detection Systems
Detection Systems 7090i Instructions de montage

Se-Kure Controls
Se-Kure Controls MicroMini SK-4841 Manuel utilisateur

Siemens
Siemens FDM273 Manuel utilisateur