Fire Control Panel –FP-C2
SYSTEM ISOLATION
Rev 1.0
fp_c2_isol_1.0.docx Page 1 of 2
Fire Control Panel for FirePro Aerosol Systems
Isolation Procedure
1. Introduction
All FirePro Fire Extinguishing Aerosol Generators use the latest generation FPC solid compound. Upon activation,
the solid compound is transformed into a rapidly expanding, highly efficient gas, based on Potassium salts. It does
not deplete oxygen levels. The FirePro Aerosol Generators have a certified life of 15 years, with minimal
maintenance required.
Ozone Depletion Potential (O.D.P.) = 0
Atmospheric Life Time (A.L.T.) = 0
Global Warming Potential (G.W.P.) = 0
Non-corrosive & Non-toxic
Self Activation Temperature
FirePro Condensed Aerosols have a built-in fail-safe activation system ensures operation of the generators when
required, even if everything else fails.
When the temperature of the Aerosol units reaches 300°C the unit will activate
DO NOT Carry out any welding or grinding work in the vicinity of the aerosol units.
Handling and Storage - Condensed Aerosol Generators do not:
•Disassemble the unit
•Carry out any welding or grinding work in
the vicinity of the fire extinguishing
system components.
•Exert force or impact which creates
physical or mechanical damage to the
casing.
STORAGE and OPERATIONAL CONDITIONS
•Temperature: –54 and +54°C
•Humidity: maximum 98% RH
•Service life: 15 years (date of manufacture appears on each generator)