5
Installation
Before installation, contact the
qualified technicians at your
local gas dealer or gas
management department to do
the installation. Any random or
improper installation will affect
the safe use of the machine or
even endanger the users’ life.
If the water heater installation is
in a room with other ventilation
devices, it is strictly prohibited
to operate additional ventilation
equipment (like a stove hood or
ventilation fan) As this can
cause a back draft of the heater.
This is why we do not
recommend this type of heater
to be installed indoors of an
occupied building or residence.
Installation requirements
Do not install the water heater
in bedroom, basement,
bathroom, kitchen or rooms
with poor ventilation. The
room for installation shall be
well ventilated and above
6m2 in area (212 Cubic Feet).
A ventilation hole as well as
an exhaust hole must be
drilled in the wall for proper
ventilation purposes. The
exhaust flue shall be installed
above the water heater, and
the ventilation hole shall be at
a level lower than the water
heater. (Fig.3)
The flame-check window of
the water heater should be at eye level (about 1.55m-1.65m above