EVAPCO Eco-Air Manuel utilisateur

EVAPCO Controller Users Manual
Bulletin 1130
For EVAPCO Authorized Parts and Service, Contact Your Local EVAPCO
Representative or the Local Mr. GoodTower®Service Provider
EVAPCO...SPECIALISTS IN HEAT TRANSFER PRODUCTS AND SERVICES.
Visit EVAPCO’s Website at: www.evapco.com
EVAPCO, Inc. — Wo ld Headqua te s & Resea ch/Development Cente
EVAPCO, Inc. • P.O. Box 1300 • Westminster, MD 21158 USA
PHONE: 10-756-2600 • FAX: 10-756-6 50 • E-MAIL: [email protected]
EVAPCO, Inc.
Wo ld Headqua te s
P.O. Box 1300
Westminster, MD 21158 USA
Phone: 10-756-2600
Fax: 10-756-6 50
E-mail: marketing@evapco.com
EVAPCO Asia/Pacific
EVAPCO Asia/Pacific Headqua te s
1159 Luoning Rd. Baoshan Industrial Zone
Shanghai 2009 9, P.R. China
Phone: (86) 21-6687-7786
Fax: (86) 21-6687-7008
E-mail:
marketing@evapcochina.com
EVAPCO Eu ope
EVAPCO Eu ope BVBA
Eu opean Headqua te s
Heersteveldweg 19
Industrieterrein Oost
3700 Tongeren, Belgium
Phone: (32) 12-395029
Fax: (32) 12-238527
E-mail:
evapco.europe@evapco.be
EVAPCO East
5151 Allendale Lane
Taneytown, MD 21787 USA
410-756-2600 p | 410-756-6450 f
EVAPCO East
Key Building
Taneytown, MD USA
410-756-2600 p
EVAPCO Midwest
Greenup, L USA
217-923-3431 p
evapcomw@evapcomw.com
EVAPCO West
Madera, CA USA
559-673-2207 p
EVAPCO Iowa
Lake View, A USA
712-657-3223 p
EVAPCO Iowa
Sales & Engineering
Medford, MN USA
507-446-8005 p
EVAPCO ewton
Newton, L USA
618-783-3433 p
evapcomw@evapcomw.com
EVAPCOLD
Greenup, L USA
217-923-3431 p
evapcomw@evapcomw.com
EVAPCO-BLCT Dry Cooling, Inc.
1011 US Highway 22 West
Bridgewater, NJ 08807 USA
Phone: 1-908-379-2665
E-mail: [email protected]
EVAPCO-BLCT Dry Cooling, Inc.
7991 Shaffer Parkway
Littleton, CO 80127 USA
Phone: 1-908-379-2665
E-mail: [email protected]
Spare Parts Phone: 908-895-3236
Spare Parts e-mail: [email protected]
EVAPCO Power México S. de R.L. de C.V.
Calle glesia No. 2, Torre E
Tizapan San Ángel, Del. Álvaro Obregón
Ciudad de México, D.F. México 01090
Phone: +52 (55) 8421-9260
e-mail: [email protected]
Refrigeration Valves & Systems Corporation
A wh lly wned subsidiary f EVAPCO, Inc.
Bryan, TX USA
979-778-0095 p
EvapTech, Inc.
A wh lly wned subsidiary f EVAPCO, Inc.
Lenexa, KS USA
913-322-5165 p
Tower Components, Inc.
A wh lly wned subsidiary f EVAPCO, Inc.
Ramseur, NC USA
336-824-2102 p
EVAPCO Alcoil, Inc.
A wh lly wned subsidiary f EVAPCO, Inc.
York, PA USA
717-347-7500 p
EVAPCO Europe, S.r.l.
Milan, taly
(39) 02-939-9041 p
EVAPCO Europe, S.r.l.
Sondrio, taly
EVAPCO Europe GmbH
Meerbusch, Germany
(49) 2159 6956 18 p
EVAPCO Air Solutions
A wh lly wned subsidiary f EVAPCO, Inc.
Aabybro, Denmark
(45) 9824 4999 p
EVAPCO Air Solutions GmbH
Garbsen, Germany
(49) 5137 93875-0 p
Evap Egypt Engineering Industries Co.
A licensed manufacturer f EVAPCO, Inc.
Nasr City, Cairo, Egypt
2 02 24022866/2 02 24044997 p
EVAPCO S.A. (Pty.) Ltd.
A licensed manufacturer f EVAPCO, Inc.
sando 1600, Republic of South Africa
(27) 11-392-6630 p
EVAPCO (Shanghai) Refrigeration
Equipment Co., Ltd.
Baoshan ndustrial Zone Shanghai, P.R. China
(86) 21-6687-7786 p
Beijing EVAPCO Refrigeration
Equipment Co., Ltd.
Huairou District Beijing, P.R. China
010-6166-7238 p
EVAPCO Australia (Pty.) Ltd.
Riverstone NSW 2765, Australia
(61) 2 9627-3322 p
EVAPCO Composites Sdn. Bhd
Rawang, Selangor, Malaysia
(60-3) 6092-2209 p
EvapTech Asia Pacific Sdn. Bhd
A wh lly wned subsidiary f EvapTech, Inc.
Puchong, Selangor, Malaysia
(60-3) 8070-7255 p
EVAPCO No th Ame ica
EVAPCO South Ame ica
EVAPCO Brasil
Equipament s Industriais Ltda.
Al. Vênus, 151 – CEP: 13347-659
ndaiatuba –São Paulo – Brasil
(55+11) 5681-2000 p
Fan Technology Resource
Cruz das Almas – ndaiatuba
São Paulo, Brasil 13308-200
55 (11) 4025-1670
fantr@fantr.com
For eco-Air™Air Cooled and Adiabatic Fluid Coolers and Condensers

2
Controller User Manual
Table of Content
ntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
EVAPCO Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
nstallation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Panel nstallation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Temperature/Pressure Sensor nstallation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Wiring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Operation and Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Screen Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Navigating the Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Modifying a Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Navigating the Scheduler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Operator nterface Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Welcome Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Standby Status Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Alarms Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Main Menu Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
On/Off Unit Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
View Setpoints Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Clock/Scheduler Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
nput/Output Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Error Log Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Board Switch Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Service Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Manufacturer Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Alarm Event Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42

3
Controller User Manual
Introduction
EVAPCO Controller
Congratulations on the purchase of your eco-Air unit with the EVAPCO Controller. The EVAPCO Controller will ensure that your
eco-Air unit is operating in the most efficient manner possible while using minimal resources. Along with proper eco-Air unit
maintenance, the EVAPCO Controller will ensure that your eco-Air unit provide years of service at peak efficiency.
The EVAPCO Controller serves as a single connection point for the eco-Air unit and contains all of the protection and logic devices
required to run the eco-Air unit in the most efficient manner possible.
n order to reduce downtime, Evapco recommends keeping a stock of spare fuses. Consult the wiring diagram for the quantity,
type, and fuse size required. Contact your local EVAPCO representative for replacement or spare parts.
This bulletin includes a description of the screens and parameters that are available through the display located on the front of the
EVAPCO Controller. Also included in this bulletin are the functions of the EVAPCO Controller. Please note that the screens
displayed on your EVAPCO Controller display may vary slightly from the images shown in this document.
Become familiar with the EVAPCO Controller by thoroughly reading and understanding the content of this bulletin. A detailed wiring
diagram can be found in the data pocket inside of the EVAPCO Controller.
f you should require any additional information about the operation or maintenance of this equipment, contact your local EVAPCO
representative. You may also visit www.evapco.com for more information.
In tallation and Wiring
Safety
Qualified personnel should use proper care, procedures, and tools when operating, maintaining, or repairing this equipment or any
other connected equipment in order to prevent personal injury and/or property damage. The warnings listed below are to be used
as guidelines only.
Warning: EVAPCO eco-Air units should never be operated without fan screens and access doors properly secured and
in place.
Warning: Avoid working on electrical circuits while they are live. Proper lock-out/tag-out and all applicable safety
practices must be followed prior to servicing any equipment.
Warning: Before opening the panel door, allow sufficient time for VFD’s to discharge after removing power. VFD’s contain
capacitive circuits which maintain a charge even after power is removed.
Warning: The three position selector switch is not intended to replace or act as a disconnect to disable the EVAPCO
eco-Air unit and/or de-energize the EVAPCO Controller. Be sure to follow lock-out/tag-out and all applicable
electrical safety practices before servicing any equipment.
Warning: Do not attempt to service or enter the eco-Air unit even if the unit status is indicated as being off. Unless power is
completely removed from the eco-Air unit, it may be possible for the eco-Air unit to start at any time without notice.
Be sure to follow lock-out/tag-out and all applicable electrical safety practices before servicing any equipment.

4
Controller User Manual
The following safety issues need to be addressed by those responsible for the installation, maintenance, and repair of the EVAPCO
Controller:
•Access to the control panel (including the disconnect switch(es)).
• Sizing and protection of electrical circuits feeding the control panel(s) and branch circuits feeding the controlled equipment.
• Proper grounding of electrical circuits.
• Qualification of persons who will install, maintain, and service the electrical equipment.
Panel In tallation Con ideration
When the EVAPCO Controller does not ship factory mounted on the eco-Air unit, the EVAPCO Controller should be placed in close
proximity to the eco-Air unit to reduce the wire lengths required. f the EVAPCO Controller is within sight of or mounted on the eco-
Air unit, the EVAPCO Controller may be used as the main electrical disconnect for the eco-Air unit. Otherwise, separate electrical
disconnects may be required. Consult applicable electrical codes to make this determination. Avoid mounting the EVAPCO
Controller with a southern exposure. This will minimize the amount of solar heat gain the system will experience and will make it
easier to view the operator interface.
Temperature/Pre ure Sen or In tallation
EVAPCO eco-Air fluid coolers are supplied with a thermowell (1/4” G threads) and a NTC temperature sensor. The thermowell and
temperature sensor should be installed in the common return pipework of the eco-Air fluid cooler unit. Thermowells must be
installed in the horizontal sections of the coil piping. A small amount of thermal paste should be added to the thermowell before the
NTC sensor is inserted to ensure a more accurate fluid temperature measurement.
Figure 1
The suggested temperature sensor location for fluid coolers. Piping shown by dashed lines provided and installed by others.
TEMPERATURE SENSOR TEMPERATURE SENSOR

EVAPCO eco-Air condensers are supplied with a pressure transducer (7/16”-20 UNF threads). The pressure transducer should be
located in the common compressor hot gas discharge pipework. t is recommended that a shut-off valve be located between the
pipework and the pressure transducer to allow the transducer to be more easily replaced should it become damaged.
When the EVAPCO Controller ships factory mounted to the eco-Air unit, the supplied temperature or pressure sensor must be
wired to the junction box location on the connection end of the eco-Air unit (Figure 3). f the EVAPCO Controller does not ship
factory mounted, the supplied temperature or pressure sensor must be wired to the EVAPCO Controller. Consult the supplied
wiring diagram for a determination if the junction box is supplied.
Each EVAPCO Controller is supplied with one ambient air sensor that is located on the bottom of the Controller enclosure. Should
the EVAPCO Controller be placed in a location where the ambient temperature (i.e. indoors) is not indicative of the ambient
temperature of the eco-Air unit, the ambient temperature sensor must be relocated to a more suitable location and the resulting
opening in the enclosure must be sealed with a Type 4 plug.
5
Controller User Manual
Figure 2
The suggested pressure sensor location for condensers. Piping shown by dashed lines provided and installed by others.
Figure 3
The junction box is highlighted and circled.
PRESSURE SENSOR PRESSURE SENSOR

6
Controller User Manual
Wiring Con ideration
Consult the supplied wiring diagram for detailed wiring information. All field wiring is indicated by dashed lines on the wiring
diagram.
All wiring in and out of the EVAPCO Controller should be with copper conductors and wire lengths must be kept as short as
possible. Consult the detailed wiring diagram for field wiring connections of each device. Applicable electrical codes for the
location should be followed during the sizing and installation of the field wiring. All fittings attached to the EVAPCO Controller
must be Type 4. All wiring must be through the bottom of the EVAPCO Controller. Top entry into the EVAPCO Controller is
not permitted. Any damage caused to any component within or connected to the EVAPCO Controller due to a top entry
connection is not warrantable!
For wiring the EVAPCO Controller to each NEMA fan motor, Belden®VFD cable 295XX (XX denotes gauge) or equivalent should
be used. The shield of the VFD cable needs to be bonded to ground at both ends of the cable.
While the EVAPCO Controller does provide provisions for connection to a BAS, this connection is not required for the EVAPCO
Controller to operate.
Operation and Servicing
On eco-Air units equipped with NEMA fan motor(s), the EVAPCO Controller contains a three position selector switch (Bypass-Off-
Auto) located behind the HM door. The operation of each position is as follows:
Auto: The Auto position allows the EVAPCO Controller to operate the eco-Air unit based on the logic programmed into the
Controller. Note that the unit must be switched on before the eco-Air unit will begin to operate. Please see the On/Off Unit
Screen section of this document for more information.
Off: n the Off position, the EVAPCO Controller will be powered; however, output commands will not be sent to any of the
attached equipment. This position is used for programming the VFD.
Bypass: n the Bypass position, the logic program is bypassed which allows the fan motor(s) to energize independent of
sensor temperature or setpoints. Power is routed around the VFD and thus the fan motor(s) will operate at full power, across-
the-line. The VFD will still be energized when the selector switch is in the Bypass position.
The door protecting the HM must be shut unless an operator is using the HM interface. This will protect the HM interface from
contamination and increase the life of the HM .
The EVAPCO Controller is supplied with air filters that must be inspected every 90 days. Depending on the installation
environment, more frequent inspection and/or replacement may be required. A dirty filter can cause the internal panel temperature
to increase and may cause component failure. Permanently removing the filter will allow dirt and particulates to enter the enclosure
and may cause premature failure.
Please consult the proper Operation and Maintenance nstructions for start-up and maintenance guides for the eco-Air unit
attached to the EVAPCO Controller.

7
Controller User Manual
ALARM button. Direct shortcut to the Alarms Screen. This button will flash red if there is an active alarm.
PRG button (Program). Direct shortcut to the Main Menu Screen.
ESC button. Leaves a menu or an entry field without changing the value.
UP button. Scrolls up in the menu or changes a value.
E T button. Goes to the selected submenu or accepts a modified value.
DOW button. Scrolls down in the menu or changes a value.
Screen Navigation
Navigating the Di play
The operator interface contains a LED display and six buttons that allow the user to navigate the various screens as well as view
and modify several setpoints that affect the operation of the eco-Air unit.
Table 1
A description of the buttons located on the operator interface.
Button Function
Figure 4
The operator interface of the EVAPCO Controller.

8
Controller User Manual
Figure 5 provides an overview of the various screens and menus of the EVAPCO Controller.
Active Alarms
Pre-Cooling Stage Rotation Screen
Flush Timer Screen
Pre-Cooling Minimum On Time Screen
Pre-Cooling Increment/Decrement Screen
Fan Motor Status Screen
Alarms Screen
Standby Screen
Standby Status Screens Main Menu Screens
A. On/Off Unit
B. View Setpoints
C. Clock/Scheduler
D. Input/Output
E. Error Log
F. Board Switch
G. Service
H. Manufacturer
Figure 5
Controller screen flowchart.
Modifying a Value
To change a parameter on a given screen, first navigate to the desired screen. n this example, the setpoint temperature will be
modified. Once at the desired screen, press the E T button.
Figure 6
The cursor next to the setpoint temperature.

9
Controller User Manual
As seen in Figure 6, the cursor (the shaded block) is next to the setpoint value. To change the value, press the UP or DOW
button. To accept the value, press the E T button.
Figure 7
The cursor moved to the next setpoint. Note that the first setpoint value has changed.
Next, press the ESC button to return to the previous menu or repeatedly press the E T button until the cursor moves to the top of
the screen.
Figure 8
The cursor is located in the top left of the screen.
Navigating the Scheduler
Several functions of the EVAPCO Controller are able to be scheduled to operate during certain periods of the year or at certain
times of the day. n this example, consider a noise restriction from 8:00pm to 5:30am starting Sunday night and ending Friday
morning. During the noise restriction hours, the fan speed will be limited to 85% via the Quiet Mode. After navigating to the proper
scheduler, the screen shown in Figure 9 will be displayed. The day of the week is indicated in the upper left corner.
Figure 9
The Scheduler Screen.

10
Controller User Manual
Each block represents a half hour period of time. First, press the E T button four times until the first block is highlighted by the
cursor. Note that this first block represents 12:00am to 12:30am.
Figure 10
The 12:00am to 12:30am block is selected.
Press the UP or DOW button to enable the Quiet Mode during the selected period of time. The selected block will become raised
indicating that the Quiet Mode will be active. Press the E T button to move to the next half hour period (12:30am to 1:00am).
Figure 11
Quiet Mode will be active from 12:00am to 12:30am.
Continue the steps above until the desired blocks are raised. As shown in Figure 12, the Quiet Mode will be active from 12:00am to
5:30 am and 8:00pm to 12:00am on Monday.
Figure 12
Quiet Mode is active from 12:00am to 5:30am and 8:00pm to 12:00am on Monday.