EngA DJM3 Instructions de montage

IOM‐17WWW.ENGINEEREDAIR.COMMAR99R3
USER OPERATION
MANUAL
FOR
DJM3
INDIRECT FIRED HEATING CONTROLLER
UNIT MODEL NO. _________________
UNIT SERIAL NO. _________________
SERVICED BY: ___________________
TEL. NO: ________________________
CANADIAN
HEAD OFFICE
AND FACTORY
USA
HEAD OFFICE
AND FACTORY
CANADIAN
EASTERN FACTORY
1401 HASTINGS CRES.
SE
CALGARY, ALBERTA
T2G 4C8
Ph: (403) 287-2590
Fax: 888-364-2727
32050 W. 83r
d
STREET
DESOTO, KANSAS
66018
Ph: (913) 583-3181
Fax: (913) 583-1406
1175 TWINNEY DRIVE
NEWMARKET,
ONTARIO
L3Y 5V7
Ph: (905) 898-1114
Fax: (905) 898-7244
SALES OFFICES ACROSS CANADA AND USA
Retain instructions with unit and maintain in a legible condition.
Please give model number and serial number when contacting
factory for information and/or parts.

A DJM3
IOM-17 2 of 27 Mar 99 R3
DJM3
TheDJM3hasbeencertifiedbyIntertek(ETL)forusewithEngineeredAirappliancesonly.Ithasbeen
evaluatedtoCSAC22.2No.24Temperature‐IndicatingandRegulatingEquipmentandUL873UL
StandardforSafetyTemperature‐IndicatingandRegulatingEquipment.ThisisaUserOperation
Manualandthereforenotsubjecttoevaluation.
IfanyerrorsoromissionsarenotedpleasecontactthenearestEngineeredAirTechnicalService
Department.
Toensurewarrantyishonored,onlyqualifiedpersonnelshouldbeemployedforserviceand
troubleshooting.IffurtherinformationisrequiredpleasecontactthenearestEngineeredAiroffice.
Therearetwosetsofelectricaldrawingsandunitfunctionsheetsprovidedwiththeappliance.Oneset
isinanenvelopewhichalsocontainstheOperation,InstallationandMaintenancemanual(s).This
packageisforcopying,thenshouldeitherbereturnedtotheapplianceorstoredinasafeplace.The
othersetisattachedtothecontrolpaneldoorandshouldneverberemoved.
Pleasereportanyomissionstothenationalservicemanager.
Warning:
Improperinstallation,adjustment,alteration,serviceormaintenancecancause
propertydamage,injuryordeath.Readtheinstallation,operatingand
maintenanceinstructionsthoroughlybeforeinstallingorservicingthisequipment.
Warning: Thisunitisconnectedtohighvoltages.Electricalshockordeathcouldoccurif
instructionsarenotfollowed.Thisequipmentcontainsmovingpartsthatcanstart
unexpectedly.Injuryordeathcouldoccurifinstructionsarenotfollowed.All
workshouldbeperformedbyaqualifiedtechnician.Alwaysdisconnectandlock
outpowerbeforeservicing.DONOTbypassanyinterlockorsafetyswitchesunder
anycircumstances.

A DJM3
IOM-17 3 of 27 Mar 99 R3

A DJM3
IOM-17 4 of 27 Mar 99 R3
TABLEOFCONTENTS
INTRODUCTION...............................................................................................................................................................5
CONTROLLERRATINGS.....................................................................................................................................................5
CONTROLLERDESCRIPTION..............................................................................................................................................6
TERMINALS..................................................................................................................................................................................6
DIPSWITCHES..............................................................................................................................................................................7
INDICATIONANDDIAGNOSTICLIGHTS........................................................................................................................................7
ADJUSTMENTPOTS......................................................................................................................................................................8
MULTIMETERTESTPOINTS..........................................................................................................................................................9
SYSTEMTIMINGS.........................................................................................................................................................................9
TEMPERATURECONTROL.................................................................................................................................................9
CALCULATEDSETPOINT(SPC)......................................................................................................................................................9
DISCHARGETEMPERATURESENSOR(DTEMP)..........................................................................................................................10
MODULATINGROOMRESET......................................................................................................................................................10
MultipleRoomSensors....................................................................................................................................................11
ROOMRESETAUTHORITYTABLE...............................................................................................................................................11
BMSRESET.................................................................................................................................................................................12
AMBIENTRESET(CONTINUOUSBLOWEROPERATIONONLY).................................................................................................................12
MAKE/BREAKRESETANDOVERRIDE...........................................................................................................................................13
“OR”and“V”Override(DayOperationonly)..................................................................................................................13
“X”and“Z”Override(DayandNightOperation).............................................................................................................13
OPERATION...................................................................................................................................................................14
DAY/NIGHTOPERATION...........................................................................................................................................................14
FANCONTROL............................................................................................................................................................................14
DAMPERCONTROL....................................................................................................................................................................14
BURNERCONTROL.....................................................................................................................................................................14
LOWLIMIT..................................................................................................................................................................................15
ResettingLowLimit..........................................................................................................................................................15
SERVICE.........................................................................................................................................................................15
SERVICEMODE...........................................................................................................................................................................15
BURNERSETUP..........................................................................................................................................................................15
TEMPERATURECONTROL..........................................................................................................................................................22
AIRBALANCING..........................................................................................................................................................................22
PRE‐PURGEPROBLEM................................................................................................................................................................22
INDUCEDVOLTAGEONREMOTECONTROLWIRING..................................................................................................................23
CALIBRATION.................................................................................................................................................................23
DISCHARGESENSOR........................................................................................................................................................................23
DISCHARGESETPOINTCALIBRATION...................................................................................................................................................23
ROOMSENSORCALIBRATION............................................................................................................................................................23
BMSSIGNALCALIBRATION...............................................................................................................................................................24
SENSORTABLE...........................................................................................................................................................................24
FANOPERATIONFLOWCHART........................................................................................................................................25
HEATOPERATIONFLOWCHART......................................................................................................................................26
UPGRADINGDJM3.2OR3.3TODJM3.4.........................................................................................................................26

A DJM3
IOM-17 5 of 27 Mar 99 R3
INTRODUCTION
TheDJM3isanindependentcontrollerforEngineeredAirDJstylegasfiredheatingequipment
designedtoprovidethemajorityofcontrolrequirements.TheDJM3modulatesavariablespeed
combustionblowerinconjunctionwithanmodulatinggasvalve.Thecombustionblowerspeedand
thegasvalveflowratearebothmodulatedtomaintaintherequireddischargeairtemperature.
Theinformationusedinthismanualshouldbeusedinconjunctionwiththeunitfunctionsheet(s)and
theDJ(E,S)&DGorDJXseriesInstallation,Operation,andMaintenancemanuals.
TheDJM3isdesignedtocontrolonlyEngineeredAirequipment.Variousupgradesandimprovements
havebeenmadeovertime.Alwaysincludeanysuffixlettersandnumbersfortroubleshootingand/or
replacement.
Note:Itisnecessarythatalloftheremotewiringandcontrolsbecompleteandoperationalbefore
startingtheappliance.
CONTROLLERRATINGS
Powerrequirements:24Vac,40VA.
ContactRating:120V5Ainductive
0‐10Vdcinputimpedance:2k
Environment:‐40to120°F(‐40to50°C)non‐condensing.
FuseRating:1.5GDCslow‐blow

A DJM3
IOM-17 6 of 27 Mar 99 R3
CONTROLLERDESCRIPTION
TERMINALS
TABLE1
Terminal Description
T1 Boardpowersupply.(HOT)24Vacisolated.
T2 Boardpowersupply.(NEUTRAL)24Vacisolated.
FS Fanswitch(orDaymode)enableinput(24Vac).
K Night(unoccupied)modeenableinput(24Vac).
HS Heatenableinput(24Vac).
N Grounded24Vacneutral(referencetoFS,K,HS).
DM1,DM2 Dampermotoroutputcontacts(dry).
FR,CFR Flamerelayoutputcontacts(dry).
AL Alarmoutput.
C Contactcommoninputpower(toALandSA).
SA Supplyairfanenableoutput.
CB1 Combustionblowermotorinput.
CB2 Combustionblowermotorspeedcontroloutput.
PV1,PV2 Pilotvalvedisablecontact(dry).
VFB120 Maingasvalvefeedback(SSOV)hotinputfor120Vvalves.
VFB24 Maingasvalvefeedback(SSOV)hotinputfor24Vvalves.
VN Maingasvalvefeedback(SSOV)neutralinput.
MX1,MX2 Modulatingvalveoutput.(DCvolts)
VS Legacyinput.Notused.
OS,GS,YS Combustionblowerspeedsensorinput.
Q,U Dischargeairtemperaturesensorinput.
SSPM Internal(jumpered)orexternaldischargesetpointinputs.
VXYZ Modulating(resistive)room/returnairthermostatinputs.
OR Singlestageheatthermostatinput.
+/‐ 0‐10Vdc(4‐20mA)temperatureresetinput.

A DJM3
IOM-17 7 of 27 Mar 99 R3
DIPSWITCHES
TheDJM3optionsareconfiguredbyDIPswitchselectionand/orwiringconnections.
TABLE2
DIPSW Description
1 EnableVdcormAtemperatureresetifON.
2 EnableambientresetifON.
3 Enableroom/returntemperatureresetifON.
4 Notused.
5 Servicemode(mustbeleftOFFfornormaloperation).
6 Notused.
7 ConstantcombustionairpurgemodeifON.
8 EnablelowlimitdischargetemperaturesensingifON
Note:TheDJM3willonlyacceptonetypetemperatureresetsignal.
INDICATIONANDDIAGNOSTICLIGHTS
Thereare4statuslightsontheDJM3labeled1to4.Theyoperatein4patterns:constanton,2second
flash(onfor1second,offfor1second),1secondflash(onfor½second,offfor½second)andan
irregularflash(flashestwice,thenoff,repeat).
TABLE3
LIGHT LEDON 2SECFLASH 1SECFLASH INTFLASH
1 LLLOCKOUT LLBYPASS DSENOPEN ‐‐‐‐‐‐‐‐‐‐
2 PREPURGE PPPROBLEM ‐‐‐‐‐‐‐‐‐‐ ‐‐‐‐‐‐‐‐‐‐
3 HEATCALL HTSWOPEN ‐‐‐‐‐‐‐‐‐‐ SERVICEMODE
4 IGNENABLE ‐‐‐‐‐‐‐‐‐‐ FLAMEFAIL ‐‐‐‐‐‐‐‐‐‐
1 ON
Theappliancehasbeenshutdownduetolowlimitfailureandlockout.
(dischargetemperaturebelow4°C(40°F))Resetwiththeserviceswitch.
Normaloperatingstatus:OFF.
1 2SEC
Unithaslowdischargetemperatureandistimingout.Ifthetemperaturedoes
notrecovertoabove4°C(40°F)itwillshutdownandlockout.
Normaloperatingstatus:OFF,orwaitingforthedischargetemperaturetorise
above4°C(40°F).
1 1SEC
Thedischargesensorcircuitisopen(sensorrangemustbebetween880and
4000Ω).
Normaloperatingstatus:OFF.
2 ON
Thecombustionblowerispurgingtheexchangerasapreliminarytoignition.
Normaloperatingstatus:EITHERONorOFF.
2 2SEC
PrePurgeproblem.TheDJM3isnotreceivingacorrectsignalfromthehall
effecttachometersensor,intoterminalsYS,OS,GS.
Normaloperatingstatus:OFF.

A DJM3
IOM-17 8 of 27 Mar 99 R3
3 ON
Thedischargesensorisbelowcalculatedsetpoint(SPC)andtheDJM3has
initiatedtheheatingsequence.
Normaloperatingstatus:ONforheating.
3 2SEC
Thereisacallforheating,howevertheheatinghasbeendisabledfromno
inputintoterminalHS(24Vac).
Normaloperatingstatus:OFF.
3 INT
FLASH
Unitisinservicemode,allowingthetechniciantomanuallysettheheating
fromlowtohighfirewiththeservicepot.
Normaloperatingstatus:OFF.
4 ON
FRandCFRcontactshaveclosed,enablingtheignitioncontroltofirethe
burner.
Normaloperatingstatus:ONforheating.
4 1SEC
Burnerignitionwasunsuccessful.TheDJM3didnotreceiveamaingasvalve
(SSOV)feedbacksignalintoterminalsVFB24orVFB120.
Normaloperatingstatus:OFF.
ADJUSTMENTPOTS
Thereareanumberofsettingandcalibrationpotentiometers(POT’s)locatedonthefrontofthe
DJM3.Modificationstotheseshouldonlybedonebyexperiencedandqualifiedpersonnel.
TABLE4
POT Description
DSENCAL Dischargesensorcalibration.
DISSPCAL Dischargesetpointcalibration.
BMSCAL BMS(0‐10Vdcor4‐20mA)resetcalibration.
ROOMCAL Roomsensorcalibration.
SERVICE Servicemodepot.
RESETRATIO Temperatureresetrangeadjustment.
LOWFIRE* LowfirespeedRPMadjustmentpot(nearterminalPV1).
CURVEMATCHING* ValvecurvematchingRPMadjustmentpot(nearterminalCS).
SETPOINT Ifused,theon‐boarddischargesetpointdial.
*Thesepotsshouldonlybeadjustedwhenusedwithacombustionanalyzer.

A DJM3
IOM-17 9 of 27 Mar 99 R3
MULTIMETERTESTPOINTS
TheDJM3hasreadoutterminalsformeasuringthedischargesensortemperatureandthecalculated
dischargesetpoint.These3testpointsarelocatedneartheMandQterminals.
MeasurementsaremadeusingaVdcmultimeterusingascaleof1Vdc=10°C.Forexample,areading
of2.1Vdc=21°C(or70°F).RefertothetablebelowforCelsiustoFahrenheitconversion.
TABLE5
VoltageReading(Vdc) °C °F
1.0 10 50
1.5 15 59
2.0 20 68
2.5 25 77
3.0 30 86
3.5 35 95
4.0 40 104
SYSTEMTIMINGS
Thetimeslistedaregeneral,andmaybeaffectedbyexternaltimedelaydevices.
TABLE6
Pre‐purge 45seconds
Postpurge 4minutes(daymode)1minute(nightmode)
Fandelay 30seconds
Warmuptime 30seconds
Cooldowntime 60seconds
Lowlimitbypass 5minutes
FlameFailure 90seconds
TEMPERATURECONTROL
CALCULATEDSETPOINT(SPC)
TheDJM3isdesignedtobeadischargeairtemperaturecontrol.Thebasedischargeairtemperature
setpointistypicallysetfromthecontrolpotlocatedonthefaceoftheDJM3.Thebasedischargeair
temperatureisnormallymodifiedfromaremotesignaltomaintainthedesiredtemperatureofthe
suppliedspace.Thisiscalledreset.TheDJM3dischargesetpointcanberesetfromavarietyofsources
suchasambientairtemperature,modulatingorstagedroomthermostats,returnairtemperature,ora
BMSsignal(0‐10Vdcor4‐20mA).
Withoutanytemperatureresetmethodthebasesetpoint(eitherfacemountedorremotemounted)is
thecalculatedsetpointthattheDJM3willattempttomaintainthedischargetemperatureat.
SetpointCalculation(SPC)=DischargeSetpoint+Reset

A DJM3
IOM-17 10 of 27 Mar 99 R3
TheDJM3isdesignedtouseeitherofthefollowingasasetpoint:
ThesetpointmountedonthefaceoftheDJM3(rangeof50‐95°F(10‐35°C)).IftheDJM3face
mountedset‐pointisused,terminals“SPandS”mustbejumpered;or
TheJohnsonControlsTE6100‐960set‐point(rangeof50‐85°F(10‐29°C)).IftheTE6100‐960isused
asaset‐point,“StoSP”isnotjumperedandtheTE6100mustbewired:
TABLE7
TE6100Wires DJM3Terminals
Violet(notused) ‐
Red(notused) ‐
Grey WiredtoterminalU
Blue WiredtoterminalM
Orange WiredtoterminalS
DISCHARGETEMPERATURESENSOR(DTEMP)
TheDJM3usesthedischargesensorforbothtemperaturecontrolandlowlimit.Becauseofthis,the
DJM3willnotoperatewithafaultydischargesensor.Ifthedischargesensorresistanceisgreaterthan
4000‐ohmsorlessthan880‐ohms,theunitwilllockouteitheronlowlimitorbadtemperaturesensor.
MODULATINGROOMRESET(continuousbloweroperationonly)
DIPswitch3mustbe"on".ThisoptionalsorequiresaTE6100wired:
TABLE8
TE6100Wires DJM3Terminals
Red(notused) ‐
GREY WiredtoterminalV
VIOLET WiredtoterminalX
ORANGE WiredtoterminalY
BLUE WiredtoterminalZ
IfDIPswitch3isonandtheTE6100isnotwiredtothecorrectDJM3terminals,theDJM3willresetthe
dischargetemperaturedownasitthinksthattheroomsensorisverywarm.Theroomtemperature
requirementscanincreaseordecrease(reset)thecalculateddischargeairset‐point.
Note:Ifroomresetcalling,the“calculated”dischargetemperaturesetpointwillvaryfromthesetting
of“master”setpoint.
Theroom‐resetfeatureisactivatedbyDIPswitch3.
RoomsensorcalibrationpotisRoomCalPot.
Roomresetbandis3°F(fixed).
The“roomresetband”meansaroomtemperatureerrorofjust3°Fwillresultinamaximumresetof
thedischargeairsetpoint.Theactualamountreset(indegrees)variesasperboththesettingofPot
ResetRatioandthedischargesetpoint.Thecalculateddischargeairsetpoint(dialsetting+reset)is
limitedbetween48and120°F.