SPEED CONTROL-12 v2a Instruction Manual
Output V2
0.0 V V2 output.
Output V3
0.0 V
Elevator
0 Allows to check the inlet flaps system “+” button opens the inlets, while “-”
button closes them. The display shows a current actuator position measured
by the potentiometer.
Stage 3
No The activation enables the Stage ventilation circuit to start (the elevator
function must be deactivated).
Stage 4
No The activation enables the Stage 4 ventilation circuit to start (the elevator
function must be deactivated).
Language English Choosing the language of the menu. Currently there are two options
available: Polish or English.
Fan Minimal spee
0 The calibration of the minimal fan speed directly attached to the controller.
The parameter determines the level of ventilation of “1%”. The positive value
of this parameter increases the fan speed, while the negative value
decreases that speed.
Min. exten
1.9 V Minimal voltage supplied to the power extending module (0-10V V1 output).
Max. exten
10.0 V Maximum voltage supplied to the power extending module (0-10V V1
output).
Cut exten
No Cutting off the power extending module. When selecting “Yes”, the (V1 0-
10V) output voltage of the control extending modules will drop to 0V and not
to to the minimal set value - when the ventilation level reaches 0%.
Inversion
No The activation triggers the inversion of the V1 output characteristics. The
voltage value will be dropping, as the ventilation level in min-max range
increases. The signal on the V1 output during the inversion is 10-0V.
Flaps Offset
0.0o C Early inlet flaps opening. The adjusted value determines the temperature
before the “Setting temp, at which the inlet flaps will open.
Closure
No The activation results in the (V2 0-10V) output voltage value of the inlet flaps
dropping to level of 0V and not to the minimal set value - in case of no
ventilation = ventilation level 0%.
Flaps min.
1.9 V Minimal voltage supplied to the inlet flaps (0-10V V2 output).
Flaps max.
10.0 V Maximum voltage supplied to the inlet flaps (0-10V V2 output).
Inversion
No The activation triggers the inversion of the V2 output characteristics. The
voltage value will be dropping, as the ventilation level in min-max range
increases. The signal on the V2 output during the inversion is 0-10V.
Measurements T Calibration S1
23.0o C -> 23.5o CThe calibration for the the analog inputs, allowing to rescale the temperature
measured from S1 and S2 sensors.
Calibration S2
23.0o C -> 23.2o C
Averaging time
60 s This parameter indicates the period, during which the temperature
measurement values are being averaged. The value of the averaged
temperature is the primary parameter of this controller function. The changes
of outputs statuses (airing, heating, inlets, ventilation stages and alarms), are
strictly connected with this parameter and cannot occur more often than
within the time adjusted in this option.
Elevator Calibration Ope
1024 -> 853 The calibration of the elevator is vital for the proper inlet flaps system work.
The “+” button opens the inlets, the “-” button closes the inlets. While
opening the inlets, the position parameter should grow and drop while
closing them – if not, verify the connection of the actuator (power supply and
the potentiometer). In “Calibration Ope” the inlets should be opened to the
maximum and then the parameter should be confirmed by pressing the “OK”
button. In “Calibration Clo” the inlets should be closed and then the
Calibration Clo
0 -> 324