Operation of DO6:
de ice without special option (see ordering option 2):
DO6 has de ice ready function
de ice with special option 6 (see ordering option 2):
ack. lamp(2)
DO6
(1) depends on de ice setting (see chapter „SETTINGS“)
(2) button »ACK LAMP« pressed or input »DIB« acti ated
(3) button »ACK HORN« pressed or input »DIC« acti ated
When any binary input is acti ated, belonging lamp is also acti ated. Lamp flashing mode
depends on de ice setting (see chapter „SETTINGS“):
A) when input is acti ated, lamp lights. When input is deacti ated, lamp lights no more, without
any acknowledgement. No DOs are acti ated.
B) (1. example) when input is acti ated, lamp start to flash. When input is deacti ated, lamp
flashes until lamps are acknowledged (button »ACK LAMP« pressed or input »DIB« acti ated).
(2. example) when input is acti ated, lamp start to flash. When lamps are acknowledged (button
»ACK LAMP« pressed or input »DIB« acti ated) lamp lights until binary input is deacti ated.
DO2 normal position is OFF. At acti ation of any binary input set at B mode, binary output DO2
starts to alternate from OFF to ON position and ice ersa. Alternation time depends on lamps
flashing time setting. When lamps are acknowledged (button »ACK LAMP« pressed or input
»DIB« acti ated), DO2 goes to OFF position no matter of binary input states.
DO3 normal postion is OFF. At acti ation of any binary input set at B mode, binary output DO3
goes to ON position for 500 ms.
DO4 normal position is OFF. At acti ation of any binary input set at B mode, binary output DO4
goes to ON position. It stays in that position until horn is acknowledged (button »ACK HORN«
pressed or input »DIC« acti ated).
DO5 normal postion is OFF. At acti ation of any binary input set at B mode, binary output DO5
goes to ON position for 500 ms.
3.3 OPERATION DURING TEST
test
DO1
DO2
DO3
DO4
DO5
DO6
When test is acti ated (button »TEST« pressed or inputs »DIA« acti ated) all lamps lights.
Binary outputs »DO1« to »DO5« are also acti ated.
When test is deacti ated (button »TEST« not released and inputs »DIA« deacti ated) all lamps
start to flash as they were triggered by binary input in normal operation. DOs are set to the
position as they were triggered by binary input in normal operation.
Device: Document: Code: Date: Page:
LSU 110 / 32 User manual LS3MUE01 15.08.2020 7