GVL 8304-K GVL 8304-K
99.824.65 1.5/03/1699.824.65 1.5/03/16
2/8 3/8
English
English
Technical data
Type : GVL 8304-K
Nominal voltage : 115 V AC ± 10%, 60 Hz
Rated power : 120 VA
Stand-by operating : 4.3 W
Class of rating : short-time duty, 20%
Protection class : II
Ingress protection : IP 50
Temperature range : -5...+40°C (23...104°F)
Output voltage : 24 V DC / unstabilized
Safe output:
Running current of drives : 3.2 A
Rated current of drives : 4 A
Housing : plastic, grey
Dimensions WxHxD : 6.8'' x 5.9'' x 3.7''
Intended use
- ventilation control for small sized building objects
- for triggering of 24 VDC drives
- 1 ventilation group
- 4 A total actuating current - unstabilized
- Only for indoor mounting
Performance features
- Ventilation safety function (key operation
OPEN/CLOSE), can be free encoded
- Entry for external control, e.g. timer
- Possibility of connecting rain detector or wind/ rain
detector without supplementary module
- Plastic housing, surface mounted type
Safety notes:
When installing the Ventilation Control Panel (VCP-C 8304), basic safety precautions should
always be followed to reduce risk of fire, electric shock, and personal injury.
Failure to follow these instructions could result in death or serious injury.
Operating voltage 115 VAC!
Connection has to be carried out only by an authorized electrical specialist.
Mounting of the control panel should be carried out by a D+H distributor, whose qualification and
experience is ensured by regular in-house training.
All wiring must be installed by a qualified electrican according to e.g. National Electrical Codes,
NFPA 70 and local codes.
For continued protection against fire, replace only with the same type and rating of fuse.
Only for indoor mounting.
Just use unchanged original D+H parts
For North America:
The International Building Codes have to be observed
View motherboard
fuse drive group DIP-switch S1
fuse mains
group
window drives*
vent button* room temp. control* Control panel (GVL 8304-K) rain sensor*
external control*
Example for Application
* optional function extension
(separate components, retrofitable!)
This instruction includes descriptions and
connection plans of components which are not part
of scope of supply of control panel. You can order
these parts and many more separately from your
D+H distributor. Further connecting plans are
available there as well.
WARNING
For continued protection against fire,
replace only with the
same type and rating of fuse.
WARNING
For continued protection against fire,
replace only with the same type and rating of fuse.
WARNING
30 - 12 AWG
max. 5 lb-in
mains connector
22 - 14 AWG
max. 7 lb-in
group connector
28 - 14 AWG
max. 4.5 lb-in