DFC-304R3 Rev 2.1 Installation Guide.doc
Page 7 of 8
Network
(NET1) MS/TP (RS485)
Communication
Status Indicators
The green LED flashes to indicate when the device is transmitting
out the port, and the red LED flashes to indicate when the device
is receiving data through the port.
Network
(NET2) MS/TP (RS485)
Communication
Status Indicators
The green LED flashes to indicate when the device is transmitting
out the port, and the red LED flashes to indicate when the device
is receiving data through the port. If communication is good, both
LEDs will flash at a high rate.
MS/TP Error MS/TP (RS485)
Network Error
Indicator
This red LED flashes to indicate a communication error or wiring
mistake on the RS-485 network.
Product Specifications
To add additional specifications put the cursor on the outside right of the table and click enter to add a row.
Power Requirements 240 VAC 50/60Hz
2000 VA maximum
Class 1
18 AWG to 12 AWG copper wire non-removable terminal blocks
(90°C minimum rated wire or equivalent to be used)
Power Consumption 24 VAC, 50/60Hz
3.0 VA maximum for BACstat
5VA maximum per pair of triac outputs
Class 2, SELV
Ambient Ratings Temperature: 32º to 113º F (0º to 45º C)
Humidity: 10 to 90% RH (non-condensing)
Altitude: under 6500 ft. (2000 m.)
Installation Category: II
Pollution Degree: 2
Communication Ports
NET1
Main LAN BACnet MS/TP (RS-485)
Communication: 9600, 19200, 38400, 76800 bps (default)
Maximum of 99 devices (50 without a repeater)
NET2
SubLAN
LINKnet
Communication: 76800 bps
Maximum 4 devices on LINKnet, with no more than 2
DFM/DNT devices per controller.
Note: Onboard transformer only provides enough power for
1 BACstat.
Inputs 1 10 KΩThermistor Dry Contact Input
2 Universal Inputs (10 bit), jumper configurable for the following input
types:
0-5 VDC
0-10 VDC
10 KΩThermistor
Dry Contact (using 10 KΩThermistor jumper setting
4-20 mA