PAGE 10 41070-0299<90-00125>
♦Route the wiring through the large hole in the top of the dis-
play box.
♦If you are using a 46029 CPM, install the relay jumper, on the
CPMs main board, in the IN position.
4. Wire the cathode sides of the MAJ diodes.
♦Jumper the cathode side (the side of the diodes without num-
bers beside them) of the MAJ diodes together.
♦Wire one of the cathodes to pin K3A.
5. Wire the cathode sides of the MIN diodes.
The cathodes of the MIN diodes (the side without numbers beside
them) can be wired to one of two relays.
♦Jumper required cathodes together and wire one of the cathodes
to pin K2A.
♦Jumper required cathodes together and wire one of the cathodes
to pin K1A.
6. Wire relay pins to the battery.
♦Wire relay pins K1B, K2B, and K3B to the battery (-48V) pin.
Terminals K1C, K2C, and K3C are used when additional resis-
tance is required in the operating path of the relays.
7. Connect power.
Connect the power source (power off) to the display box:
♦Battery to the -48V pin through a one ampere fuse and ground
to the +48V pin.
8. Wire the relay outputs, if needed.
Each of the three relays in the display box has a set of contacts for
remote sending of the alarm inputs.
♦Wire the K1 - K3 outputs, if needed.
There are two pins labeled 500 ohms that are across a 500-ohm
resistor to provide optional strapping to limit the current of one of
the relay outputs, if required.
♦Wire the resistor, if needed, in series with the relay output.
9. Mount the display box.
♦Mount the display box before reinstalling the cover. Use the
four mounting holes on the back or the four holes on the left
side of the box. Use #6 mounting hardware (not supplied).
♦Replace the cover on the display box.
10. Mount the switch box.
INSTALLATION
NOTE:
The unit operates at -48 VDC.
For -24 VDC operation, contact
Dantels Field Service Depart-
ment.
CONTINUED . . .