Consilium Salwico CS3000 Manuel utilisateur

Fire Alarm System
Salwico CS3000
Service manual
Ver. 6
çConsilium

The contents of this document are subject to revision without notice due to continued progress in
methodology, design and manufacturing. Consilium assumes no legal responsibility for any error
or damage resulting from the usage of this document.
Edition 5, 09 1 E, August 2009.
Document no. S-4-007.875
Part no: 070073
© 2004-2009, Consilium Fire & Gas AB
Consilium Marine AB
P.O. Box 8763
SE-402 76 GÖTEBORG
SWEDEN
Tel: +46-31-710 77 00, Fax: +46-31-710 78 00
Internet: www.consilium.se

Service Manual CS3000 Contents i
Document no.: S-4-007.875/E
Prepared: 1995-03-17 Fia
Revision: R4 2004-03-15 BM
© 1995, Consilium Marine AB
Contents
About this manual..................................................................................................... ii
Chapter 1: Control unit
Service mode............................................................................. 1-1
Set address........................................................................ 1-1
Bypass built-in short circuit isolators................................... 1-1
Chapter 2: The circuit board of the control unit
Input/Output board IKK-4................................................. 2-1
Chapter 3: The circuit boards of the central unit
Loop processor board SPK-2 ............................................... 3-01
Alarm processor board LPK-2.............................................. 3-09
Relay board ARK-2.................................................................. 3-13
Input board INK-2..................................................................... 3-18
Output board UTK-2................................................................ 3-22
Interface board GSK-2.............................................................3-26
Interface board RS232K-2..................................................... 3-30
Interface board KPK-2............................................................ 3-34
Rack CSR-3200........................................................................ 3-38
Power unit CSS-3300 ............................................................. 3-40
Appendix A. DIP switch settings............................................................... A-1
Appendix B. Fault codes CS3000 version 4...................................... B-1
Appendix C. Fault codes CS3000 version 6..................................... C-1

Service Manual CS3000 Contents ii
Document no.: S-4-007.875/E
Prepared: 1995-03-17 Fia
Revision: R4 2004-03-15 BM
© 1995, Consilium Marine AB
About this manual
This manual is intended to be used by personnel who maintain and perform
service on the CS3000 system.
Chapter Control Unit gives a general description on how the Control unit
works.
Chapter The Circuit Board of the Control Unit describes the functions of the
Control unit’s circuit board.
For information regarding the Central unit’s various circuit boards refer to The
Circuit Boards of the Central Unit chapter.
DIP switch settings for all different parts of the CS3000 system are listed in
the DIP Switch Settings appendix.
The fault codes for CS3000 version 4 and 6 are listed in the Fault Codes
CS3000 Version 4 and Fault Codes CS3000 Version 6 appendixes
respectively.
For a more detailed description of the system refer to the CS3000 Reference
Manual.

Service Manual CS3000 Chapter 1: Service mode 1-1
Control unit
Document no.: S-4-007.875/E
Prepared: 1995-03-17 Fia
Revision: R4 2004-03-15 BM
© 1995, Consilium Marine AB
Chapter 1: Control unit
Service mode
The control unit includes a fourth access level to be used only by the service
engineer. There are two functions in the service mode: bypass the built-in short
circuit isolators and definition of control unit address.
Set address
(Access level 4)
Each control unit in the system must have a unique address in the interval 217
- 232. The control unit number must correspond with the number defined in
the Definition program. The control unit address must be set after the system
definition is downloaded and the system is restarted.
•Press F4 (MENU) until SERVICE is displayed on line 4.
•Press F1 (SERVICE).
•Press F1 (ADDRESS).
•Enter the address for the control unit. The address interval is 217 - 232.
Bypass built-in short circuit isolators
The built-in short circuit isolators, two on each loop, are bypassed when you
activate the SERVICE function. The short circuit isolators remain bypassed
until you activate them again.
•Press F4 (MENU) until SERVICE is displayed on line 4.
•Press F1 (SERVICE).

Service Manual CS3000 Chapter 2: Input/Output board IKK-4 2-1
The circuit board of the control unit
Document no.: S-4-007.875/E
Prepared: 1995-03-17 Fia
Revision: R4 2004-03-15 BM
© 1995, Consilium Marine AB
Chapter 2: The circuit board of the control unit
Input/Output board IKK-4
General
The Input/output board (IKK-4) interfaces the control unit processor board to
the system loop. The IKK-4 board also includes circuits for transient
suppression of all external signals. The IKK-4 board is controlled by the
control unit board, via the address and data busses.
Handling
Fuses
Fuse Fuse rating Fault code
F1: Control unit panel 500 mAT 5x20 mm Not supervised
F2: Main fuse 100 mAT 5x20 mm Not supervised
F3: Main fuse for F4-F5 500 mAT 5x20 mm Not supervised
F4: Power supply ext. device 315 mAT 5x20 mm Not supervised
F5: Power supply 315 mAT 5x20 mm Not supervised

Service Manual CS3000 Chapter 2: Input/Output board IKK-4 2-2
The circuit board of the control unit
Document no.: S-4-007.875/E
Prepared: 1995-03-17 Fia
Revision: R4 2004-03-15 BM
© 1995, Consilium Marine AB
Function
Block diagram

Service Manual CS3000 Chapter 2: Input/Output board IKK-4 2-3
The circuit board of the control unit
Document no.: S-4-007.875/E
Prepared: 1995-03-17 Fia
Revision: R4 2004-03-15 BM
© 1995, Consilium Marine AB
1. Data buffer
The data bus is buffered before entering/leaving the board.
2. Address decoder
The address decoder selects the different blocks. The address decoder is
controlled by the control unit board.
3. Regulator
The regulator converts power voltage to 5 VDC.
4. Expansion
Future expansion possibilities. Not used.
5. Board ID
The control unit board reads the IKK-4 ID.
6. Inputs
Reads all external inputs.
7. Outputs
Controls the four transistor outputs.
8. Buzzer
An external buzzer may be connected via a transient protected output. The
buzzer will be parallel connected to the fire alarm and the fault buzzer on the
control unit board.
9. Barrier
The RS 232 communication is protected against transients before entering the
control unit board.
10. System loop barrier
Transient barrier for the system loop.
11. Barrier
The power supply voltage output is protected against external transients.
12. Power supply output
A fused and fault supervised output for power supply to an external device.
13. Opto-isolated inputs
Four opto-isolated transient protected external inputs.
14. Opto-isolated outputs
Four transistor outputs. Deactivated at hang-ups in the programme execution.

Service Manual CS3000 Chapter 2: Input/Output board IKK-4 2-4
The circuit board of the control unit
Document no.: S-4-007.875/E
Prepared: 1995-03-17 Fia
Revision: R4 2004-03-15 BM
© 1995, Consilium Marine AB
Technical data
Board size: 145 x 107 mm
Ambient temperature: -10°C - +70°C.
Ambient humidity: 96% Rh.
Input power: Uin : 24 VDC (-20% - + 25%).
Current consumption: Iin nom: 15 mA
I
in max: 40 mA.
Outputs: 4 opto-isolated sourcing outputs
Inputs: 4 opto- isolated inputs, active high

Service manual CS3000 Chapter 3: Loop processor board SPK-2 3-1
The circuit boards of the central unit
Document no.: S-4-007.875/E
Prepared: 1995-03-17 Fia
Revision: R4 2004-03-15 BM
© 2002, Consilium Marine AB
Chapter 3: The circuit boards of the central unit
Loop processor board SPK-2
The loop processor boad SPK-2 exists in three different models. Model 1 and
model 2 differs only in the exterior of the front panel, whereas Model 3 has an own
block diagram.
General
The loop processor board SPK-2 controls and supervises two detector loops with
analogue and addressable detectors. The detectors are constantly polled in order to
detect faults or changes in alarm status. Detector-initiated alarms are also
recognised and verified. The events are reported to the LPK-2 and proper hardware
signals are then activated.
Handling
Indications
Model 1 There are nine LEDs on the front panel of the board.
No 1 (green) when lit:proper voltage supply.
No 2 (yellow) when lit:fault in loop #1.
No 3 (red) when lit:fire alarm in loop #1.
No 4 (yellow) when lit:fault in loop #2.
No 5 (red) when lit:fire alarm in loop #2.
No 6 (yellow) when lit:local processor failure
No 7 (in service mode) will flash synchronously with the central unit’s
communication with the loop-PCB.
No 8, 9 (in service mode) will flash synchronously with polling of the
loop-units
Model 2 & 3 There are eight LEDs on the front panel of the board.
No 1 (green) when lit:proper voltage supply.
No 2 (yellow) when lit:local processor failure.
No 3, 4 (green) (in service mode) will flash synchronously with polling of the
loop-units
No 5 (yellow) when lit:fault in loop #1.
No 6 (red) when lit:fire alarm in loop #1.
No 7 (yellow) when lit:fault in loop #2.
No 8 (red) when lit:fire alarm in loop #2.
Autres manuels pour Salwico CS3000
2
Table des matières
Autres manuels Consilium Système de sécurité
Manuels Système de sécurité populaires d'autres marques

EDM
EDM Solution 6+6 Wireless-AE Manuel utilisateur

Highway Safety Group
Highway Safety Group EA401 Manuel utilisateur

Siren
Siren LED GSM Manuel utilisateur

Detection Systems
Detection Systems 7090i Instructions de montage

Se-Kure Controls
Se-Kure Controls MicroMini SK-4841 Manuel utilisateur

Siemens
Siemens FDM273 Manuel utilisateur