In Row Installation Manual
- 9 -
3.2 Electrical Connection
All models are fitted with one (two when ATS is provided), 3-pole
mains isolators, neutral and earth terminal, which are located in the
electrical power panel.
The isolators and terminals will accept cables up to #2 AWG (35
mm²). The power cables should be sized in accordance with local
and national codes. Refer to the "Electrical Data" section in the
Technical Data Manual for current requirements.
The disconnect switch on the front of the unit is mechanically
connected to power source disconnect switch. Opening the
disconnect switch will turn off both the sources of power to the unit.
3.3 Interconnecting Wiring
All the units internal wiring are completed and tested prior to delivery.
A numbered terminal block for field installed control wiring is
provided at the upper area of the power panel.
The numbered terminal block will accept control wiring up to #12
AWG (4 mm²). The terminal assignment is listed as follows:
Terminal Function Requirement
11-12 Standby enable Normally open output
13-14 Common alarm (General) Normally open output
21-22 Common alarm (Critical) Normally open output
15-16 Remote on / off Normally open dry contact input
17-18 Standby start Normally open dry contact input
19-20 Fire alarm Normally closed dry contact input
23 thru 28 Condenser/Pump interlock Normally open dry contact output
31-32 Compressor disable (optional) Normally open dry contact input
35-36 Remote on/off Interrupt (optional) Normally open dry contact input
37-38 Unit Status (optional) Normally open dry contact output
39- 42 Custom Fault1/2 (optional) Normally open dry contact input
43- 44 Liquid High Limit (optional) Normally open dry contact input
49- 50 Hum/ Reheat disable (optional) Normally open dry contact input
57- 58 Damper Motor Interlock (optional)Normally open dry contact output
59- 60 Damper End Switch (optional) Normally open dry contact input