
Number of channels: 1
Supply voltage: 20~35V DC
Current consumption: 65mA (at 24Vdc supply,20mA output)
Safe-area output:
Current: 0/4~20mA, HART digital signal
Load resistance: RL≤550Ω
Load resistance: RL≥250Ω(HART)
Voltage: 0/1~5V
Load resistance: RL≥330kΩ
Note: Users can specify current or voltage output when ordering.
Hazardous-area input:
Current: 0/4~20mA, HART digital signal
Available voltage: Open circuit voltage: ≤28V
Voltage: ≥15.5V at 20mA
Normal working current: ≤25mA
each 90 of final value in 2ms
Power supply protection: Protect the barrier form reverse supply voltage
destroy
Electromagnetic compatibility: According to IEC 61326-1(GB/T 18268),
IEC 61326-3-1
Dielectric strength:
Between non-intrinsically safe part and intrinsically safe part≥2500VAC
Between power supply part and non-intrinsically safe part≥500VAC
Insulation resistance:
Between non-intrinsically safe part and intrinsically safe part≥100MΩ
Between power supply part and non-intrinsically safe part≥100MΩ
Weight: Approx.110g
Suitable location: Mounting in non-hazardous area, and connected to
the IS apparatus in zone 0 hazardous area.
Suitable IS apparatus:
2-wire HART transmitter,3-wire transmitter, current source
≤
Transfer accuracy: 0.1%F.S.
Temperature drift: 0.005%F.S./℃
Response time: R %
DNV11 ATEX 08691X
II(1)G[Ex ia Ga]ⅡC -20℃≤Ta≤+60℃
Functional safety(SIL): SIL3 Conform to the IEC61508
National Supervision and Inspection Center for Explosion Protection
and Safety of Instrumentation(NEPSI)
Compliancy with standard: IEC60079-0(EN60079-0)
IEC60079-11(EN60079-11)
IEC60079-26(EN60079-26)
Ex-marking: [Ex ia Ga] ⅡC
maximum voltage: Um=250V
Intrinsic safety parameter:(7,8,9,10terminals)
Uo=28V, Io=93mA, Po=651mW
ⅡC:Co=0.083μF , Lo=4.2mH
ⅡB:Co=0.65μF , Lo=12.6mH
ⅡA:Co=2.15μF , Lo=33.6mH
9,10 terminals:
Uo=1.2V, Ui=20V , Ii=120mA
(1) For distributed inductance and capacitance e.g. as in a cable, allow
the values of capacitance and inductance;
(2) For circuits containing up to 1 % inductance or up to 1%
capacitance with a cable, allow the values of capacitance and inductance;
(3) For connection of the combined inductance and capacitance where
both are greater than 1% of the allowed value (excluding the cable), allow
up to 50% each of the values of capacitance and inductance.
Largest external capacitance (Co) and inductance (Lo) numerical
attention when using the following requirements:
Application
Dimensions
118.9mm×106.0mm×12.5mm
Safety related application(SIL3)-
1.These models have been assessed for using in IEC61508
functional safety applications.
2.Failure rates and safety-related parameters refer to the certificate.
Note: 1. It is not allowed to use HHC (HART hand-held communicator) in
hazardous area and safe area at the same time.
2.
must have an EX certification.
HHC (HART hand-held communicator) used in hazardous area
SIL 3
IEC 61508
1 2 3
Safe-area
Hazardous-area
Summarize Operation Conditions
Specification
Intrinsic safety description
2-wire HART transmitter, 3-wire transmitter, current source input
isolated barrier, provide isolated dc supplies for transmitters which
located in hazardous area. Transfer 4~20mA signal(or current source
signal) which generated by the transmitter form hazardous area to safe
area separately, also allows bi–directional transmission of HART
communication signals. The product needs an independent power supply.
Input circuit,output circuit and power supply are each galvanically isolated.
(1). The air should not contain any medium corrupting the coat of
chrome,nickel and silver.Moreover,violent quiver and impact or any cause
of electromagnetic induction (such as big current or spark,etc.)must be
avoided when using.
(2). Operating temperature: -20℃~+60℃
(3). Storage temperature: -40℃~+80℃
(4). Relative humidity: 10%~90%
Intrinsic safety explosion protection loop system
Special requirements have to be confirmed before using the intrinsically
safe explosion loop system(intrinsically circuit) which connected by isolated
barrier and intrinsically safe apparatus in field:
(1) The explosion level of intrinsically safe apparatus should meet the
requirements of operation conditions. The apparatus should pass the
explosion protection test and get the certificate by state-authorized
explosion-proof product certification bodies.
(2) The intrinsic safety parameters of isolated barrier and intrinsically
safe apparatus both are sure, and comply with 12.2.5 of GB 3836.15-2000.
(3)If any parameters are unclear, the system has to be confirmed by
state-authorized explosion-proof product certification bodies.
0575
IN OUT
7 (+)
8 (-)
2(-)
1(+)
9 (+)
10(-)
6(-)
5(+)
-+
-
+
9
10
8/9
10
S
7
+
-
-
+
HHC
Current
source
GS8547-EX
3-wire
transmitter
2-wire
transmitter
Power supply
Power supply
HHC