Brink ELAN 25 Manuel utilisateur

Installation instruction
Elan 25

STORE NEAR THE APPLIANCE
Country : UK
Installation instructions
Indirectly red air heater
Elan 25

Elan 25 1th edition May 2006
Tabel of contents
Chapter Page
Application
Standard version
1
1.1
1
1
Version
Upow and downow versions
Technical information
2
2.1
2.2
2
2
3
Design
Exploded view appliance
Function components
3
3.1
3.2
4
4
5
Operation
Outline description
LED indication system and operating panel
Ventilation switch
Cooling
4
4.1
4.2
4.3
4.4
6
6
6
8
8
Installation
Installation general
Placing the appliance
Free space around appliance
Regulations
Hot water connections
Right-handed and left-handed versions
Location heat recovery on Elan 25 Downow
Assembly
Connecting ducts
Overview connection options Elan 25 Downow R+L
Overview connection options Elan 25 Upow R+L
Condensate discharge
Electric connections
Connecting the power mains
Connecting cooling
Connecting the ventilation switch
5
5.1
5.1.1
5.1.2
5.1.3
5.1.4
5.1.5
5.1.6
5.2.1
5.2.2
5.2.3
5.2.4
5.3
5.4
5.4.1
5.4.2
5.4.3
9
9
9
9
9
9
9
10
11
11
12
13
14
14
14
15
15
Putting into operation
Switching the appliance on and off
Setting the output temperature
Setting the air quantity
Adjusting the air quantity at the grates
Other settings
Menu structure display
6
6.1
6.2
6.3
6.4
6.5
6.6
16
16
16
17
18
18
19
LED display system
General explanation display
Readout normal operation
Fault messages
7
7.1
7.2
7.3
21
21
22
23
Trouble shooting
Trouble shooting
Block diagram control and safety
8
8.1
8.2
25
25
26
Maintenance
User maintenance
Installer maintenance
9
9.1
9.2
27
27
28

Elan 25 1th edition May 2006
Tabel of contents
Electric diagrams
Wiring diagram
Connecting diagram
Connecting the ventilation switch
Connecting cooling
Fire safety
10
10.1
10.2
10.3
10.4
10.5
29
29
30
31
32
33
Service
Exploded view Elan 25 Upow
Exploded view Elan 25 Downow
Service kits
11
11.1
11.2
11.3
34
35
36
37
Chapter Page

Elan 25 1th edition May 2006

Elan 25 1th edition May 2006 1
Application Chapter 1
An appliance from the Elan 25 series is an indirectly red air
heater suitable for installations where a hot water supply is
available.
The appliance is also suitable for district heating.
The electric power consumption is reduced strongly because a
direct current fan is used. This fan has a high electric efciency
under all conditions of use.
It is possible to combine the Elan 25 Downow air heater with
the heat recovery unit Renovent HR.
The air quantity is automatically adapted to the outlet tempera-
ture of the appliance. All this results in very stable room tem-
perature, realising a perfect interior climate.
The appliance is available in a left-handed and a right-handed
version.
A right-handed version has the lter door on the right.
The appliance comes as standard with frost safety. This provi-
sion ensures that the heat exchanger cannot freeze.
When the temperature downstream of the heat exchanger
drops below 10 ºC, a switch ontact on the control unit is closed
(see section 10.2). That can for instance be used to switch on a
central heating pump to make (hot) water ow through the heat
exchanger. If the temperature should still drop below 5 ºC, the
system fan will be switched off.
The system fan will start running again if the temperature above
the heat exchanger becomes higher than 30 ºC.
The appliance comes ready to plug in. When it is placed, the
appliance must be connected to the system air channels, the
condensate discharge (applicable if a Renovent is mounted)
and the mains power.
It is possible to connect a ventilation switch.
This switch can be used to set the appliance in three different
modes, see section 4.3 and section 10.3.
1.1 Standard version

2 Elan 25 1th edition May 2006
The Elan 25 is available in a version with bottom output (Down-
ow) and in a version with top output (Upow)
2.1 Upow and downow versions
1 = Hot air
2 = Return air
Chapter 2 Version
5241-0
Figure 1: Basic diagram Elan 25
5562-0
Downow Upow

Elan 25 1th edition May 2006 3
Water ow [ºC]
Air input temperature [ºC]
Nominal Maximum
+16 +18 +20 +22 +16 +18 +20 +22
90/70 1,58 1,53 1,47 1,42 1,59 1,54 1,48 1,42
90/50 1,26 1,20 1,14 1,08 1,25 1,19 1,13 1,07
70/50 1,05 1,00 0,95 0,89 1,06 1,00 0,94 0,89
50/35 0,61 0,55 0,50 0,44 0,60 0,55 0,49 0,44
An air heater type Elan 25 is supplied for an installation were
hot water supply is available.
The appliance comes with the CE mark and complies with
the machine directive 89/392/EEC, the low-voltage directive.
73/23/EEC and the EMC directive 89/336/EEC.
2.2 Technical information
Nominal Maximum
Air displacement [m3/h] 1800 2200
Heating capacity [kW] 21,9 25,4
Water capacity [l/h] 956 1108
Waterside resistance [kPa] 2,24 2,94
Rated power fan [W] 315 460
Water ow [ºC] 70/50
Air input temperature [ºC] 18
Supply voltage [V~/Hz] 230/50
Maximum operating pressure exchanger [bar] 16
Water capacity exchanger [l] 3,26
Protection degree IP30
Water connection (female thread) [”] 1
Weight [ kg] 62
Correction factor heating capacity Elan 25 at other water and air input temperatures
Version Chapter 2

4 Elan 25 1th edition May 2006
5577-0
Figure 3: Location components Elan 25 R Upow
Chapter 3 Design
3.1 Exploded view appliance
Figure 2: Location components Elan 25 R Downow
5200-D
1 = Feedthrough condensate discharge heat recovery (if applicable)
2 = Feedthrough power cable 230 V
3 = Switchbox with control unit
4 = Operating panel
5 = Water connection (Return)
6 = Return temperature sensor
7 = Water connection (Supply)
8 = Filter door
9 = System fan
10 = Filter
11 = Heat exchanger
12 = System temperature sensor

Elan 25 1th edition May 2006 5
3.2 Function components
Design Chapter 3
1 Feedthrough condensate discharge Feedthrough condensate discharge if a heat recovery appliance is placed on the Elan
2 Feedthrough power cable Feedthrough 3-core power cable 230 V
3 Switchbox) Box with electronic components for various controls and monitoring for safe operation
of the appliance. It also contains the 20-pole connector for specic applications
4 Operating panel The operating panel has a display for indicating several operational situations, a reset
button for unlocking faults and keys for program settings
5 Water connection (Return) Connecting the water return
6 Return temperature sensor Sensor that measures the return air and, after switching on the frost safety, releases
the control again
7 Water connection (Supply) Connecting the water supply
8 Filter door Opening it gives access to the lter
9 System fan Arranges transport of air to the relevant rooms and sucks in the return air
10 Filter Filters dust particles from the air and protects the system fan from fouling
11 Heat exchanger This is where heat is exchanged to the air to be heated
12 System temperature sensor Sensor that controls the system fan rpm and, if necessary, activates the frost safety
Table des matières
Autres manuels Brink Chauffage
Manuels Chauffage populaires d'autres marques

oventrop
oventrop Regucor Series Manuel utilisateur

Blaze King
Blaze King CLARITY CL2118.IPI.1 Manuel utilisateur

ELMEKO
ELMEKO ML 150 Manuel utilisateur

BN Thermic
BN Thermic 830T Manuel utilisateur

KING
KING K Series Mode d’emploi

Empire Comfort Systems
Empire Comfort Systems RH-50-5 Guide de démarrage rapide

Empire Heating Systems
Empire Heating Systems WCC65 Manuel utilisateur

Wetekom
Wetekom 92 86 43 Manuel utilisateur

Desa
Desa SPC170-F Manuel utilisateur

Watlow
Watlow Watrod Electric Tubular Heaters Manuel utilisateur

Haverland
Haverland ECO-DRY GPS Series Manuel de la liste des pièces

Stelpro
Stelpro ASILVC2060 Series Manuel utilisateur