How to connect the (TM-48VA) 48 volt adapter and lightning protector to the TriMetric battery monitor. BOGART ENGINEERING 1/16/03How to connect the (TM-48VA) 48 volt adapter and lightning protector to the TriMetric battery monitor. BOGART ENGINEERING 1/16/03
Loosen the 5 screws on TriMetric terminal block and
remove wire jumper (if present) between + and M+.
Place the adaper so the 5 wires extending from the
adapter poke into the TriMetric terminal block as shown.
Tighten securely all 5 screws. For the adapter to fit in
some boxes it may be necessary to pull this end up away
slightly from front panel so adapter will fit in box.
Loosen the 5 screws on TriMetric terminal block and
remove wire jumper (if present) between + and M+.
Place the adaper so the 5 wires extending from the
adapter poke into the TriMetric terminal block as shown.
Tighten securely all 5 screws. For the adapter to fit in
some boxes it may be necessary to pull this end up away
slightly from front panel so adapter will fit in box.
G1
G2
SIG
+
+
MM
Wire the TriMetric in the
usual way (with the wires in
the same order as shown in
the regular TriMetric
instructions), except connect
to the adapter teminals as
shown. The wire jumper from
+ to M+ must connect only
here as shown.
(Not here.)
Wire the TriMetric in the
usual way (with the wires in
the same order as shown in
the regular TriMetric
instructions), except connect
to the adapter teminals as
shown. The wire jumper from
+ to M+ must connect only
here as shown.
(Not here.)
To battery connections
as shown in TriMetric
manual.
To battery connections
as shown in TriMetric
manual.
"TriMetric side""TriMetric side"
"TriMetric side""TriMetric side"
For TriMetric model TM-2020 meter only: For meter to read voltage correctly with 48V
systems (and jumpers configured as shown in STEP 1 for 48V) the "charged setpoint voltage" must be set
to above 35.0 volts. For meter to read correctly when jumpers are configured for 12 or 24V systems the
"charged setpoint voltage" must be set to below 35.0 volts. See TABLE 1 (page 13 of instructions and page
5) for how to do this. On table look under the DISPLAY MODE, volts.
For TriMetric model TM-2020 meter only: For meter to read voltage correctly with 48V
systems (and jumpers configured as shown in STEP 1 for 48V) the "charged setpoint voltage" must be set
to above 35.0 volts. For meter to read correctly when jumpers are configured for 12 or 24V systems the
"charged setpoint voltage" must be set to below 35.0 volts. See TABLE 1 (page 13 of instructions and page
5) for how to do this. On table look under the DISPLAY MODE, volts.
For TriMetric model TM-2B meter only For meter to read voltage correctly with 48V systems (and
jumpers configured as shown in STEP 1 for 48V) the meter must be set to 48V mode. To do this refer to TriMetric
instructions, part 2, pages 2-3 and page 7: "d7 program". Here is a summary:
1. Use "SELECT" to select "blank" display, (just after "Amp-Hour" display).
2. Hold "SELECT" down for several seconds until you see "D 0" flashing in display. Release "SELECT".
3. Push "RESET" repeatedly until display reads "d 7". Then push "SELECT". (In display you should see maximum
battery volts with occasionally flashing "d 7")
4. Push and hold down "SELECT"--and while holding push RESET momentarily. Release both buttons.
5. Either "24" or "48" will appear in dispay. To put in 48V mode, push reset unti "48" appears.
6. Push "SELECT". Meter is now in "48V" mode.
For TriMetric model TM-2B meter only For meter to read voltage correctly with 48V systems (and
jumpers configured as shown in STEP 1 for 48V) the meter must be set to 48V mode. To do this refer to TriMetric
instructions, part 2, pages 2-3 and page 7: "d7 program". Here is a summary:
1. Use "SELECT" to select "blank" display, (just after "Amp-Hour" display).
2. Hold "SELECT" down for several seconds until you see "D 0" flashing in display. Release "SELECT".
3. Push "RESET" repeatedly until display reads "d 7". Then push "SELECT". (In display you should see maximum
battery volts with occasionally flashing "d 7")
4. Push and hold down "SELECT"--and while holding push RESET momentarily. Release both buttons.
5. Either "24" or "48" will appear in dispay. To put in 48V mode, push reset unti "48" appears.
6. Push "SELECT". Meter is now in "48V" mode.
STEP 5: For 48 volt operation, if
you wish to slightly increase
accuracy of voltage reading, see
"calibration" on reverse of this
sheet.
STEP 5: For 48 volt operation, if
you wish to slightly increase
accuracy of voltage reading, see
"calibration" on reverse of this
sheet.
STEP 1: Configure jumpers properly on the adapter,
depending on your system voltage: 12, 24 or 48. Pull
three small rectangular jumpers straight off pins, and
place on correct position. If you are not sure which
setting to use, see "Maximum/minimum voltage
allowed to adapter", shown on reverse of this sheet.
STEP 1: Configure jumpers properly on the adapter,
depending on your system voltage: 12, 24 or 48. Pull
three small rectangular jumpers straight off pins, and
place on correct position. If you are not sure which
setting to use, see "Maximum/minimum voltage
allowed to adapter", shown on reverse of this sheet.
48V
24V
12V
48V
24V
12V
48V
24V
12V
48V
24V
12V
48V
24V
12V
48V
24V
12V
12 V. configuration12 V. configuration 24 V. configuration24 V. configuration 48 V. configuration48 V. configuration
Configuration jumpers.Configuration jumpers.
Adapter boardAdapter board
Back view of
TriMetric (with cover
removed)
Back view of
TriMetric (with cover
removed)
AdapterAdapter
TriMetric terminal
block.
TriMetric terminal
block.
STEP2STEP2 STEP3STEP3
STEP 4: IMPORTANT: Complete this step or TriMetric "VOLTS" reading will be off by a factor of 2.STEP 4: IMPORTANT: Complete this step or TriMetric "VOLTS" reading will be off by a factor of 2.