B l u e R i d g e
T e c h n o l o g i e s
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RK2-IG-V11.00
Retrofit Kit 2
Install Guide : Page 6
Connection
Power Specications (Figure 5)
Power In: 24VAC +/-10%, 30VA, 50-60 Hz
Auxiliary Out: 24VAC Full Wave Rectied
Digital Input Specications (Figure 6)
Digital Input: 24 two-wire inputs
Software Conguration: Maintained, state change, momentary on/off,
momentary on, or momentary off
Jumper Conguration: 8 input segments, dry contact (N) or 24VDC
externally powered (R)
Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / Dry
Contact 500’(152m) or externally powered 1,000’(304m)
Analog Input Specications (Figure 8)
Analog Input: 6 three-wire 0-5VDC inputs
Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / 250’(76m)
Digital Input Special Case (Figure 7)
Douglas WR8501-88 and equivalent switches may be congured to
operate with RK2. This conguration eliminates the external power
supply and green LED while maintaining the red LED as a pilot light.
(Figure 5)
(Figure 6)
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
Controller RIB-A / RIB-B 16-20pin Ribbon Cable
Controller Terminations RIB-A(1) Terminations RIB-B(1) Terminations
RIB-A RIB-B
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS (+) In
BAS (-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
J2
DDN Network
Terminator Jumper
LEXP Terminations
POWER INPUTS 1-16INPUTS 17-32
N
J5
J18 J19
ADDRESS
TO J26 OF Controller
J4
J9
J13
R
R N
B D
A C
DI Jumper
49-56*
DI Jumper
41-48*
Address
Jumper
Controller
Port
Power LED
DI 49
DI 50
DI 51
DI 52
DI 53
DI 54
DI 55
DI 56
GND
DI 41
DI 42
DI 43
DI 44
DI 45
DI 46
DI 47
DI 48
GND
GND
DI 32
DI 31
DI 30
DI 29
DI 28
DI 27
DI 26
DI 25
GND
DI 40
DI 39
DI 38
DI 37
DI 36
DI 35
DI 34
DI 33
DI Jumper
25-32*
DI Jumper
33-40*
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
Switch
Controller Terminations
AI (Analog Input) / DI (Digital Input) / GND (Ground)
*DI Jumper Position N(Dry Contact) / R(Externally Powered)
SW1 SW4SW3
OVERAUTO
BT485
DDN/CAN
5V
A6
A5
A4
A3
A2
A1
G
PWR
RUN
17-24
R
N
1-8
G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G
G 17 18 19 20 21 22 23 24
R
N
9-16
INPUT
POWER
24VAC
AUX VAC
RELAYS 33-60
J26
LEXP
RELAYS 1-32
R
N
S B- A+
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
ON
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3
J2
5VDC
AI 6
AI 5
AI 4
AI 3
AI 2
AI 1
GND
DI Jumper
17-24*
DI Jumper
1-8*
DI Jumper
9-16*
24VDC
DDN Network(-)
DDN Network(+)
GND
BT485
Terminator Plug
(if applicable)
BAS(+) In
BAS(-) In
Shield
Baud Rate / Protocol
Dip Switch
Network Address Rotary Switch 10’s
Network Address
Rotary Switch 1’s
Override Controls
Power LED
Run LED
LEXP Port
24VAC(+) Power In
24VAC(-) Power In
24VAC(+) Auxiliary Out
24VAC(-) Auxiliary Out
DDN Network
Terminator Jumper
DI 9
DI 10
DI 11
DI 12
DI 13
DI 14
DI 15
DI 16
GND
GND
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
GND
DI 17
DI 18
DI 19
DI 20
DI 21
DI 22
DI 23
DI 24
Relays 1-32
Relays 33-60
Controller
Digital Input: Two Button Low Voltage Switch (Dry Contact)
1
G
2
Switch 1
Switch 2
Common
Controller
CTS-DDN
DDN Network: CTS-DDN
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
CTS-DDN
DDN Network:
CTS-DDN
w/24VDC External Power Supply
24
H
L
G
24VDC (Red)
Signal (+) (Green)
Signal (-) (White)
Ground (Black)
CTS Leads
CL3P / 22AWG / 4 Conductor
Unsheilded
Controller
24
H
L
G
5V
A1
G
Power
Signal
Common
Signal
Power
Common
Analog Input: 5VDC Light Sensor
N/O
Common
Power
Ground
Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact)
Light Sensor
BAS Network (Input and Output)
*Do not terminate shield on BAS output.
Signal (+)
Signal (-)
Shield*
Belden 8760
A+
B-
S
A+
B-
S
Controller
Controller
Controller
1
G
Switch
Common
Digital Input: Douglas WR8501-88 or equivalent (Dry Contact)
Controller WR8501-88
1
G
White
Red
Power In: 24VAC
Controller Transformer
P1
P2
Occupancy
Sensor
GND 24V COM N/O N/C
BT485 Terminator
BAS Network (End-of-line Device)
Signal (+)
Signal (-)
Shield
Belden 8760
Controller
BT485
Network Address 10’s
Network Address 1’s
Un-terminated Terminated
J2 J2
DDN Network Terminator Jumper
Network Address
9600 19200 38400 76800
SW3 SW4
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
N2 Network Addresses 100-255
See right for N2 addresses 100-255
Baud Rate / Protocol Dip Switch: BACnet MS/TP
4800 9600 19200 38400
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
SW1
1
ON
2 3 4 5 6 7 8
Programming
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: P1
Network Address +200
SW1
1
ON
2 3 4 5 6 7 8
Network Address +100
SW1
1
ON
2 3 4 5 6 7 8
Programming / 9600
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: N2
Dry Contact
R
N
Digital Input (DI) Jumper
Externally Powered
R
N
24VDC Supply
24V GND
11.00”(279mm)
4.50”(113mm) 2.13”(54mm)
9.88”(251mm)
12”(304mm)
15.50”(394mm)16.50”(419mm)
Front
Front
1.56”(40mm)
Side
1.06”(27mm)
Side
Controller RIB-A / RIB-B
Front
Front
5
2
1
2
13 4
INPUT
POWER
24VAC
24VAC(-) Power In
24VAC(+) Power In
16pin Ribbon Cable
RO (Relay Output)
Relay Terminations
RED BLUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Pin 1
Pin 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 1
RO 2
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 17
RO 18
RIB-A(2) Terminations RIB-B(2) Terminations
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN1
RO 33
RO 34
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
RO 49
RO 50
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN2
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
16-20pin
Ribbon Cable
16pin
Ribbon
Cable
RO 1-16
RO 17-32
RO 33-48
RO 49-60
6
Controller
Digital Input: Two Button Low Voltage Switch (Externally Powered)
Switch
ARCnet
SW1
1
ON
2 3 4 5 6 7 8
Baud Rate / Protocol Dip Switch: BACnet ARCnet
1
G
2
Switch 1
Switch 2
Common
24VDC Supply
24VGND
(Figure 7)
(Figure 8)