BGH BMPE36CTL Manuel utilisateur

1
Modelos:
BMPE36CTL, BMPE60CTL & BMPE72CTL
Manual de usuario e instalación
Unidades interiores
de alta eficiencia
1.5 - 6 TR
Refrigerante R410-A

2
RECOGNIZE THIS SYMBOL AS AN INDICATION
OF IMPORTANT SAFETY
INFORMATIO
DO NOT DESTROY THIS MANUAL
Please read carefully and keep in a safe place for future reference by a serviceman.
is document is customer property and is to remain with this unit.
ese instructions do not cover all the different variations systems nor does it provide
for every possible contingency to be met in connection with installtion.
All phases of this installation must comply with NATIONAL STATE AND LOCAL CODES.
If additional information is required please contact your local distributor.
ese instructions are intended as an aid to qualified
licensed service personnel for proper installation, adjustment
and operation of this unit. Read these instructions
thoroughly before attempting installation or operation.
Failure to follow these instruction may result in improper
installation,adjustment, service or maintenance possibly
resulting in fire, electrical shock, property damage,
personal injury or death.

3
Safety
General
2.1 Unit dimensions
Applications
3.1 Vertical upflow
3.2 Vertical downflow
3.3 Horizontal
3.4 Installation in an unconditioned space
Electrical wiring
4.1 Power wiring
4.2 Control wiring
4.3 Grounding
4.4 Electrical data
Airflow performance
Ductwork
Refrigerant connections
7.1 Condensate drain tubing
Air filter (not factory-installed)
Filter installation dimensions
Wire diagram
Table of contents
04
08
09
10
10
10
12
13
14
14
14
15
15
16
18
19
19
21
22
23
1
2
3
4
5
6
7
8
9
10

4
1. Safety
is is a safety alert symbol. When you see this symbol on labels or in manuals,
be alert to the potential for personal injury.
is is an attention alert symbol. When you see this symbol on labels or in manuals,
be alert to the potential for personal injury.
Disconnect all power to unit before installing or servicing. More than one disconnect switch
may be required to de-energize the equipment. Hazardous voltage can cause server personal
injury or death.
If removal of the blower assembly is required, all disconnect switches supplying power to the
equipment must be de-energized and locked (if not in sight of unit ) so the field power wires
can be safely removed from the blower assembly. Failure to do so can cause electrical shock
resulting in personal injuring or death.
Because of possible damage to equipment or personal injury, installation, service, and
maintenance should be performed by a trained, qualified service personnel. Consumer service
is recommended only for filter cleaning / replacement. Never operate the unit with the acess
panels removed.
ese instructions are intended as an aid to qualified, licensed service personnel for proper
installation, adjustment and operation of this unit. Read these instructions thoroughly before
attempting installation or operation.
failure to follow these instructions may result in improper installation, adjustment, service or
maintenance possibly resulting in fire, electrical shock, property damage, personal injury or
death.

5
Decide the correct way of conveying the equipment.
Try to transport this equipment with the original package.
If the air conditioner needs to be installed on a metal part of the building, electric insulation
must be performed, and the installation must meet the relevant technical standards of
electric devices.
e appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits must be disconnected.
e appliance must be positioned so that the plug is accessible.
e enclosure of the appliance shall be marked by word, or by symbols, with the direction of
the fluid flow.
e appliance shall be installed in accordance with national wiring regulations If the supply
cord is damaged, it must be replaced by the manufacture or its service agent or a similarly
qualified person in order to avoid a hazard.
An all-pole disconnection switch having a contact separation of at least 3mm in all poles
should be connected in fixed wiring.
e temperature of refrigerant circuit will be high, please keep the interconnection cable away
from the copper tube.
is appliance can be used by children aged from 8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in a safe way and understand
the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision。
Install the unit where the air inlet and air outlet are free from obstacles and strong wind.
Install the unit in a dry and well ventilated place.
Install the unit where the bearing surface is level and can bear weight of the unit, and is
suitable for installing the unit horizontally without increasing noise or vibration.
Install the unit where the operation noise and the expelling of air do not affect neighbors.
Install the unit where no flammable gas is leaked.
Install the unit where it is convenient for pipe connection and electric connection.

6
DISPOSAL: Do not dispose this product as unsorted municipal waste.
Collection of such waste separately for special treatment is necessary.
Do not dispose of electrical appliances as unsorted municipal waste, use separate collection
facilities.
Contact you local government for information regarding the collection systemsavailable.
If electrical appliances are disposed of in landfills or dumps, hazardous substances can leak
into the groundwater and get into the food chain, damaging your health and well-being.
e unit must be permanently grounded. Failure to do so can result in electrical shock causing
personal injury or death.
PROPOSITION 65: is appliance contains fiberglass insulation. Respirable particles of
fiberglass are known to State of California to cause cancer.
All manufacturer products meet current federal OSHA Guidelines for safety.
California Proposition 65 warnings are required for certain products, which are not covered by
the OSHA standards.
California’s Proposition 65 requires warnings for products sold in California that contain or
produce any of over 600 listed chemicals known to the State of California to cause cancer
or birth defects such as fiberglass insulation, lead in brass, and combustion products from
natural gas.
All “new equipment” shipped for sale in California will have labels stating that the product
contains and /or produces Proposition 65 chemicals. Althoughwe have not changed our
processes, having the same label on all ourproductd facilitates manufacturing and shipping.
We cannot always know“when, or if” products will be sold in the California market.
You may receive inquiries from customers about chemicals found in, or produced by, some
of our heating and air-conditioning equipment, or found in natural gas used with some of our
products. Listed below are those chemicals and substances commonly associated with similar
equipment in our industry and other manufacturers.

7
Glass Wool (Fiberglass) Insulation
Carbon Monoxide (CO).
Formaldehyde
Benzene
More details are available at the websites for OSHA (Occupational Safety and Health
Administration), at www.osha.gov and the State of California’s OEHHA (Office of
Environmental Health Hazard Assessment), at www.oehha.org. Consumer education is
important since the chemicals and substances on the list are found in our daily lives.
Most consumers are aware that products present safety and health risks, when improperly
used, handled and maintained.
Make sure the blower motor support is tight (3-motor mount
bolts) then check to see if wheel is secured to motor shaft
before operating unit.
BLOWER MOTOR SHIPPING BOLT
e first 36 inches of supply air plenum and ductwork must be constructed of sheet metal as
required by NFPA 90B. e supply air plenum or duct must have a solid sheet metal bottom
directly under the unit with no openings, registers or flexible air ducts located in it. If flexible
supply air ducts are used they may be located only in the vertical walls of rectangular plenum,
a minimum of 6 inches from the solid bottom. Metal plenum of duct may be connected to the
combustible floor base, if not, it must be connected to the unit supply duct exposed to the
supply air opening from the downflow unit.
Exposing combustible (non-metal) material to the supply opening of a downflow unit can
cause a fire resulting in property damage, personal injury or death.
Exception warning to downflow:
Installations on concrete floor slab with supply air plenum and ductwork completely encased
must be not less than 2 inches of concrete (See NFPA 90A).

8
2. General
e unit can be positioned for bottom return air in the upflow position, left and right return in
the horizontal position, top return in downflow position.
is Air Handler provides the flexibility for installation in any upflow or downflow horizontal
application. e direct drive motors provides a selection of air volume to match any
application. 3-Speed motors provide selections of air flow to meet desired applications.
Top and side power and control wiring, accessible screw terminals for control wiring all
combine to make the installation easy, and minimize installation cost. Please contact your local
distributor. See fig.1.
For ensure the proper installation, Select the enough solid and level site.
Ensure enough space required for installation and maintenance.
Top view of the outdoor unit (multiple units installed).

9
2.1 Unit dimensions
Dimension data
Note: 25º clearance is required in the front
of the unit for filter an coil mantenance.
Fig 1 Dimensions
Electrical conections may exit top
or either side.
24
36
60
72
Dimensions inch [mm]
UNIT HEIGHT
“H” IN. [mm]
MODEL
SIZE
UNIT WIDTH
“W” IN.[mm]
UNIT LENGHT
“D” IN.[mm]
SUPPLY
DUCT “A”
UNIT WEIGHT/
SHIPPING WEIGHT
(LBS.[kg])
41-3/8”[1050]
46-1/2”[1180]
54-1/2”[1385]
54-1/2”[1385]
18-1/8”[ 460]
19-5/8”[500]
22”[560]
22”[560]
20-1/2”[520]
20-5/8”[550]
24”[610]
24”[610]
16”[406]
18”[456]
19-1/2”[496]
19-1/2”[496]
106/119 [48]/[54]
141/156 [64]/[71]
171/187 [78]/[85]
171/187 [78]/[85]

10
3. Applications
3.1 Vertical Upflow
• Vertical Upflow configuration is the factory set on all models (see Fig 1).
• If a side return air opening is required, field fabricate a return air plenum with an opening
large enough to supply unit and strong enough to support unit weight.
• If return air is to be ducted, install duct flush with floor. Use fireproof resilient gasket 1/8 to
1/4 in. thick between the ducts, unit and floor. Set unit on floor over opening.
IMPORTANT NOTE
Torque applied to drain connections should not exceed 15.ft.lbs.(see Fig.1&2)
3.2 Vertical Downflow
Conversion to Vertical Downflow: A vertical upflow unit may be converted to the
vertical downflow on it. Remove the door and indoor coil and reinstall 180° from
original position. See Fig. 2~3.
Fig2 Dimensions for
front connect coil