Technical Documentation
KSR-Z –Capacitor-Bank Protection Relay
Page 9/36
2.3 Other features
2.3.1 Natural unbalance compensation
The KSR-Z contains the function "natural unbalance compensation". This function allows to
measure and store the natural unbalance current (Inuc)at the protected capacitor banks. The value
of the natural unbalance current depends on production tolerances of the used capacitors. The
unbalance current is measured in the star point connection of two stages. This current can be
compensated in amplitude and phase angle to zero, to detect further changes in phase angle and
absolute value. During the normal operation the KSR-Z subtracts the stored Inuc value from the
current In. The result of this operation should be "0". In case of variations of this result it is possible
to set a threshold between 0.01A and 50kA to trigger an alarm.
Attention: The natural unbalance compensation is only possible with a voltage signal between L1
–N and a current signal at current channel 1. This signals are needed get the information of the
phase angle and absolute value.
2.3.2 Metering functions
The KSR-Z metering features provide continuous measurement of Currents and Voltages which are
connected as analogue inputs. The signal processor calculates different values from these inputs.
VLine to Neutral TRMS Voltages VL1-N, VL2-N, VL3-N
VLine to Line TRMS Voltages VL1-L2, VL2-L3, VL3-L1
THD THD –factors for voltages (VLine to Neutral) and currents (IL1, IL2, IL3, IUB)
I TRMS Current IL1, IL2, IL3, IUB
If RMS values of fundamental waves of currents IL1, IL2, IL3 and IUB
(without harmonics)
I UC4 Unbalanced current compensated value IUC4
I EF Earth fault current actual value IEF and compensated value IEF-cp
Ith exponentially damped current values of IL1, IL2, IL3 and IUB to simulate
thermal measurement
T ambient temperature
Harmonics Order of (3-51) for current and voltages (only ODD harmonic orders)
Please check Appendix A for detailed explaination of thermal damping function.