I. CLEANING THE UNIT
If it is necessary to clean the outside surface,
use a dry cloth or sponge. Do not use
solvents or abrasive cleaners. Do not open
the enclosure if it is wet (risk of electrical
shock).
J. FUSE REPLACEMENT
The panels mains input is protected by a
T500mA, 250-V fuse. Use no other type of
fuse or the Eco-6 panel could be damaged or
could fail to perform properly.
Warning Shock Hazard. Exposed
Circuitry within! It is strongly
recommended the power is isolated before
carrying out any work within the unit.
K. STORAGE AND HANDLING
OF SENSING CABLE
Despite their rugged construction, EcoLeak
and TraceTek sensing cables must be handled
in a manner appropriate for a sensing
device or they may be damaged and require
replacement.Therefore, you should follow
some basic rules for storing and handling all
sensing cables:
• Store spare cable in its original packaging
or container in a clean, dry place until ready
for installation.
• Schedule cable and probe/sensor
installation after all mechanical, plumbing,
and electrical work has been completed
• Clean the area where the cable is to be
installed, and remove any obvious debris or
other sources of contamination.
• Do not solder or weld near the cable
without providing protection from heat,
solder ux, or weld splatter.
• Do not drop tools or oor tiles on the cable;
sharp and heavy objects may damage the
cable.
• Avoid walking or stepping on the cable.
Provide shielding (for example, a half shell
• of plastic pipe or upturned cable tray) where
additional protection is necessary.
• Do not use insulation tape or similar to
secure sensing cable (some tapes and
adhesives absorb moisture) or use solvents
that could eventually cause an alarm.
• Do not drag sensing cable through
contaminants (such as pipe ux, PVC
cement, solvents, oil, water or dirt)
L. NOTE ON CABLE CLEANING
EcoLeak and TraceTek sensing cables use
a solid core polymer construction and can
usually be easily cleaned with tap water. In
extreme cases or when large amounts of
cable are contaminated, either cable can
be washed in a dishwasher. Try a water
only (no detergent) cycle rst and avoid the
heated dry cycle. When placing the cable in
the dishwasher be sure to keep water out of
the connectors (TraceTek cable ends can be
connected together for convenience).
The TraceTek TT5000 sensing cables cannot
be cleaned and must be replaced after
exposure to fuel or solvent.
K. FINAL COMMISSIONING
CHECK LIST
1. Complete a system inspection in the
presence of the owner.
2. Ensure a plan showing the location of the
zone and sensor is available.
3. Check that the following information
is clearly visible adjacent to the alarm
module:
• “In case of alarm” instruction.
• Location of the system “as tted
drawing” in case it is not installed adjacent
to the alarm module.
• Name and contact number of the person
responsible for operating the system
• Supplier’s contact name and address.
Or details of the installation/maintenance
company.
4. Hand over these Installation, Operating
and Maintenance Instructions.