Antec MULTI-VARIABLE MONITOR Series Manuel utilisateur

MANUAL V100
MULTI-VARIABLE MONITOR
MVM Series

MULTI-VARIABLE MONITOR
TABLE OF CONTENTS
IMPORTANT NOTES
CAUTION
This mark indicates an important point for the proper
function of the MVM. Improper installation or setup may
cause unit failure. Pay close attention to all caution and
tech tips throughout this manual.
For local area support, please
contact your local Antec Controls
Representative
For more information visit
AntecControls.com
Product Overview
General......................................................................... 1
MVM Specifications ..................................................... 1
Included in Package...................................................... 2
Sample Wiring Diagram................................................ 3
Installation and Mounting Instructions
Wall Cutout and Bracket Installation............................. 4
Display Navigation
Functionality ................................................................. 5
Home Screen ............................................................... 6
MVM Operation ........................................................... 7
Settings ........................................................................ 8
Login Screen ................................................................ 9
Networking & Setup
BACnet Integration ..................................................... 10
Configuration
Graphic Configuration................................................. 11
Data Point Configuration ............................................ 17
Maintenance
Troubleshooting.......................................................... 24

General
The Multi-Variable Monitor (MVM) is a
touchscreen monitor that can be used
to display and adjust settings from
multiple devices on a BACnet network.
The MVM supports both BACnet MS/
TP and BACnet IP to connect with the
room level devices.
The MVM can be used to display any
BACnet point including alarm status,
room temperature, humidity, room
pressure, air change rate per hour,
and occupancy. The MVM is able to
connect to multiple devices, which
allows it to be used as a remote
station to monitor multiple rooms
while displaying critical information for
each room.
An easy to use interface allows the
user to quickly and easily identify the
source of any alarms. Audible alarms
are available locally and remotely.
Password protection ensures that
only administrators can change room
settings.
MVM Specifications
• Dimensions:
7" – 8.8 in. (223 mm) x 6.4 in. (162 mm) x 2.6 in (65 mm)
15" – 15.5 in. (394 mm) x 12.5 in. (318 mm) x 2.6 in (65 mm)
• Display Type:
7" – Capacitive touch, 7.0 in. (178 mm), TFT, dimmable
15" – Capacitive touch, 15.0 in. (381 mm), TFT, dimmable
• Resolution:
7" – 800 px x 480 px, 262144 colors
15" – 1024 px x 768 px, 262144 colors
• Input Power:
7" – 24 VAC, 14 VA, Class 2
15" – 24 VAC, 25 VA, Class 2
• Environmental (operating): 550°F to 105°F (10°C to 40°C), 10% to 90% R.H. (non-condensing)
• Communication Protocol: BACnet MS/TP, BACnet IP
• Face: Glass, IP54
MULTI-VARIABLE MONITOR
PRODUCT OVERVIEW
1
AntecControls.com |MVM - Manual
FRONT DISPLAY

Included in Package
1. Multi-Variable Monitor
Quantity: 1
2. Mounting Bracket
Quantity: 1
3. Installation Manual
Quantity: 1
Please ensure you have all
components before proceeding.
Inspect components for shipping
damage. Do not install any
components that appear damaged,
contact your local Antec Controls
Representative for replacements.
For the latest information
and videos please visit
AntecControls.com
1. MULTI-VARIABLE MONITOR (MVM) 3. INSTALLATION MANUAL
2. MOUNTING BRACKET
MANUAL V100
MULTI-VARIABLE MONITOR
MVM Series
INCLUDED ITEMS
MULTI-VARIABLE MONITOR
PRODUCT OVERVIEW
2MVM - Manual |AntecControls.com

Sample Wiring Diagram
MULTI-VARIABLE MONITOR
PRODUCT OVERVIEW
3
AntecControls.com |MVM - Manual

Ensure you have all components
necessary for installation. Inspect
components for signs of shipping/
handling damage. Do not proceed
if you suspect any components are
damaged.
S
K
J
L
CABLE ENTRIES
RM
QN
P
Dim. 7" 15"
J 7.677" 13.976"
K 5.63" 11.614"
L 8.11" 14.37"
M 0.827" 1.87"
N 2.441" 5.217"
P 1.181" 1.839"
Q 2.756" 3.543"
R 1.969" 3.937"
S 1.969" 3.937"
WALL MOUNT DIMENSIONS
MOUNTING BRACKET AND MVM INSTALLATION
MULTI-VARIABLE MONITOR
INSTALLATION AND MOUNTING INSTRUCTIONS
4MVM - Manual |AntecControls.com

Functionality
The MVM is designed to provide ease of use monitoring of multiple variables from BACnet devices.
The MVM Home Screen provides monitoring information in a simple format displaying information including Room Status and
Isolation Mode.
Features
1. Password protected menus.
2. Monitor up to 8 rooms simultaneously.
3. Audible Alarms - available locally and remotely.
The home page will display in one of the following configurations, depending on the number of rooms that are being
monitored.
SINGLE ROOM CONFIGURATION
FOUR ROOM CONFIGURATION
TWO ROOM CONFIGURATION
SIX ROOM CONFIGURATION
THREE ROOM CONFIGURATION
EIGHT ROOM CONFIGURATION
MULTI-VARIABLE MONITOR
DISPLAY NAVIGATION
5
AntecControls.com |MVM - Manual

Menu Button – Opens the navigation menu which allows access to
the login screen and the settings menu.
Room Name – Displays the name of the room being monitored. This
is configurable and is password protected.
Room Pressure – The current room pressure reading.
Room Status – Indicates whether the room is maintaining the
desired setpoints in its current mode.
Isolation Mode – Indicates whether the room is in Negative or
Positive Isolation mode.
Home Screen
Upon startup of the MVM, the Home Screen is displayed.
This Home Screen provides the user with a clear indication of the room mode, status, and pressure reading.
1
2
3
4
5
5
4
3
2
1
MULTI-VARIABLE MONITOR
DISPLAY NAVIGATION
6MVM - Manual |AntecControls.com

MVM Operation
When fully set up, the MVM can be interfaced with any BACnet device to monitor environmental measurements and room
status. The MVM will change its display to match the room status of the controller that is being monitored.
Status LCD Display
Normal - Pressure reading within low / high set points
Caution - Example: Open Door
Alarm - Example: Pressure reading outside low/high alarm set points
Setback - Pressure measured but no alarms
MULTI-VARIABLE MONITOR
DISPLAY NAVIGATION
7
AntecControls.com |MVM - Manual

TCP/IP – Allows the user to adjust the IP address of the device when
connecting to a local network.
BACnet – Allows the user to adjust the BACnet settings of the MVM.
CEA709 – Not required.
CEA852/RNI – Not required.
Date/Time – Can be used to set the date and time of the device.
Commands – Allows the user to perform a number of commands such as
calibrating the touch screen or resetting the device.
Storage – Not required.
Info – Allows the user to adjust the screen brightness and the speaker
volume.
About – Shows the device firmware.
Exit – Closes the setup menu.
Settings
The Settings are accessible through the Home Screen and are password protected (see previous section).
These menus allow the user to change any of the configurable options on the MVM.
TCP/IP
BACnet
CEA709
CEA852/RNI
Date/Time
Commands
Storage
Info
About
Exit
System Setup Menu
MULTI-VARIABLE MONITOR
DISPLAY NAVIGATION
8MVM - Manual |AntecControls.com
Table des matières