Assembly and Commissioning Instructions
Softstarters
VS ... - 17...45

VS II ...-17...45 1
as per 07/10 15700.10005
Table of Contents Page
1. Safety notes 3
2. Conformity 3
3. General description 4
4. Usage to the intended purpose 4
5. EC Declaration of Conformity 5
6. Block diagram 6
7. Commissioning 6
7.1 Mounting instructions 6
7.2 Connection 8
7.3 Parameter settings 9
8. LED indicators 11
8.1 Option „M“ 11
9. Fault 12
9.1 Fault description 12
9.2 Fault remedy 13
9.3 Resetting of faults 13
10. Technical data (standard)* 14
10.1 Environmental conditions 15
11. Dimensioning rules 15
11.1 Dimensioning of pre-fuses 15
11.2 Determining the permissible starting frequency 17
12. Special units 20
12.1 Devices with rated voltage of 230V or 480V 20
12.2 Devices featuring a wide-voltage-range power section 20
12.3 Devices featuring special voltage >= 500V 20
12.4 Devices with motor-PTC input 20
13. Installation guideline 22
13.1 Connection 22
13.1.1 Earthing 22
13.1.2 Cabling 22
13.2 General connection diagram 24
13.3 Typical connections 25
13.4 Motor/Soft start in delta connection (only units with option „M“) 26
13.5 Wide-voltage-range connection 27

2 VS II ...-17...45
Notes and symbols used in these instructions
Note: Notes explain the advantages of certain adjustments or settings and help
you to make use of the device in the best possible way.
Warning notices: Read them carefully and follow them strictly!
Warning notices are indicated in order to protect you against danger or to
help you to prevent the device from being damaged.
Caution: Danger to life through electric shock!
When you see this sign, always make sure that the device is de-energized
and secured against unintentional energizing.
These commissioning instructions were prepared with great care. Nevertheless, Advanced
Control does not assume liability for damage resulting from mistakes
possibly contained in this manual. Technical changes that serve to improve the product are
subject to change without notice.
14. Dimensions 28
15. Special units 28

VS II ...-17...45 3
1. Safety notes
The described devices are electrical equipment for use in industrial electrical power
installations. An impermissible removal of the covers during operation can cause
serious damage to your health, since these devices contain live parts with high
voltages.
Adjustment work may only be performed by trained staff observing the safety regulations.
Assembly and mounting work may only be carried out with the equipment deenergized.
Make sure that all drive components are properly earthed.
Please read these commissioning instructions carefully before putting the device into operation.
Besides, the user must ensure that the devices and associated components are fitted and
connected in accordance with the appliable local, legal and technical regulations. The VDE-
regulations VDE 0100, VDE 0110 (EN 60664), VDE 0160 (EN 50178) , VDE 0113 (EN 60204,
EN 61310),VDE 0660 (EN 50274) plus the appropriate regulations of the TÜV (Technical Control
Association) and the trade associations apply in Germany.
The user must ensure that the drive turns into a safe operating state following a device failure, in
the event of maloperation, or if the control unit has failed etc..
Caution: Even if the motor is at rest, it is not physically separated from the mains.
2. Conformity
In industrial linguistic usage the drive controllers of the type series VersiStart II are called
"devices", however, in the sense of the "law on the safety of equipment", the "EMC-law" or the
"EC-maschinery directive" they are not devices or machines ready for use or connection but they
are components. It is only possible to define their final function, when these components are
integrated into the design and construction of the user.
To be able to use the devices to their intended purpose, it requires power supply networks
according to DIN EN 50160 (IEC38).
The user takes the responsibility that the user’s design and construction comply with the appli-
cable legal provision.
The commissioning is strictly forbidden as long as the conformity of the final product with the
guidelines 2006/42/EC (Machinery directive) and 2006/95/EC (Low voltage directive) is not
proved.

4 VS II ...-17...45
3. General description
In the case of the soft starters of the VersiStart II type the motor voltage is changed in two phases
(1L1/5L3) by a generalized phase control and power semiconductors. Starting from an adjustable
starting trigger angle the trigger angle is continually reduced. Via the adjusted ramp-up time the
motor voltage increases according to a ramp function until the maximum value is reached. When
the acceleration time is over, the power seminconductors are bypassed by integrated relays and
the motor is directly supplied with power from the mains.
After opening of the start/stop-contact, the trigger angle is continuously increased via a ramp-
function, and, as a result, the motor voltage is decreased. The motor softly decelerates with the
adjusted deceleration time.
Acceleration time, starting voltage and deceleration time can be separately adjusted via potentio-
meters.
Acceleration or deceleration are effected by closing or opening of the contact on the terminals
X1/X2.
The boost function is switched on by bridging the terminals X1/X3. Thus, at the beginning of the
soft start, an increased starting voltage is applied to the motor for a period of 0,5s.
The power supply to the control electronics is effected via the power section. On request, the
power supply can also be implemented via an external power supply unit (24V min. 150mA DC).
The devices are suitable for an operation of 3-phase motors in star or delta connection.
Interconnection of motors in a so-called -connection is possible as well.
For -connection, it is necessary to use a main contactor K1, since one motor winding lies
directly between two phases.
4. Usage to the intended purpose
The devices of the VersiStart II-series are electrical equipment that is used in industrial electrical
power installations. They are designed for application in machines, in order to reduce the starting
torque and starting current peaks as well as the tripping torque of drives with three-phase
induction motors.
Typical Applications:
• door and gate drives
• pumps, ventilators, fans
• conveying systems
• packaging machines
• transport systems, assembly lines
• machine applications
3
3

VS II ...-17...45 5
5. EC Declaration of Conformity
EC Declaration of Conformity
Name / Address: Peter Electronic GmbH & Co.KG
Bruckäcker9
92348 Berg
Germany
hereby declares that the following product (device, component, unit) in the version as supplied
Product designation: Softstarter
Serien / type designation: VS II 230...690-17...45; B; M; UL; D; H
Article group: 257...
Year of manufacture: 2005
complies with the provisions of the following EC-directives:
2004/108/EG concerning
Electromagnetic compatibility
and
2006/95/EG concerning
Electrical equipment designed for use within
certain voltage limits
The following harmonized standards have been applied:
EN 60947-1: Low-voltage switchgear and
2008 controlgear
General rules
EN 60947-4-2: Low-voltage switchgear and
2007 controlgear
Contactors and motor-starters -
AC semiconductor motor
controllers and starters
This EC Decleration of Conformity is no longer valid, if the products is modified or changed
without our agreement.
This declaration is issued under the sole responsibility of the signatory.
Berg, 05.08.2009 Dr. Thomas Stiller, Managing Director
(place, date)
(signatory and function of the signatory)
(signature)
The manufacturer / company placing the product on the market
(authorized representatives of the manufacturer / companies placing the product on the market
that are established within the Community)

6 VS II ...-17...45
6. Block diagram
7. Commissioning
The device is to be put into operation in 3 steps:
1. Mounting
2. Connection and
3. Parameter setting
Note:
Please notice the max. permissible starting current (under 7/Technical data).
7.1 Mounting instructions
Caution: Danger to life through electric shock!
The following conditions are to be complied with in order to ensure a safe
and reliable operation of the VersiStart II.
1. The device series VersiStart II is to be used under conditions of the
overvoltage category III.
2. Make sure that pollution degree 2 or better, in accordance DIN EN60644-1 /
IEC664, is complied with.
supply
voltage
Trigger
pulse
generator
6T32T1 4T2
Control
for
bypass
5L31L1 3L2
Electronics
Ramp
control
Start
U start
X8
X7
RA2
t acc t dec
X3
X2
Boost
X6
X5
RA1
X1
X4
control supply U 24VDC
at option "B"
+
s

VS II ...-17...45 7
3. The device has to be installed into a housing (min. degree of protection: IP54).
Please take care of a sufficient heat dissipation.
4. The device must be operated without being exposed to contamination by
water, oil, carbon deposits, dust, etc..
5. Insert in North America, UL and CSA-listed.
5.1 ’Suitabe For Use On A Circuit Capable Of Delivering Not More Then 5kA rms
Symmetrical Amperes, 600 Volts Maximum’ and ’When Protected by A Circuit
Breaker type N2MB2-AF63-NA 63A, 600 Volts Maximum.’
5.2 ’Use Copper Conductors 60/75°C, or 75°C only.’
Place the device vertically on a perpendicular mounting plate with the motor terminals pointing
downwards. The device is to be snap-mounted onto a 35mm top-hat rail according to DIN EN
50022. Underneath the device, no additional heat sources such as heating resistors must be
mounted or arranged.
Warning:
To avoid heat concentrations, a distance of at least 40mm is to be kept
between cable duct and device.
Clearance X
Under normal drive conditions, the devices can be
mounted side by side.
In the case of applications requiring high starting
frequencies and / or high-inertia starting, the devices
should be mounted with a distance of approx. 10mm in
between them, in order to ensure good ventilation of the
heat sink.
On
Bypass
versi start II
1
2
3
4
5
6
7
8
0
100%
0
100%
0
100%
t
t
U
Start
X
min. 40mm
min. 40mm

8 VS II ...-17... 45
7.2 Connection
Power section (see also connection diagram)
Control section
The input resistance of the control inputs is 10kOhm. To control them, it is necessary to use
switching contacts enabling reliable switching of the lower control currents (e.g., AgNi+Au)!
If the contact on the terminals X1 a. X2 is closed, the motor accelerates with the adjusted accele-
ration time ramp. When the contact is open, the motor decelerates with the adjusted deceleration
time ramp.
Caution: Danger to life through electric shock!
The motor is not physically separated from the mains.
Alternatively, the device can also be controlled with d.c. voltage.
If only soft starts are required, VersiStart II may also be controlled via the main contactor. For this
purpose, the terminals X1 and X2 have to be bridged.
Adjusting the control type
Devices of the VersiStart II series may be controlled by two types of control.
1. Control with a switching contact or switching transistor between terminal X1 and X2.
2. Control by d.c. voltage 10 … 24VDC between terminals X2 and X4.
Control supply voltage USonly in the case of wide-voltage devices (option B)
Between the terminals X1 (+) and X4 ( ) an auxiliary voltage of 24VDC ±10%/150mA is to be
injected.
Terminal 1L1:
Terminal 3L2:
Terminal 5L3:
Earth connection
Terminal 2T1:
Terminal 4T2:
Terminal 6T3:
Mains voltage L1
Mains voltage L2
Mains voltage L3
PE
Motor terminal U
Motor terminal V
Motor terminal W
X2
Start/Stop
Control terminals +
X1 X3 X4
RA 1 RA 2
Boost
Fault Device
bypassed
X5 X6 X7 X8

VS II ...-17...45 9
7.3 Parameter settings
On the front panel there are 3 potentiometers by means of which the following settings can be
made.
Default setting of potentiometers:
Adjusting soft start
To adjust an optimum starting behavior, you should carry out a test run. Contrary to the default
settings, you should make the following basic potentiometer-settings.
Switch on the supply voltage and start acceleration. Watch the starting behavior and adapt the
approporiate parameters to your drive. At any rate, the starting voltage should be adjusted with
the potentiometer UStart so that the motor starts immediately. At the same time, unnecessary
humming with the motor being at rest is to be avoided.
The potentiometer is to be adjusted so that the requested acceleration time or starting
characteristics is achieved. The acceleration time should always be chosen as short as
possible, in order to keep the thermal stress acting on device and motor as small as possible.
This leads to short times until the bypass relays pull in and ensures good acceleration
characteristics while the power semiconductors and motor are less heated. This is of special
importance in the case of high-inertia starting or high switching frequencies. The acceleration
time, however, has to be adjusted so that the motor reaches nominal speed before the internal
bypass relays close.
Warning:
If the adjusted acceleration time is too short, the internal bypass relays close
before the motor has reached nominal speed. This can cause damage to
the bypass relays.
Parameter Poti Setting range
Acceleration time Acceleration time adjustable from 0.5...10sec
Starting voltage UStart 40…80% of rated voltage
Deceleration time adjustable from 0.5...10sec
Potentiometer (acceler. time) = mid-position
Potentiometer UStart (starting voltage) = left stop (counter-clockwise)
Potentiometer (deceler. time) = left stop (counter-clockwise)
Fans, roller tracks, conveyor belts, etc. 50%, UStart 0%, 0%
Centrifuges, conveyor screws, mixers,
compressors, etc.
50%, UStart 50%, 50%
Pressure pumps, etc. 50%, UStart 50%, 50%