ACV BG 2000-S Series Manuel du propriétaire

662Y0000
INSTALLATION OPERATING AND
SERVICING INSTRUCTIONS
NOTICE D’INSTALLATION,
D’UTILISATION ET D’ENTRETIEN
INSTALLATIE-, GEBRUIK- EN
ONDERHOUD INSTRUCTIES
NOTICIAS DE INSTALACIÓN,
UTILIZACIÓNY MANTENIMIENTO
ISTRUZIONI D’INSTALLAZIONE,
USO E MANUTENZIONE
ANLEITUNG ZU INSTALLATION,
GEBRAUCH UND WARTUNG
exellence in hot water
EN
DE
IT
ES
NL
FR
BG 2000-S
BG 2000-S 25 / 35 / 45 / 55
BG 2000-SV 35
BG 2000-S 60 / 70
BG 2000-S 100

INSTALLATION OPERATING AND SERVICING INSTRUCTIONS 1
NOTICE D’INSTALLATION, D’UTILISATION ET D’ENTRETIEN 7
INSTALLATIE-, GERBUIK- EN ONDERHOUD INSTRUCTIES 13
NOTICIAS DE INSTALACIÓN, UTILIZACIÓNY MANTENIMIENTO 19
INSTRUZIONI DELL’ INSTALLAZIONE, DELL’ USO E DI MANUTENZIONE 25
ANLEITUNG ZU INSTALLATION, GEBRAUCH UND WARTUNG 31
EN
DE
IT
ES
NL
FR
EN ISO 9002 : 1994 Certification Watermark Licence - AS 3498Safety Quality License for boiler and pressure vessel

A D
G
F
EB
C
L1
N
1
23456789101112
S3
B4
N
T2
T1
L1
L1
N
123456789101112
S3
B4
N
T2
T1
L1
L1
N
123456789101112
S3
B4
N
T2
T1
L1
1 7
2
5
R
3 4
6
P1
P2
P3
P4
BG 2000-S / 60 / 70
BG 2000-S / 100
BG 2000-S / 60 / 70
BG 2000-S / 100
BG 2000-S / 25 / 35 / 45 / 55 - (SV / 35)
BG 2000-S / 25 / 35 / 45 / 55 - (SV / 35)

L
M
1
2
3
4

R
U
T
S
N
Q
P
O
X
Y
Z
12
3
4
1
2
BG 2000-S / 60 / 70 / 100
BG 2000-S / 25 / 35 / 45 / 55 - (SV / 35)
BG 2000-S / 60 / 70 / 100

H
K
J
I
BG 2000-S / 25 / 35 / 45 / 55
BG 2000-SV / 35
BG 2000-S / 60 / 70
BG 2000-S / 100
1
6
5
23
4
7
1
6
5
23
4
7
1
6
5
23
4
7
1
6
5
23
4
7
89
10
11
12
13
14
15
89
10
11
12
13
14
15
89
10
11
12
13
14
15
89
10
11
12
13
14
15

1
EN
■OPERATION 2
◆Controlling the air - gas mixture 2
◆Lighting and flame control 2
◆Functional diagram 2
◆Burner tube gas 2
◆Description - burners 3
■FITTING OF THE BURNER 3
■SETTINGS 3
■SETTING PROCEDURE IN CASE OF REPLACEMENT 3
◆Fan rotation speed 3
◆Gas flow rate 3
◆Electrode adjustment 4
■BURNER COMPONENTS 4
■DIMENSIONS 4
■BURNER WIRING 4
■SERVICING THE BURNER 4
■FAULT-FINDING PROCEDURES 5
◆Fault table 5
◆Table of corrective measures 6
■INDEX
These instructions are intended for qualified heating engineers trained by ACV.
BG 2000-S burners are preset at the factory for natural gas.
ACV reserves the right to change the technical specifications and components of its products without prior notice.

2
EN
■OPERATION
The BG 2000-S burner is fitted with a gas valve – venturi assembly, an electronic controller, a fan, a
flame holder and lighting and ionisation electrodes.
◆CONTROLLINGTHE AIR – GAS MIXTURE (illustration D)
As the fan sucks in air through the venturi, a drop in pressure (P1) is produced in the neck of the venturi.The
gas valve regulator then reacts to maintain a pressure differential equal to the offset value between the
pressure at the gas valve outlet (P2) and atmospheric pressure (P3): P2 – P3 = offset
If the air flow decreases, P1 increases;the same occurs for P2; P2 is then >P3;the regulator R is moved higher
to make P2 – offset = P3; pressure P4 falls and the valve C is turned down: the gas flow decreases.
By careful adjustment of the offset, an air – gas pressure ratio of 1 is obtained, regardless of the fan speed.
The pressure differential between the venturi neck and the gas valve outlet then causes gas to be sucked
through the venturi.
The gas flow adjustment screw can be used to adjust the quantity of gas injected for a given air flow, which will
set the %CO2 in the flue gas. A given output can then be set simply by adjusting the speed of rotation of the
fan and the % CO2 to preset values.
◆LIGHTING AND FLAME CONTROL
The S 4565 AD 2080 control unit performs the tasks of lighting the burner by producing a spark at the ignition
electrode, and maintaining the flame when the gas valve is opened by measuring the ionisation current.
The lighting sequence is shown in the diagram below:
When the boiler thermostat detects a demand for heat, the fan starts; after 15 seconds of preliminary flushing,
the gas valve is opened and simultaneously a spark is produced. If an ionisation current is detected in the first
5 seconds, combustion occurs normally until the end of the demand. If not, the gas valve is closed and the fan
stopped, the burner being in safety mode. It must then be reset manually before lighting is attempted again.
◆FUNCTIONAL DIAGRAM (illustration D)
1. Air 3. Venturi 5. Offset adjustment screw 7. Air - gas mixture
2. Gaz 4. Fan 6. Gas flow a adjustement screw (CO2)
◆BURBER TUBE GAS (illustrations E / F / G)
The air-gas mixture leaving the gas valve - venturi assembly is forced into the burner tube gas and combustion
spreads evenly around the burner.
BG 2000-S burners are fitted with three different types of flame holder: two are made of stainless steel
(illustration E) for outputs less than 60 kW, the others (illustrations F / G) receive metal fibre (NIT) which distributes
the flame better. It also gives longer life and considerably lower pollution emissions.
Ionisation
Thermostat
Fan
Gas valve opens
Spark
15s
5s

3
EN
◆DESCRIPTION - BURNERS (illustrations H / I / J / K)
1. Burner flame holder
2. Ignition electrode
3. Gas valve
4. Venturi
5. Burner chamber plate seal
6. Burner chamber plate insulation
7. Ionisation electrode
8. Fan
■FITTING THE BURNER (illustrations L / M)
1. Remove the burner chamber plate.
2. Fit the BG 2000-S burner.
3. Insert the burner connector in the boiler socket.
4. Connect the gas to the burner, vent the air and test for gas leaks.
5. Start up the boiler.
■SETTINGS
Note:
•The offset value is set at the factory.
•The burner can only be fitted to one of the boilers in the table above.
•The CO2value given in the table above is valid only for natural gas; for propane, refer to the propane
conversion brochure. (code: 662Y0100)
■SETTING PROCEDURE IN CASE OF REPLACEMENT
◆FAN ROTATION SPEED
•Remove the green protective disk (1, illustration N) on the front of the fan.
•Remove the cover protecting the fan blades. (illustration P)
•Using a stroboscope (or any other suitable instrument) measure the rotation speed of the fan attached to the
motor shaft (3, illustration Q);adjust the fan speed to the value given in the setting parameter table by turning
the potentiometer screw (2, illustration O) (anticlockwise to reduce speed, clockwise to increase speed), after
the adjustment to replace the protection.
◆GAS FLOW RATE (illustration R)
•Measure burner combustion using an electronic flue gas analyser.
•Adjust the % CO2to the value given in the setting parameter table by turning the gas flow adjustment screw
(1, illustration R):anticlockwise for increased flow (rise in %CO2), clockwise for decreased flow (tall in % CO2).
1. Gas flow adjustement screw (CO2).
2. Pressure offset measurement.
3. Upstream gas pressure measurement.
4. Offset adjusting screw cover
9. Flame inspection window
10. Burner chamber plate
11. Burner plug
12. Potentiometer setting
13. Fan power plug
14. Gas supply
15. Relay
3000
4150
4150
3900
3450
4600
4600
4600
-0,5
-0,5
-0,5
0,0
0,0
0,0
0,0
0,0
9,0
9,0
9,0
9,0
9,0
9,0
9,0
9,0
25,0
35,0
35,0
45,0
55,0
69,9
69,9
85,0
Delta Perf. 25
Delta Perf. 35
Alfa Sprint S / SV
Delta Perf. 45
Delta Perf. 55
HM 60 N
HM 70 N
HM 100 N
BG 2000-S / 25
BG 2000-S / 35
BG 2000-S / 35
BG 2000-S / 45
BG 2000-S / 55
BG 2000-S / 60
BG 2000-S / 70
BG 2000-S / 100
Rpm
Offset
mbar
%
CO2
Output
kW
BoilersBurners
Warning!
To respect the parameters of the offset
adjustement mentioned again in the table
above.

4
EN
◆ELECTRODE ADJUSTMENT
●BG 2000-S / 25 / 35 / 45 / 55 (SV / 35) (illustration S)
Distance from electrode to burner (X): 4 to 6 mm.
●BG 2000-S / 60 / 70 / 100 (illustrations T / U)
Distance from electrode to burner (Y): 10 to 15 mm.
Electrode gap (Z): 2 to 5 mm.
■BURNER COMPONENTS
Electronic relay : Honeywell S4565 AD 2080-1 54768005
Fan:MVL RG 148/1200 3612 537D3028
Gas valve : Honeywell VK 4105 1014 537D4009
Venturi : Honeywell 002 (BG 2000-S/25 & - /35) 537D4034
001 (BG 2000-S/45) 537D6038
051 (BG 2000-S/55 & -S/60 & -S/70) 537D4028
Flame holder : Furigas Diam 63 45kW (BG 2000-S/25 & -S(V)/35 & -S/45) 537DZ004
Diam 63 55 kW (BG 2000-S/55) 537DZ006
Diam 63 + NIT (BG 2000-S/60 & -S/70) 537DZ021
Diam 98 + NIT (BG 2000-S/100) 537DZ019
■DIMENSIONS
■BURNER WIRING
●BG 2000-S / 25 / 35 / 45 / 55 (SV / 35) (illustration A)
●BG 2000-S / 60 / 70 (illustration B)
●BG 2000-S / 100 (illustration C)
■SERVICING THE BURNER (illustrations H / I / J / K)
1. After removing the burner, check the condition of the ignition (2) and ionisation (7) electrodes, insulation
(6) and burner chamber seal (5). Change them if necessary.
2. Check the condition of the flame holder (1).
3. Refit the burner and check that the burner lights.
4. Check the gas connection for leaks.
5. Ensure correct combustion.
248
248
248
248
248
342
342
228
228
228
228
228
248
248
295
295
310
310
375
375
375
BG 2000-S / 25
BG 2000-S(V) / 35
BG 2000-S / 45
BG 2000-S / 55
BG 2000-S / 60
BG 2000-S / 70
BG 2000-S / 100
CBAType
AB
C
Autres manuels pour BG 2000-S Series
1
Ce manuel convient aux modèles suivants
8
Table des matières
Langues :
Autres manuels ACV Brûleur